| 2013-01-23 14:04:16 | RESIDENTIAL RE-ROOF BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- FLAT ROOF: |
| | A) FLAT ROOF ASSEMBLY ON PAGE 30 OF NOA 08-0410.09 |
| | SUBMITTED CAN'T BE USED IN THIS BUILDING. THE DESIGN |
| | PRESSURES ARE TOO LOW TOO MEET THE DESIGN PRESSURES |
| | REQUIRED BY R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL FOR |
| | THE PERIMETER AND CORNER AREAS. GENERAL LIMITATION #9 |
| | DOESN'T ALLOW NAIL ENHANCING. NEED TO SELECT AN |
| | APPROVED ASSEMBLY WITH GENERAL LIMITATION #7, WHICH |
| | ALLOWS NAIL ENHANCING BY MEANS OF RAS 117 CALCULATIONS. |
| | |
| | B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR |
| | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS |
| | REQUIRED BY GENERAL LIMITATION ON LAST PAGE OF NOA |
| | SUBMITTED. NEED CALCULATIONS TO MEET DESIGN PRESSURES |
| | REQUIRED BY SEC. R301.2.1.4.3. |
| | |
| | ***NOTE: DESIGN PROFESSIONAL DOING THE RAS 117 |
| | CALCULATIONS TO TAKE INTO CONSIDERATION THAT THIS |
| | BUILDING IS LOCATED ON EXPOSURE "C". SEE SEC. |
| | R301.2.1.4.3. |
| | |
| | 2- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| | 9N-3 FOR THE ADHESIVE TO BE USED FOR THE CONCRETE TILE. |
| | SEE CONCRETE TILE NOA SUBMITTED FOR LISTED ADHESIVE. |
| | |
| | 3- PROVIDE 2 COPIES OF EACH PRODUCT APPROVAL AS |
| | REQUIRED BY SEC.107.1 CITY AMENDMENTS TO FBC. |
| | |