Plan Review Details - Permit 13010383
Plan Review Stops For Permit 13010383
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-03-29 Cont ID  
Sent By rmcdouga Date 2013-03-29 Time 09:15 Rev Time 0.00
Received By rmcdouga Date 2013-03-28 Time 10:27 Sent To  
Notes
2013-03-29 09:21:28ALTHOUGH STRUCTURE IS LOCATED IN AN A5 FLOOD ZONE, THIS
 REMODEL IS NOT A SUBSTANCIAL IMPROVEMENT.
  
 THE ROOFING PRODUCT APPROVAL THAT WAS SUBMITTED IS
 MIAMI DADE NOA NO. 07-1120.13 FOR CEDAR SHAKES &
 SHINGLES. A REVISION IS REQUIRED FOR THE PRODUCT
 APPROVALS FOR THE BUILT-UP ROOFING THAT WAS NOT
 SUBMITTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-03-20 Cont ID  
Sent By rmcdouga Date 2013-03-20 Time 09:41 Rev Time 0.00
Received By rmcdouga Date 2013-03-19 Time 15:08 Sent To  
Notes
2013-03-20 09:13:442010 FBC
  
 DENIED BY BUILDING
  
 1) THE TWO STRUCTURAL SHEETS THAT WERE SUBMITTED HAVE
 COPIED SIGNATURES OF THE ENGINEER IN THE TITLE BLOCK.
 FAC 61G15-23.002 REQUIRES THE ENGINEER'S ORIGINAL WET
 SIGNATURE. SUBMIT SIGNED AND SEALED STRUCTURAL
 DRAWINGS.
  
 2) ON SHEET 2 OF THE STRUCTURAL DRAWINGS WALL SECTION 1
 SPECIFIES 1 X 8 T&G FOR THE ROOF SHEATHING. THIS IS NOT
 ACCEPTABLE FOR 36" RAFTER SPACING. FBCR TABLE R803.1
 REQUIRES 1-1/2" T & G FOR THIS SPAN. PLEASE CORRECT.
 NOTE: THE SPECIFIED FASTENERS WILL NEED TO BE REVISED
 FOR THE THICKER LUMBER SHEATHING.
  
 3) SPECIFY THE ROOF PITCH ON THE PLANS. FBCR905.7.2
 WOOD SHINGLES REQUIRE A MINIMUM 3/12 SLOPE AND 905.8.2
 WOOD SHAKES REQUIRE A MINIMUM 4/12 SLOPE.
  
 4) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 CASEMENT WINDOWS, FIXED GLASS WINDOWS AND BUILT-UP
 ROOFING, SPECIFIED ON THE PLANS, THAT HAVE BEEN
 REVIEWED AND APPROVED BY THE DESIGNER OF RECORD. DCA
 RULE 9N-3 AND CITY AMENDMENTS 107.3.4.1
  
 5) THE STRUCTURAL DRAWINGS SPECIFY THREADED RODS
 ATTACHING THE RAFTERS AND GABLE FRAMING MEMBERS.
 HOWEVER, THE DRAWINGS APPEAR TO SHOW LAG BOLTS OR LARGE
 SCREWS BECAUSE THEY DO NOT APPEAR TO EXTEND ALL THE WAY
 THROUGH THE LUMBER IN ORDER TO BE BOLTED TOGETHER.
 PLEASE CLARIFY. CITY AMENDMENTS 107.2.1 AND FBC R301.1
  
 6) THE ENERGY CALCULATION FORM IS REQUIRED TO BE SIGNED
 BY THE OWNER/AGENT. FBC ENERGY CONSERVATION SECTION
 405.4
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-01-31 Cont ID  
Sent By rmcdouga Date 2013-01-31 Time 14:16 Rev Time 0.00
Received By rmcdouga Date 2013-01-29 Time 16:09 Sent To  
Notes
2013-01-31 14:16:532010 FBC
  
 DENIED BY BUILDING
  
 1) SHOW COMPLIANCE WITH FBC ENERGY CONSERVATION SECTION
 401.2 FOR THE NEW BREAKFAST ROOM.
  
 2) SHOW COMPLIANCE WITH FBC R314.3.1 FOR SMOKE ALARMS.
  
 3) UPDATE GENERAL NOTES ON SHEET CVR TO REFLECT THE
 2010 FBC AND THE REFERENCED STANDARDS IN CHAPTER 43 OF
 FBC RESIDENTIAL. ASTM C94-07, ACI - 08 EDITIONS, AND
 2010 FBC FOR #S 40 AND 41.
  
 4) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 EXTERIOR DOORS, WINDOWS, ROOFING MATERIAL, TRUSS
 ANCHORS AND CONNECTORS AS REQUIRED BY DCA RULE 9N-3.
  
 5) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT. CITY AMENDMENTS 107.3.4.1.
  
 6) PROVIDE STRUCTURAL DETAILS FOR THE CONSTRUCTION OF
 THE ARCH AT THE GABLE OF THE SECOND FLOOR BALCONY. CITY
 AMENDMENTS 107.2.1
  
 7) THE PLANS SHOW A FRENCH DOOR AT THE REAR OF THE
 BREAKFAST ROOM THAT OPENS OUT OVER THE EXISTING POOL.
 INDICATE HOW THIS WILL COMPLY WITH FBCR 311.3 WHICH
 REQUIRES A FLOOR OR LANDING ON EACH SIDE OF EACH
 EXTERIOR DOOR.
  
 8) SHOW COMPLIANCE WITH FBCR 4101.17 FOR RESIDENTIAL
 SWIMMING POOL BARRIER REQUIREMENT AT NEW ADDITION.
  
 9) THE STRUCTURE IS LOCATED IN AN A5 FLOOD ZONE WHICH
 REQUIRES THE ADDITION TO HAVE A FINISH FLOOR ELEVATION
 OF 7'-6" BFE WHICH INCLUDES A 6" FREEBOARD REQUIRED BY
 THE CITY'S MUNICIPAL CODE. SPECIFY THE FINISH FLOOR
 ELEVATION ON THE PLANS AND PROVIDE AN ELEVATION
 CERTIFICATE WITH THE PROPOSED FINISH FLOOR ELEVATION.
 FBCR 322 AND CITY FLOOD PLAIN ORDINANCE
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-03-08 Cont ID  
Sent By rlecky Date 2013-03-08 Time 12:24 Rev Time 0.00
Received By rlecky Date 2013-03-08 Time 12:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-02-01 Cont ID  
Sent By rlecky Date 2013-02-01 Time 12:01 Rev Time 0.00
Received By rlecky Date 2013-02-01 Time 10:51 Sent To  
Notes
2013-02-01 12:12:2013010383
 3024 WASHINGTON ROAD
 RESIDENTIAL ADDITION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12
  
 RECEPTACLES IN THE BREAKFAST ROOM SHALL BE SERVED FROM
 ONE OR MORE 20 AMPERE BRANCH CIRCUITS. NEC 210.52
 (B)(1)
  
 BALCONIES, DECKS AND PORCHES SHALL HAVE AT LEAST ONE
 GFCI PROTECTED RECEPTACLE OUTLET. NEC 210.52 (E)(3)
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2013-02-15 Cont ID  
Sent By fmittner Date 2013-02-15 Time 16:17 Rev Time 0.00
Received By fmittner Date 2013-02-15 Time 16:17 Sent To  
Notes
2013-02-13 17:18:37NEW SHEETS SUBMITTED. JG.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2013-01-17 Cont ID  
Sent By fmittner Date 2013-01-17 Time 15:34 Rev Time 0.00
Received By fmittner Date 2013-01-17 Time 15:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-03-29 Cont ID  
Sent By rmcdouga Date 2013-03-29 Time 09:15 Rev Time 0.00
Received By rmcdouga Date 2013-03-25 Time 14:19 Sent To  
Notes
2013-03-25 14:20:32SENT TO R MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-03-20 Cont ID  
Sent By rmcdouga Date 2013-03-20 Time 09:45 Rev Time 0.00
Received By rmcdouga Date 2013-02-13 Time 17:11 Sent To  
Notes
2013-02-13 17:11:35SENT TO R9 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-02-01 Cont ID  
Sent By rlecky Date 2013-02-01 Time 12:12 Rev Time 0.00
Received By rlecky Date 2013-01-15 Time 17:04 Sent To  
Notes
2013-01-17 17:04:56SENT TO R7 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2013-04-01 Cont ID  
Sent By rmcdouga Date 2013-04-01 Time 16:25 Rev Time 0.00
Received By rmcdouga Date 2013-04-01 Time 16:25 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2013-03-20 Cont ID  
Sent By rmcdouga Date 2013-03-20 Time 09:41 Rev Time 0.00
Received By rmcdouga Date 2013-03-20 Time 09:41 Sent To  
Notes
2013-03-20 09:45:53AN IMPACT FEE REVIEW BY PALM BEACH COUNTY IS REQUIRED.
 ONE SET OF APPROVED PLANS ARE TO BE SIGNED OUT AND
 TAKEN TO PALM BEACH COUNTY FOR REVIEW. THE REVIEWED
 PLANS WITH THE IMPACT REVIEW STAMP ON THEM AND A COPY
 OF THE PAID RECEIPT ARE TO BE RETURNED TO THE WEST PALM
 BEACH BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT IS
 ISSUED.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-01-31 Cont ID  
Sent By rmcdouga Date 2013-01-31 Time 10:31 Rev Time 0.00
Received By rmcdouga Date 2013-01-31 Time 10:31 Sent To  
Notes
2013-01-31 10:32:41IMPACT FEE REVIEW BY PALM BEACH COUNTY IS REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2013-03-28 Cont ID  
Sent By rmcdouga Date 2013-03-28 Time 11:22 Rev Time 0.00
Received By rmcdouga Date 2013-03-28 Time 11:22 Sent To  
Notes
2013-03-28 11:24:19NO MECHANICAL PERMIT WAS APPLIED FOR AT THIS TIME. A
 SEPARATE PERMIT, APPLICATION AND REVIEW IS REQUIRED FOR
 A MECHANICAL PERMIT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-03-15 Cont ID  
Sent By hmoser Date 2013-03-15 Time 15:23 Rev Time 0.00
Received By hmoser Date 2013-03-15 Time 15:23 Sent To  
Notes
2013-03-15 15:24:34NO MECHANICAL PLANS SUBMITTED.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2013-02-15 Cont ID  
Sent By fmittner Date 2013-02-15 Time 16:17 Rev Time 0.00
Received By fmittner Date 2013-02-15 Time 16:17 Sent To  
Notes
2013-02-13 17:18:58NEW SHEETS SUBMITTED. JG.

Review Stop Z ZONING
Rev No 1 Status P Date 2013-01-17 Cont ID  
Sent By fmittner Date 2013-01-17 Time 15:34 Rev Time 0.00
Received By fmittner Date 2013-01-17 Time 15:34 Sent To  
Notes
2013-01-17 15:35:09TO JULIO -FM