Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-02-01 Cont ID  
Sent By rlecky Date 2013-02-01 Time 10:11 Rev Time 0.00
Received By rlecky Date 2013-02-01 Time 10:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-01-22 Cont ID  
Sent By rlecky Date 2013-01-22 Time 09:04 Rev Time 0.00
Received By rlecky Date 2013-01-22 Time 09:03 Sent To  
Notes
2013-01-22 09:38:26PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 PROVIDE AN ELECTRIC SERVICE RISER PLAN SHOWING THE NEW
 PANEL, MAIN BREAKER, GROUNDING, CONDUIT AND FEEDER. THE
 MAIN DISCONNECT SHALL BE LOCATED AT THE POINT OF
 SUPPLY. NEC 215.15, 230.70
  
 ELECTRICAL REPAIR OF AN EXISTING STRUCTURE IS REQUIRED
 TO INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-02-01 Cont ID  
Sent By rlecky Date 2013-02-01 Time 10:11 Rev Time 0.00
Received By rlecky Date 2013-01-29 Time 17:24 Sent To  
Notes
2013-01-29 17:25:13IN ELECTRIC BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-01-22 Cont ID  
Sent By rlecky Date 2013-01-22 Time 09:39 Rev Time 0.00
Received By rlecky Date 2013-01-18 Time 16:51 Sent To  
Notes
2013-01-18 16:52:00ELECTRIC BOX <$5K. JW