Plan Review Details - Permit 13010327
Plan Review Stops For Permit 13010327
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2013-05-15 Cont ID  
Sent By shill Date 2013-05-15 Time 09:35 Rev Time 0.00
Received By shill Date 2013-05-15 Time 09:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2013-04-17 Cont ID  
Sent By shill Date 2013-04-17 Time 14:59 Rev Time 0.00
Received By shill Date 2013-04-17 Time 14:59 Sent To  
Notes
2013-04-17 15:08:26****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. SEE FBC TABLE 602 REGARDING FIRE RESISTANCE
 REQUIREMENTS AND REVISE PLANS TO SHOW COMPLIANCE; BOTH
 DISTANCE TO PROPERTY LINES AS WELL AS DISTANCE TO
 ASSUMED PROPERTY LINE BETWEEN PROPOSED SHED AND
 EXISTING BUILDING. INCLUDE ALL INFORMATION REQUIRED TO
 SHOW CODE COMPLIANCE SUCH AS BUILDING TYPE (FBC CHAPTER
 6), AREA, OCCUPANCY CLASSIFICATION (FBC CHAPTER 3).
  
 PER CONVERSATION WITH CONTRACTOR, THIS WILL BE
 REDLINED.
  
 2. SEE FBC TABLE 602. TYPE IIB STRUCTURE, 5' FROM
 PROPERTY LINE REQUIRES A 1 HOUR RATED WALL. THE DETAIL
 PROVIDED IS FOR A NON BEARING WALL, EXPOSURE TO INSIDE
 ONLY. FBC 705.5, RATED WALLS LESS THAN 10' FROM THE
 PROPERTY LINE ARE TO BE RATED FROM BOTH INSIDE AND
 OUTSIDE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2013-02-26 Cont ID  
Sent By shill Date 2013-02-26 Time 13:15 Rev Time 0.00
Received By shill Date 2013-02-26 Time 13:15 Sent To  
Notes
2013-02-26 13:16:30****CORRECTIONS****
 2/22/2013 RESUBMITTAL
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. OK
  
 2. SEE FBC TABLE 602 REGARDING FIRE RESISTANCE
 REQUIREMENTS AND REVISE PLANS TO SHOW COMPLIANCE; BOTH
 DISTANCE TO PROPERTY LINES AS WELL AS DISTANCE TO
 ASSUMED PROPERTY LINE BETWEEN PROPOSED SHED AND
 EXISTING BUILDING. INCLUDE ALL INFORMATION REQUIRED TO
 SHOW CODE COMPLIANCE SUCH AS BUILDING TYPE (FBC CHAPTER
 6), AREA, OCCUPANCY CLASSIFICATION (FBC CHAPTER 3).
  
 3RD REVIEW:
  
 SEE FBC TABLE 602. TYPE IIB STRUCTURE, 5' FROM PROPERTY
 LINE REQUIRES A 1 HOUR RATED WALL. PROVIDE A DETAIL OR
 CHANGE PROPOSED LOCATION.
  
 DISTANCE TO ASSUMED PROPERTY LINE BETWEEN THE TWO
 STRUCTURES ON THE SAME LOT NOT PROVIDED. NO INFORMATION
 REGARDING THE EXISTING BUILDING WAS PROVIDED.
  
 NEW COMMENT:
  
 3. PLEASE PROVIDE AN ARCHITECTURAL DETAIL OF THE FOUR
 SIDES OF THE PROPOSED SHED WHICH INCLUDES OPENINGS
 (DOORS AND/OR WINDOWS) AND ORIENTATION OF THE PROPOSED
 SHED (INDICATE NORTH, SOUTH, EAST, WEST ELEVATIONS).
 SEE FBC TABLE 602, TABLE 705.8.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-02-26 Cont ID  
Sent By shill Date 2013-02-26 Time 12:42 Rev Time 0.00
Received By shill Date 2013-02-26 Time 12:42 Sent To  
Notes
2013-02-26 12:50:44****CORRECTIONS****
 2/13/2013 RESUBMITTAL
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. OK
  
 2. SEE FBC TABLE 602 REGARDING FIRE RESISTANCE
 REQUIREMENTS AND REVISE PLANS TO SHOW COMPLIANCE; BOTH
 DISTANCE TO PROPERTY LINES AS WELL AS DISTANCE TO
 ASSUMED PROPERTY LINE BETWEEN PROPOSED SHED AND
 EXISTING BUILDING. INCLUDE ALL INFORMATION REQUIRED TO
 SHOW CODE COMPLIANCE SUCH AS BUILDING TYPE (FBC CHAPTER
 6), AREA, OCCUPANCY CLASSIFICATION (FBC CHAPTER 3).
  
 2ND REVIEW:
  
 SEE FBC TABLE 602. TYPE IIB STRUCTURE, 3' FROM PROPERTY
 LINE REQUIRES A 2 HOUR RATED WALL. PROVIDE A DETAIL OR
 CHANGE PROPOSED LOCATION.
  
 DISTANCE TO ASSUMED PROPERTY LINE BETWEEN THE TWO
 STRUCTURES ON THE SAME LOT NOT PROVIDED. NO INFORMATION
 REGARDING THE EXISTING BUILDING WAS PROVIDED.
  
 NEW COMMENT:
  
 3. PLEASE PROVIDE AN ARCHITECTURAL DETAIL OF THE FOUR
 SIDES OF THE PROPOSED SHED WHICH INCLUDES OPENINGS
 (DOORS AND/OR WINDOWS) AND ORIENTATION OF THE PROPOSED
 SHED (INDICATE NORTH, SOUTH, EAST, WEST ELEVATIONS).
 SEE FBC TABLE 602, TABLE 705.8.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-02-01 Cont ID  
Sent By shill Date 2013-02-01 Time 14:56 Rev Time 0.00
Received By shill Date 2013-02-01 Time 14:56 Sent To  
Notes
2013-02-01 15:06:29****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. PROVIDE ENGINEERING FOR THE SHED, FBC 1609. IF THE
 SHED HAS A DCA APPROVAL, PROVIDE THE APPROVAL FROM THE
 WEBSITE WWW.FLORIDABUILDING.ORG. THIS SHOULD INCLUDE
 THE COVER SHEET AND ALL DRAWINGS STAMPED BY THE STATE.
  
 2. SEE FBC TABLE 602 REGARDING FIRE RESISTANCE
 REQUIREMENTS AND REVISE PLANS TO SHOW COMPLIANCE; BOTH
 DISTANCE TO PROPERTY LINES AS WELL AS DISTANCE TO
 ASSUMED PROPERTY LINE BETWEEN PROPOSED SHED AND
 EXISTING BUILDING. INCLUDE ALL INFORMATION REQUIRED TO
 SHOW CODE COMPLIANCE SUCH AS BUILDING TYPE (FBC CHAPTER
 6), AREA, OCCUPANCY CLASSIFICATION (FBC CHAPTER 3).

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2013-05-15 Cont ID  
Sent By shill Date 2013-04-17 Time 09:34 Rev Time 0.00
Received By shill Date 2013-04-11 Time 13:25 Sent To  
Notes
2013-04-12 13:25:35SENT TO ZONING BOX.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2013-04-17 Cont ID  
Sent By shill Date 2013-04-17 Time 15:16 Rev Time 0.00
Received By shill Date 2013-04-01 Time 09:08 Sent To  
Notes
2013-04-01 09:08:31TO ZONING
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-02-26 Cont ID  
Sent By shill Date 2013-02-26 Time 13:16 Rev Time 0.00
Received By shill Date 2013-02-22 Time 13:44 Sent To  
Notes
2013-02-22 13:45:02TO MD DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-02-26 Cont ID  
Sent By shill Date 2013-02-26 Time 12:50 Rev Time 0.00
Received By shill Date 2013-02-13 Time 16:01 Sent To  
Notes
2013-02-14 16:02:33SENT TO ZONING SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-02-01 Cont ID  
Sent By shill Date 2013-02-01 Time 15:08 Rev Time 0.00
Received By shill Date 2013-01-14 Time 15:06 Sent To  
Notes
2013-01-14 15:06:35ZONING

Review Stop Z ZONING
Rev No 4 Status P Date 2013-04-09 Cont ID  
Sent By mdekle Date 2013-04-09 Time   Rev Time 0.00
Received By mdekle Date 2013-04-02 Time   Sent To B
Notes
2013-04-09 13:11:59FIVE FOOT MINIMUM SETBACKS DEPICTED ON THE PLAN.

Review Stop Z ZONING
Rev No 3 Status F Date 2013-02-22 Cont ID  
Sent By mdekle Date 2013-02-22 Time   Rev Time 0.00
Received By mdekle Date 2013-02-22 Time   Sent To B
Notes
2013-02-22 14:39:33PLANNING AND ZONING: **** FAILED ****
  
 1. BASED ON THE RESPONSE COMMENTS SUBMITTED; THE
 PROPOSED REAR SETBACK REDUCTION REQUIRES A VARIANCE VIA
 THE CITY'S ZONING BOARD OF APPEALS. PLEASE CONTACT
 STAFF TO SCHEDULE A PRE APPLICATION MEETING.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME
 AND/OR CONSULT THE CITY?S ZONING AND LAND
 DEVELOPMENT REGULATIONS ONLINE @WWW.MUNICODE.COM.
  
 MURRIAH DEKLE, MPA, PLANNER
 PLANNING & ZONING DIVISION
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2013-02-20 Cont ID  
Sent By mdekle Date 2013-02-20 Time   Rev Time 0.00
Received By mdekle Date 2013-02-15 Time   Sent To B
Notes
2013-02-20 16:32:53PLANNING AND ZONING: **** FAILED **** REPEAT COMMENTS
  
 PLEASE RESPOND TO COMMENTS IN WRITING AND SUBMIT AS
 PART OF THE RESUBMITTAL PACKET. THE SUBMITTAL OF THE
 REQUESTED INFORMATION MAY GENERATE ADDITIONAL COMMENTS.
  
 1. THE PROPOSED LOCATION DOES NOT MEET THE REQUIRED
 BUILDING SETBACKS AS SET FORTH IN SECTION 94-304 (B)(2)
 PLEASE REVISE ACCORDINGLY.
 2. THE PROPOSED LOCATION APPEARS TO CONFLICT WITH THE
 REQURIED CAR PARKING AREA. PLEASE BE ADVISED; THE
 PROPERTY MUST PROVIDE THE MINIMUM NUMBER OF PARKING
 SPACES AS REQUIRED PER SECTION 94-486 OF THE CITY'S
 ZONING AND LAND DEVELOPMENT CODE.
 3. THE APPLICANT IS REQUESTED TO PROVIDE CLARIFICATION
 REGARDING:
 A. THE INTENDED USE FOR THE BUILDING.
 B. THE PROPOSED HEIGHT OF THE BUILDING.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME
 AND/OR CONSULT THE CITY?S ZONING AND LAND
 DEVELOPMENT REGULATIONS ONLINE @WWW.MUNICODE.COM.
  
 MURRIAH DEKLE, MPA, PLANNER
 PLANNING & ZONING DIVISION
 TEL: (561) 822-1442
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2013-01-17 Cont ID  
Sent By mdekle Date 2013-01-17 Time   Rev Time  
Received By mdekle Date 2013-01-14 Time   Sent To B
Notes
2013-01-17 15:25:15PLANNING AND ZONING: **** FAILED ****
  
 PLEASE RESPOND TO COMMENTS IN WRITING AND SUBMIT AS
 PART OF THE RESUBMITTAL PACKET. THE SUBMITTAL OF THE
 REQUESTED INFORMATION MAY GENERATE ADDITIONAL COMMENTS.
 1. THE PROPOSED LOCATION DOES NOT MEET THE REQUIRED
 BUILDING SETBACKS AS SET FORTH IN SECTION 94-304 (B)(2)
 PLEASE REVISE ACCORDINGLY.
 2. THE PROPOSED LOCATION APPEARS TO CONFLICT WITH THE
 REQURIED CAR PARKING AREA. PLEASE BE ADVISED; THE
 PROPERTY MUST PROVIDE THE MINIMUM NUMBER OF PARKING
 SPACES AS REQUIRED PER SECTION 94-486 OF THE CITY'S
 ZONING AND LAND DEVELOPMENT CODE.
 3. THE APPLICANT IS REQUESTED TO PROVIDE CLARIFICATION
 REGARDING:
 A. THE INTENDED USE FOR THE BUILDING.
 B. THE PROPOSED HEIGHT OF THE BUILDING.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME
 AND/OR CONSULT THE CITY?S ZONING AND LAND
 DEVELOPMENT REGULATIONS ONLINE @WWW.MUNICODE.COM.
  
 MURRIAH DEKLE, MPA, PLANNER
 PLANNING & ZONING DIVISION
 TEL: (561) 822-1442
 EMAIL: [email protected]
  