| 2013-01-17 15:29:16 | BUILDING PLAN REVIEW |
| | PERMIT:13010420 |
| | ADD: 550 S ROSEMARY, SUITE # 160 |
| | CONT: KCA CONSTRUCTION |
| | TEL: (561)361-1491 |
| | E-MAIL: [email protected] |
| | |
| | ARCHITET: ARTURO G. GRIEGO # AR 94011 |
| | |
| | ENGINEER: J. SAUVE PE FL #57585 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) THIS BUILDING IS CONSIDERED A THRESHOLD BUILDING, |
| | THE STRUCTURAL SHEETS INDICATE WORK TO BE COMPLETED |
| | UNDERTHE SCOPE OF THIS PERMIT WHICH WILL REQUIRE A |
| | THRESHOLD INSPECTOR. |
| | FL S. S. 553.71(7) " THRESHOLD BUILDING" MEANING ANY |
| | BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT IN |
| | HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY |
| | CLASSIFICATION AS DENIED IN THE FLORIDA BUILDING CODE |
| | WHICH EXCEEDS 5,000 SQ FT IN AREA AND AN OCCUPANT |
| | CONTENT OF GREATER THAN 500 PERSONS. |
| | |
| | 1A) THRESHOLD INSPECTION PLAN 109.3.6.1 THE ENFORCING |
| | AGENCY SHALL REQUIRE A SPECIAL INSPECTOR TO PERFORM |
| | STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING PURSUANT |
| | TO A WRITTEN STRUCTURAL INSPECTION PLAN PREPARED BY THE |
| | ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN MUST |
| | BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE |
| | ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A |
| | THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL |
| | INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION |
| | PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE |
| | ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED |
| | DOCUMENTS. |
| | |
| | 1B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S |
| | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| | REQUIRED BY THIS CODE. |
| | CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR |
| | PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION BEFORE |
| | THE PERMIT MAY BE ISSUED. |
| | |
| | 1C) THRESHOLD BLDG, REQUIRED STATEMENT: W.P.B. |
| | AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING WHICH |
| | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| | BEST OF THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, THE |
| | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 1D) A THRESHOLD PLAN REVIEW STOP WILL BE ADDED TO THE |
| | REQUIRED PLAN REVIEWS, WHEN ALL DOCUMENTS HAVE BEEN |
| | SUBMITTED THE CHIEF BUILDING INSPECTOR KEN CONRAD WILL |
| | PASS THIS REVIEW STOP.PLEASE CALL THE CITY OF WEST PALM |
| | BEACH'S AUTOMATED TELEPHONE INSPECTIONS LINE (561) |
| | 805-6700) FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF |
| | JOBSITE INSPECTIONS. |
| | |
| | 1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY |
| | FOR THIS TYPE OF CONCRETE RESTORATION. THIS MAY BE |
| | SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD: |
| | [email protected] |
| | |
| | 2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED |
| | HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL |
| | REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, AN |
| | INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN |
| | INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST MEETING |
| | THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | 2) LS1 NOR THE DOOR SCHEDULE FOUND ON A1.0 PROVIDE THE |
| | TYPE OF HARDWARE REQUIRED ON THE EGRESS DOORS, PLEASE |
| | REVIEW 2010 FBC-B 1008.1.10 FOR PANIC HARDWARE. |
| | |
| | 3) THIS REVIEW WILL BE UNDER THE 2010 EXST BLDG CODE |
| | CHAPTER 9 CHANGE OF OCCUPANCY SINCE THERE ARE TENANT |
| | SPACES GOING FROM MERCANTILE TO A2, ASSEMBLY AND NEED |
| | TO MEET THE REQUIREMENTS OF 2010 EXST. BLDG CODE |
| | 901.3.1 PARTIAL CHANGE OF OCCUPANCY. WHERE A PORTION OF |
| | AN EXISTING BUILDING IS CHANGED TO A NEW OCCUPANCY |
| | CLASSIFICATION SECTION 912 SHALL APPLY. |
| | |
| | 4) SHEET S1.1 INDICATES THE USE OF NON COMPRESSIBLE |
| | FOAM FILLER FOR USE IN THE STAGES, PLEASE PROVIDE |
| | MANUFACTURERS SPECIFICATION MEETING THE REQUIREMENTS OF |
| | 2010 FBC-B TABLE 1607.1(4). |
| | |
| | 5) 2010 EXISTING BUILDING CODE 912.8 ACCESSIBILITY, |
| | EXISTING BUILDINGS THAT UNDER GO A CHANGE OF OCCUPANCY |
| | SHALL COMPLY WITH THE PROVISIONS OF THE FLORIDA |
| | ACCESSIBILITY ACCESSIBILITY CODE.226.1 GENERAL. WHERE |
| | DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION OF |
| | FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES |
| | AND STANDING SPACES AT THE DINING SURFACES SHALL COMPLY |
| | WITH 902. IN ADDITION, WHERE WORK SURFACES ARE PROVIDED |
| | FOR USE BY OTHER THAN EMPLOYEES, AT LEAST 5 PERCENT |
| | SHALL COMPLY WITH 902. |
| | ACCESSIBILITY CODE 226.2 DISPERSION. DINING SURFACES |
| | AND WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE |
| | DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING |
| | DINING SURFACES AND WORK SURFACES. |
| | |
| | 6) THE STAGES DO NOT PROVIDE VERTICAL ACCESSIBILITY |
| | ACCESSIBILITY CODE, 201.1.1. |
| | |
| | 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 8) 01/18/2013 PLEASE SEE SHEET A4.1 AND THE 2010 FL |
| | ACCESSIBILTY CODE REQUIREMENT FOR AMBULATORY STALLS IN |
| | BOTH THE MENS AND WOMENS RESTROOMS SECTION 213.3.1. & |
| | 604.8.2 FOR AMBULATORY STALLS. |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |