Plan Review Details - Permit 13010149
Plan Review Stops For Permit 13010149
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-01-10 Cont ID  
Sent By wjolin Date 2013-01-10 Time 13:23 Rev Time 0.00
Received By wjolin Date 2013-01-10 Time 11:55 Sent To M
Notes
2013-01-10 12:58:01701 SOUTH OLIVE AVENUE - SUITE 108 & 111
 PERMIT #13010149
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISION*****
  
 THE DRAWING LAYER CONTAINING THE HYDRAULIC NODE
 INFORMATION APPEARS TO BE FROZEN. SHOW THE HYDRAULIC
 NODES SO THE HYDRAULIC CALCULATIONS CAN BE REVIEWED
 APPROPRIATELY.
  
 FOR SYSTEM PRESSURES EXCEEDING 100 PSI, ARMOVERS AND
 END OF BRANCH LINE PENDENT SPRINKLERS SHALL BE
 PROTECTED FROM UPWARD MOVEMENT. INDICATE THE HANGER
 TYPE OR METHOD TO BE USED FOR RESTRAINING UPWARD
 MOVEMENT.
  
 INDICATE THE MAXIMUM SYSTEM WORKING PRESSURE AND THE
 HYDROSTATIC TEST PRESSURE ASSOCIATED WITH THIS FLOOR.
  
 THE EXTENDED COVERAGE PENDENT SPRINKLER (TY4232)
 LOCATED IN OFFICE #207 HAS AN OPERATING TEMPERATURE OF
 155F MAKING THE SPRINKLER STANDARD RESPONSE ACCORDING
 TO THE LISTING INFORMATION. THIS SPRINKLER WILL NEED AN
 OPERATING TEMPERATURE OF 135F TO QUALIFY AS QUICK
 RESPONSE.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-01-10 Cont ID  
Sent By tgordon Date 2013-01-10 Time 14:33 Rev Time 0.00
Received By tgordon Date 2013-01-07 Time 15:27 Sent To  
Notes
2013-01-08 15:29:01EXPEDITED
 GAVE TO WESLEY

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2013-01-10 Cont ID  
Sent By tgordon Date 2013-01-10 Time 14:32 Rev Time 0.00
Received By tgordon Date 2013-01-10 Time 14:32 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved