| 2013-01-10 10:48:44 | BUILDING PLAN REVIEW |
| | PERMIT: 13010144 |
| | ADD: 4920 LORING DRIVE |
| | CONT: METRO PCS |
| | TEL: (772)353-7401 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | JAN. 10/2013 |
| | ACTION: DENIED |
| | |
| | 1) PEASE REVIEW NOTE # 2 FOUND ON SHEET A-1 FOR KHA. A |
| | CERTIFIFIED LETTER/ REPORT SEALED BY A REGISTERED |
| | PROFESSIONAL ENGINEER STATING THE SUFFIENT CAPACITY IN |
| | ACCORDANCE WITH ALL APPLICABLE CODES AND STANDARDS. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 2) THE PLANS ARE MISSING THE WIND DESIGN CRITERIA. |
| | 1609.1.1 EXCEPTION # 5 ANSI/ EIA/TIA-222G-05. |
| | |
| | OR |
| | |
| | 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | 2.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 2.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 2.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 2.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 2.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE |
| | TABLE 1609.2(2) . |
| | |
| | 3) SHEET A-1 DOES NOT PROVIDE AT WHAT DISTANCE THE TWO |
| | BRACKET FASTENER ASSEMBLIES HAVE TO BE APART, NOR DOES |
| | THE PLAN STATE FOR THAT GIVEN DISTANCE THE FASTENERS |
| | ARE LOCATED WHAT THE MAXIMUM DISTANCE THE POLE/ MAST |
| | CAN BE ABOVE THE TOP FASTENER. THIS WILL ALSO NEED TO |
| | BE ADDRESSED BY THE REGISTERED PROFESSIONAL ENGINEER |
| | PROVIDING THE LETTER/ REPORT. RESISTING THE FORCES FOR |
| | THE MOMENT OF OVERTURNING. 2010 FBC-B 1609.8 ROOFTOP |
| | STRUCTURES AND EQUIPMENT OR 1609.1.1 EXCEPTION # 5 |
| | ANSI/ EIA/TIA-222G-05. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |