Plan Review Details - Permit 12120776
Plan Review Stops For Permit 12120776
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status N Date 2013-01-29 Cont ID  
Sent By shill Date 2013-01-29 Time 13:36 Rev Time 0.00
Received By shill Date 2013-01-29 Time 13:36 Sent To  
Notes
2013-01-29 13:36:22SEE MASTER
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-01-28 Cont ID  
Sent By shill Date 2013-01-28 Time 16:26 Rev Time 0.00
Received By shill Date 2013-01-28 Time 16:26 Sent To  
Notes
2013-01-28 16:30:59****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 FBC R 301, RESISTANCE TO WIND LOADS:
  
 1. OK
  
 2. INDICATE WHICH APPROVED ASSEMBLY IS PROPOSED.
  
 2ND REVIEW, THE ASSEMBLY ON SHEET 21 HIGHLIGHTED. IF
 YOU USE THIS ASSEMBLY, ENHANCED FASTENING CALCULATIONS
 REQUIRED. PLEASE NOTE THAT THE ASSEMBLY ON SHEET 23
 COMPLIES WITH DESIGN PRESSURE FOR ZONE 3 AND ENHANCED
 FASTENING SPECIFIED BY AN ARCHITECT OR ENGINEER WOULD
 NOT THEN BE REQUIRED.
  
 3. ENHANCED FASTENING NAILING IS TO STATE NUMBER OF
 FIELD ROWS.
  
 2ND REVIEW, ENHANCED FASTENING CALCULATIONS NOT
 SUBMITTED.
  
 4. OK
  
 NEW COMMENT:
  
 PER BUILDING OFFICIAL, THIS IS NOT A SUB PERMIT, THIS
 SHOULD BE A REVISION TO THE MASTER AND THEN A SUB
 PERMIT CAN BE ISSUED AFTER REVISION HAS BEEN REVIEWED
 AND PASSED. THIS COMMENT DOES NOT NEED TO BE ADDRESSED
 BUT ADJUSTMENTS TO FEES SHALL BE MADE PRIOR TO
 ISSUANCE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-01-02 Cont ID  
Sent By shill Date 2013-01-02 Time 14:56 Rev Time 0.00
Received By shill Date 2013-01-02 Time 14:56 Sent To  
Notes
2013-01-02 15:02:15****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 FBC R 301, RESISTANCE TO WIND LOADS:
  
 1. PLEASE SEE DEFINITION OF EXPOSURE B, FBC RESIDENTIAL
 301, ASCE7-10. THIS PARCEL IS LOCATED IN EXPOSURE C.
 THE ARCHITECT STATES THAT THE PROPERTY IS MORE THAN ONE
 MILE FROM THE INTRACOASTAL; THIS CONDITION DOES NOT
 DETERMINE EXPOSURE B.
  
 2. INDICATE WHICH APPROVED ASSEMBLY IS PROPOSED.
  
 3. ENHANCED FASTENING NAILING IS TO STATE NUMBER OF
 FIELD ROWS.
  
 4. NOA SUBMITTED IS NOT LEGIBLE. PROVIDE TWO LEGIBLE
 SETS OF DOCUMENTS FBC 107.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-01-28 Cont ID  
Sent By shill Date 2013-01-28 Time 16:31 Rev Time 0.00
Received By shill Date 2013-01-17 Time 11:17 Sent To  
Notes
2013-01-17 11:17:15TO SH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-01-02 Cont ID  
Sent By shill Date 2013-01-02 Time 15:02 Rev Time 0.00
Received By shill Date 2012-12-28 Time 16:39 Sent To  
Notes
2012-12-28 16:39:42GAVE TO SAMANTHA