Plan Review Details - Permit 13010358
Plan Review Stops For Permit 13010358
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2013-06-04 Cont ID  
Sent By jgomez Date 2013-06-04 Time 08:15 Rev Time 0.00
Received By jgomez Date 2013-06-04 Time 08:15 Sent To  
Notes
2013-06-04 11:13:45BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- ENGINEER OF RECORD TO REVISE ROOF TILE FASTENING
 INFORMATION ON PRODUCT APPROVAL TABLE ON SHEET A2.0 TO
 MATCH PRODUCT APPROVAL SUBMITTED. THE DESIGN PRESSURES
 AND PADDY SIZE DON'T MATCH PRODUCT APPROVAL SUBMITTED.
  
 2- PROVIDE BUILDING INSPECTOR WITH COMPLETE TRUSS
 PACKAGE WHEN REQUESTING ROOF FRAMING INSPECTION. TRUSS
 PACKAGE TO HAVE: A)TRUSS ENGINEER'S ORIGINAL SEAL AND
 SIGNATURE. B) ENGINEER TITLE BLOCK WITH NAME OF
 PROJECT, NAME OF ENGINEER, ADDRESS, LICENSE NUMBER AND
 DATE OF SIGNING AND SEALING DRAWINGS .
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2013-03-27 Cont ID  
Sent By jgomez Date 2013-03-27 Time 16:27 Rev Time 0.00
Received By jgomez Date 2013-03-27 Time 15:06 Sent To  
Notes
2013-03-27 15:34:59RESIDENTIAL (R3) ADDITION BUILDING REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ROOF COVERING.
  
 ***NOTE: PLANTATION ROOF TILE NOA 10-0804.15 SUBMITTED
 WAS SUPERSEDED BY MIAMI-DADE. VISIT THE MIAMI-DADE
 WEBSITE AND DOWNLOAD CURRENT NOA.
  
 B) SELF-ADHESIVE UNDERLAYMENT FOR NEW CONCRETE ROOF
 TILE AS SPECIFIED BY THE ENGINEER OF RECORD.
  
 ***NOTE: BORAL ROOF UNDERLAYMENTS FL14317-R1 SUBMITTED
 CAN'T BE USED IN THIS BUILDING. ACCORDING TO SEC.
 5.5.2.1 OF THE FLORIDA PRODUCT APPROVAL SUBMITTED THE
 MAXIMUM DESIGN PRESSURE IS -45PSF. NEED PRODUCT
 APPROVAL THAT MEETS OR EXCEEDS DESIGN PRESSURES FOR
 ROOF PERIMETER AND CORNER AREAS. SEE PLANS FOR
 CALCULATED DESIGN PRESSURES THAT NEED TO BE MET.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL OF THE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
 TO FBC.
  
 3- ENGINEER OF RECORD TO PROVIDE COMPLETE ROOF ASSEMBLY
 SPECIFICATIONS AS REQUIRED BY SEC. 107.2.1.2 CITY
 AMENDMENTS. SPECIFY ROOF TILE FASTENING METHOD.
 DRAWINGS SUBMITTED DON'T SPECIFY TILE FASTENING METHOD.
  
 4- CLARIFY ROOF SHEATHING THICKNESS. ROOF SHEATHING
 NOTE ON SHEET A2.0 SPECIFIES 19/32" CDX PLYWOOD ROOF
 SHEATHING, WHILE, CROSS SECTIONS 1/A5.0 AND 2/A5.0
 SPECIFIES 3/4" PLYWOOD SHEATHING. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 5- ENGINEER OF RECORD TO SPECIFY ON PLANS ROOF
 VENTILATION AS REQUIRED BY SEC. R806. SPECIFY LOCATION
 AND SIZE.
  
 6- TRUSS PACKAGE SUBMITTED NEED TO HAVE ENGINEER'S
 ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY SEC.
 61G15-23.002 FLORIDA ADMINISTRATIVE CODE AND CHAPTER
 471 FLORIDA STATUTE.
 ***NOTE: PROVIDE TRUSS PACKAGE WITH ENGINEER'S SEAL AND
 SIGNATURE TO THE BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-03-26 Cont ID  
Sent By jgomez Date 2013-03-26 Time 14:05 Rev Time 0.00
Received By jgomez Date 2013-03-26 Time 14:05 Sent To  
Notes
2013-03-26 15:26:02RESIDENTIAL (R3) ADDITION BUILDING REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ROOF COVERING.
  
 ***NOTE: PLANTATION ROOF TILE NOA 10-0804.15 SUBMITTED
 WAS SUPERSEDED BY MIAMI-DADE. VISIT THE MIAMI-DADE
 WEBSITE AND DOWNLOAD CURRENT NOA.
  
 B) SELF-ADHESIVE UNDERLAYMENT FOR NEW CONCRETE ROOF
 TILE AS SPECIFIED BY THE ENGINEER OF RECORD.
  
 ***NOTE: BORAL ROOF UNDERLAYMENTS FL14317-R1 SUBMITTED
 CAN'T BE USED IN THIS BUILDING. ACCORDING TO SEC.
 5.5.2.1 OF THE FLORIDA PRODUCT APPROVAL SUBMITTED THE
 MAXIMUM DESIGN PRESSURE IS -45PSF. NEED PRODUCT
 APPROVAL THAT MEETS OR EXCEEDS DESIGN PRESSURES FOR
 ROOF PERIMETER AND CORNER AREAS. SEE PLANS FOR
 CALCULATED DESIGN PRESSURES THAT NEED TO BE MET.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL OF THE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
 TO FBC.
  
 3- ENGINEER OF RECORD TO PROVIDE COMPLETE ROOF ASSEMBLY
 SPECIFICATIONS AS REQUIRED BY SEC. 107.2.1.2 CITY
 AMENDMENTS. SPECIFY ROOF TILE FASTENING METHOD.
 DRAWINGS SUBMITTED DON'T SPECIFY TILE FASTENING METHOD.
  
 4- CLARIFY ROOF SHEATHING THICKNESS. ROOF SHEATHING
 NOTE ON SHEET A2.0 SPECIFIES 19/32" CDX PLYWOOD ROOF
 SHEATHING, WHILE, CROSS SECTIONS 1/A5.0 AND 2/A5.0
 SPECIFIES 3/4" PLYWOOD SHEATHING. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 5- ENGINEER OF RECORD TO SPECIFY ON PLANS ROOF
 VENTILATION AS REQUIRED BY SEC. R806. SPECIFY LOCATION
 AND SIZE.
  
 6- TRUSS PACKAGE SUBMITTED NEED TO HAVE ENGINEER'S
 ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY SEC.
 61G15-23.002 FLORIDA ADMINISTRATIVE CODE AND CHAPTER
 471 FLORIDA STATUTE.
 ***NOTE: PROVIDE TRUSS PACKAGE WITH ENGINEER'S SEAL AND
 SIGNATURE TO THE BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-02-04 Cont ID  
Sent By jgomez Date 2013-02-04 Time 17:30 Rev Time 0.00
Received By jgomez Date 2013-02-04 Time 15:18 Sent To  
Notes
2013-02-04 17:30:02RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- ACCORDING TO SEC. R301.2.1.4.3 OF 2010
 FBC-RESIDENTIAL THIS BUILDING IS LOCATED ON EXPOSURE
 "D" NOT "B". REVISE DESIGN SPECIFICATIONS AND REVISE
 ALL THE DESIGN PRESSURES AS REQUIRED.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ROOF COVERING. (CONCRETE TILE ACCORDING TO PROPERTY
 APPRAISAL).
 B) CONCRETE TILE ADHESIVE IF USING IT FOR THE
 INSTALLATION OF TILE. SEE TILE PRODUCT APPROVAL FOR
 LISTED PRODUCTS.
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS/DETAILS. ***NOTE; PROVIDE ONLY THE PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR.
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO FBC.
  
 4- ENGINEER OF RECORD TO PROVIDE COMPLETE ROOF ASSEMBLY
 SPECIFICATIONS AS REQUIRED BY SEC. 107.2.1.2 CITY
 AMENDMENTS. SPECIFY ROOF TILE FASTENING METHOD AND THE
 DESIGN PRESSURES.
  
 5- PROVIDE ROOF SHEATHING COMPLETE SPECIFICATIONS.
 SPECIFY WOOD TYPE, THICKNESS AND FASTENING AS REQUIRED
 BY SEC. R803.2.3.1 OF 2010 FBC-RESIDENTIAL. ***NOTE:
 MIN. 8D RING SHANK NAILS ARE REQUIRED AND CORNER AREAS
 (4'-0" MIN.) REQUIRE NAILING AT 4"O.C.
  
 6- SPECIFY ON PLANS CARBON MONOXIDE ALARMS AS REQUIRED
 BY SEC. R315 OF 2010 FBC-RESIDENTIAL.
  
 7- SPECIFY ON PLANS ROOF VENTILATION AS REQUIRED BY
 SEC. R806.
  
 8- SPECIFY ON PLANS ATTIC ACCESS FOR NEW ROOF AREA AS
 REQUIRED BY SEC. R807.
  
 9- ENGINEER OF RECORD TO PROVIDE AL THE INFORMATION ON
 THE DRAWINGS TITLE BLOCK AS REQUIRED BY SEC.
 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE AND CHAPTER
 471 FLORIDA STATUTE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-03-22 Cont ID  
Sent By rlecky Date 2013-03-22 Time 16:19 Rev Time 0.00
Received By rlecky Date 2013-03-22 Time 16:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-02-01 Cont ID  
Sent By rlecky Date 2013-02-01 Time 12:33 Rev Time 0.00
Received By rlecky Date 2013-02-01 Time 12:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2013-06-04 Cont ID  
Sent By jgomez Date 2013-06-04 Time 11:13 Rev Time 0.00
Received By jgomez Date 2013-05-24 Time 11:39 Sent To  
Notes
2013-05-25 11:40:00GAVE TO JULIO

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-03-27 Cont ID  
Sent By jgomez Date 2013-03-27 Time 15:06 Rev Time 0.00
Received By jgomez Date 2013-03-27 Time 15:06 Sent To  
Notes
2013-03-27 14:51:04PRODUCT APPROVALS SUBMITTED BY E-MAIL. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-03-27 Cont ID  
Sent By jgomez Date 2013-03-27 Time 08:52 Rev Time 0.00
Received By jgomez Date 2013-03-21 Time 09:40 Sent To  
Notes
2013-03-21 09:40:53R06

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-02-04 Cont ID  
Sent By jgomez Date 2013-02-04 Time 17:30 Rev Time 0.00
Received By jgomez Date 2013-01-15 Time 14:19 Sent To  
Notes
2013-01-16 14:20:24SENT TO R2 SHELF FOR REVIEW. JG.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2013-08-15 Cont ID  
Sent By jgomez Date 2013-08-15 Time 14:00 Rev Time 0.00
Received By jgomez Date 2013-08-15 Time 14:00 Sent To  
Notes
2013-08-15 14:01:31NEED ROOFING CONTRACTOR FOR THE ROOFING SUB-PERMIT.
 PRODUCT APPROVALS ALREADY APPROVED WITH MASTER PERMIT.
 JG.

Review Stop Z ZONING
Rev No 1 Status P Date 2013-01-18 Cont ID  
Sent By mdekle Date 2013-01-18 Time   Rev Time  
Received By mdekle Date 2013-01-18 Time   Sent To  
Notes
2013-01-17 10:55:441/17/13