Plan Review Details - Permit 13010622
Plan Review Stops For Permit 13010622
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-03-12 Cont ID  
Sent By jgomez Date 2013-03-12 Time 10:12 Rev Time 0.00
Received By jgomez Date 2013-03-12 Time 09:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-02-08 Cont ID  
Sent By jgomez Date 2013-02-08 Time 17:25 Rev Time 0.00
Received By jgomez Date 2013-02-08 Time 17:25 Sent To  
Notes
2013-02-08 17:26:08RESIDENTIAL (R3) REPAIRS BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR NEW ROOF TO BE INSTALLED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6712

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2013-04-10 Cont ID  
Sent By shill Date 2013-04-10 Time 17:18 Rev Time 0.00
Received By shill Date 2013-04-10 Time 17:18 Sent To  
Notes
2013-04-10 17:18:46OK PER D HARVEY - SEE SIGNATURE/STAMPS ON PLAN
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2013-03-08 Cont ID  
Sent By rlecky Date 2013-03-08 Time 17:17 Rev Time 0.00
Received By rlecky Date 2013-03-08 Time 17:00 Sent To  
Notes
2013-03-08 17:14:5813010622
 5014 PINEWOOD AVE.
 RESIDENTIAL REPAIR
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 THE SUBMITTED ELECTRIC SERVICE RISER IS MISSING THE
 GROUNDING CONDUCTOR, GROUNDING ELECTRODE, THE
 INTERSYSTEM BOND AND THE ELECTRICAL SERVICE WIRE SIZES.
 NEC 215.5, 250.94
  
 PROVIDE PANEL SCHEDULES FOR EACH UNIT. NEC 215.5
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-02-11 Cont ID  
Sent By rlecky Date 2013-02-11 Time 10:33 Rev Time 0.00
Received By rlecky Date 2013-02-11 Time 10:18 Sent To  
Notes
2013-02-11 10:35:3113010622
 5014 PINEWOOD AVE.
 RESIDENTIAL REPAIR
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 IF THE RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE
 OR A FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED
 WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. 2010
 FBC R314, 315
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12
  
 THE BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
  
 PROVIDE AN ELECTRIC SERVICE RISER SHOWING THE PANEL,
 MAIN BREAKER, CONDUIT AND FEEDERS. PROVIDE PANEL
 SCHEDULES EACH UNIT. NEC 215.15
  
 A SEPARATE PERMIT IS REQUIRED FOR EACH STRUCTURE.
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-04-12 Cont ID  
Sent By jgomez Date 2013-04-12 Time 09:01 Rev Time 0.00
Received By jgomez Date 2013-04-04 Time 15:21 Sent To  
Notes
2013-04-05 15:22:14RE-SUBMITTAL SENT TO ELECTRICAL SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-03-12 Cont ID  
Sent By jgomez Date 2013-03-12 Time 10:12 Rev Time 0.00
Received By jgomez Date 2013-02-27 Time 11:09 Sent To  
Notes
2013-02-27 11:20:28R05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-02-11 Cont ID  
Sent By rlecky Date 2013-02-11 Time 11:24 Rev Time 0.00
Received By rlecky Date 2013-01-23 Time 17:20 Sent To  
Notes
2013-01-31 17:20:55SENT TO R1 SHELF FOR REVIEW. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-02-11 Cont ID  
Sent By jgomez Date 2013-02-11 Time 09:56 Rev Time 0.00
Received By jgomez Date 2013-02-11 Time 09:56 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2013-02-07 Cont ID  
Sent By mdekle Date 2013-02-07 Time   Rev Time 0.00
Received By mdekle Date 2013-01-23 Time 11:21 Sent To  
Notes
2013-01-28 11:21:31ENTERED ZONING STOP BY MISTAKE. JG.