Plan Review Details - Permit 12120664
Plan Review Stops For Permit 12120664
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-03-06 Cont ID  
Sent By jgomez Date 2013-03-05 Time 17:13 Rev Time 0.00
Received By jgomez Date 2013-03-05 Time 17:12 Sent To  
Notes
2013-03-05 17:22:40BUILDING REVIEW APPROVED WITH PROVISO:
 *** 1- PROVIDE PRODUCT APPROVALS ( 2 COPIES) AS
 REQUIRED BY DCA RULE 9N-3 FOR: A) GARAGE DOOR. 18'-0"
 AS SHOWN ON PLANS (ONE SUBMITTED IS FOR 16'-0"). B)
 PRECAST LINTELS AS SHOWN ON PLANS.
 C) DECORATIVE COLONIAL SHUTTERS AS SHOWN ON EXTERIOR
 ELEVATION. AND PROVIDE INSTALLATION SCHEDULE.
 *** 2- DESIGNER OF RECORD TO APPROVE IN WRITING ABOVE
 PRODUCT APPROVALS.
 *** 3- PROVIDE COMPLETE MANUFACTURER SPECS FOR A FIXED
 BBQ APPLIANCE DESIGNED TO BE INSTALLED IN A COVERED
 PATIO AS SHOWN ON PLANS. SEC. 107.2.1 CITY AMENDMENTS
 TO FBC.
 *** 4- TRUSS PACKAGE TO BE PRESENTED TO THE BUILDING
 INSPECTOR AT TIME OF FRAMING INSPECTION WITH THE
 FOLLOWING REVISIONS AS REQUIRED BY SEC. 61G15-31.003
 WHEN USING PREFABRICATED WOOD TRUSSES: A) ENGINEER'S
 ORIGINAL SIGNATURE (NOT COPY), B) NAME OF ENGINEER OF
 RECORD, C) TITLE BLOCK OF TRUSS ENGINEER ON EACH SHEET.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-01-22 Cont ID  
Sent By jgomez Date 2013-01-22 Time 15:41 Rev Time 0.00
Received By jgomez Date 2013-01-22 Time 15:41 Sent To  
Notes
2013-01-22 15:47:31NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PLEASE BRING PLANS TO PALM BEACH COUNTY BUILDING TO
 PAY THE IMPACT FEES. BRING BACK STAMPED PLANS AND COPY
 OF THE PAID RECEIPT. REQUIRED BY COUNTY IMPACT FEE
 ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- PROVIDE SOIL TEST REPORT (2 COPIES WITH ORIGINAL
 SEAL AND SIGNATURE). SEC. R401.4 OF 2010
 FBC-RESIDENTIAL.
  
 ***RESPONSE TO SUBMITTAL: REPEAT COMMENT. NOT
 ADDRESSED.
  
 3- ACCORDING TO SEC. R301.2.1.4.3 THIS BUILDING IS
 LOCATED ON EXPOSURE "C" NOT "B". NEED TO REVISE THE
 BUILDING DESIGN DATA AND ALL THE DESIGN PRESSURES FOR
 COMPONENTS AND CLADDING FOR ROOF, DOORS AND WINDOWS
 ACCORDINGLY. (NOTE: DESIGN PRESSURES FOR GARAGE DOORS
 ARE NOT THE SAME FOR A 18'-0" WIDE DOOR AND FOR A 6'-0"
 WIDE DOOR. REVISE AS REQUIRED ALSO).
  
 ***RESPONSE TO SUBMITTAL: REPEAT COMMENT. NOT
 ADDRESSED.
  
 4- PROVIDE PRODUCT APPROVALS ( 2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) GLASS BLOCK AS SHOWN ON PLANS.
 B) PRECAST LINTELS AS SHOWN ON PLANS.
 C) ALL SEMCO (SEE DETAIL 10/D-1) AND ALL SIMPSON
 STRUCTURAL CONNECTORS AS SHOWN ON
 PLANS/DETAILS/SPECIFICATIONS.
 D) STORM SHUTTERS IF DOORS/WINDOWS DON'T HAVE IMPACT
 GLASS. AND, PROVIDE COMPLETE INSTALLATION SCHEDULE.
 E) ROOF TILE AS SHOWN ON PLANS.
 F) ROOF TILE ADHESIVE AS SHOWN ON PLANS. SEE CONCRETE
 TILE PRODUCT APPROVAL FOR LISTED ADHESIVES.
 G) ALL WINDOWS AS SHOWN ON PLANS. SINGLE HUNG, FIXED,
 ROUND AND ARCHED WINDOWS.
 H) ALL DOORS AS SHOWN ON PLANS. ENTRY DOOR WITH
 SIDELITE, ETC. AND, CLEARLY IDENTIFY WHICH PRODUCT
 APPROVAL IS FOR EACH DOOR. EX: ENTRY DOOR, CABANA BATH
 DOOR, MASTER BEDROOM EXTERIOR SWING DOOR, ETC.
 I) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY
 SPECIFY MULLION SIZE TO VERIFY COMPLIANCE WITH THE
 CALCULATED DESIGN PRESSURES.
 J) DECORATIVE COLONIAL SHUTTERS AS SHOWN ON EXTERIOR
 ELEVATION.
 K) GARAGE DOORS FOR SIZES SHOWN ON PLANS.
  
 *** RESPONSE TO SUBMITTAL: REPEAT COMMENT. NOT
 ADDRESSED.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL OF THE ABOVE PRODUCT
 APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS TO FBC.
  
 *** RESPONSE TO SUBMITTAL: REPAT COMMENT. NOT
 ADDRESSED.
  
 6- PROVIDE COMPLETE MANUFACTURER SPECS FOR APPLIANCES
 DESIGNED TO BE USED IN THE OUTDOOR SUMMER KITCHEN. SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
  
 ***RESPONSE TO SUBMITTAL: REPEAT COMMENT. NOT
 ADDRESSED.
  
 7- STRUCTURAL DOOR BUCK DETAIL 4/D-1. PROVIDE
 CALCULATIONS SHOWING HOW THE STRUCTURAL 2X4 BUCK
 FASTENED WITH 3/16" TAPCONS SPACED AT 36" O.C. WILL
 MEET THE DESIGN PRESSURES REQUIRED BY ITEM #3 ABOVE.
 SEC. 107.2.1.3 CITY AMENDMENTS TO FBC. (NOTE: CLARIFY
 WHY FASTENERS SPECIFIED FOR WINDOW BUCKS SEEMS TO BE
 STRONGER THAN THE ONES SPECIFIED FOR THE DOORS). ALSO,
 CHECK SIZE OF BUCK WITH SIZE REQUIRED BY THE DOOR
 PRODUCT APPROVAL. REMEMBER THAT BUCK MUST PROVIDE FULL
 SUPPORT TO THE DOOR FRAME. 2X4 BUCK MAY NOT BE WIDE
 ENOUGH.
  
 ***RESPONSE TO SUBMITTAL: REPEAT COMMENT. NOT
 ADDRESSED.
  
 8- SHEET S-2: REVISE ROOF FRAMING NOTE REGARDING THE
 MINIMUM LIVE LOAD FOR THE BOTTOM CHORD OF THE TRUSS.
 SEE FOOTNOTES B AND G OF TABLE R301.5 OF 2010
 FBC-RESIDENTIAL AND REVISE AS REQUIRED.
  
 *** RESPONSE TO SUBMITTAL: REPEAT COMMENT. NOT
 ADDRESSED.
  
 9- TRUSS PACKAGE SUBMITTED.
 A) REVISE DESIGN CRITERIA TO EXPOSURE "C" AS REQUIRED
 BY SEC. R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL.
  
 B) REVISE DESIGN LOADS TO MATCH DESIGN LOADS SPECIFIED
 BY THE ENGINEER OF RECORD ON SHEET S-2. SEC. 107.2.1
 CITY AMENDMENTS TO FBC.
  
 C) THERE IS AN ENGINEER OF RECORD FOR THIS BUILDING.
 COVER SHEETS SAYS N/A. REVISE COVER SHEET AS REQUIRED.
 SEC. 107.3.4.1 CITY AMENDMENTS.
  
 *** RESPONSE TO SUBMITTAL: REPEAT COMMENT. NOT
 ADDRESSED.
  
 10- ENGINEER OF RECORD TO REVIEW AND APPROVE TRUSS
 PACKAGE PRIOR TO SUBMITTAL TO THIS OFFICE. SEC.
 107.3.4.1 CITY AMENDMENTS.
  
 ***RESPONSE TO SUBMITTAL: REPEAT COMMENT. NOT
 ADDRESSED.
  
  
 ***NOTE:
 MISSING ONE SET OF PLANS. ONE SET OF PLANS TAKEN OUT ON
 1/8/13 BUT WERE NOT RETURNED YET.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-01-03 Cont ID  
Sent By jgomez Date 2013-01-03 Time 09:07 Rev Time 0.00
Received By jgomez Date 2013-01-03 Time 08:59 Sent To  
Notes
2013-01-03 09:13:39NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PLEASE BRING PLANS TO PALM BEACH COUNTY BUILDING TO
 PAY THE IMPACT FEES. BRING BACK STAMPED PLANS AND COPY
 OF THE PAID RECEIPT. REQUIRED BY COUNTY IMPACT FEE
 ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- PROVIDE SOIL TEST REPORT (2 COPIES WITH ORIGINAL
 SEAL AND SIGNATURE). SEC. R401.4 OF 2010
 FBC-RESIDENTIAL.
  
 3- ACCORDING TO SEC. R301.2.1.4.3 THIS BUILDING IS
 LOCATED ON EXPOSURE "C" NOT "B". NEED TO REVISE THE
 BUILDING DESIGN DATA AND ALL THE DESIGN PRESSURES FOR
 COMPONENTS AND CLADDING FOR ROOF, DOORS AND WINDOWS
 ACCORDINGLY. (NOTE: DESIGN PRESSURES FOR GARAGE DOORS
 ARE NOT THE SAME FOR A 18'-0" WIDE DOOR AND FOR A 6'-0"
 WIDE DOOR. REVISE AS REQUIRED ALSO).
  
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION WAS UPDATED AS REQUIRED BY SEC. 109.3 OF
 CITY AMENDMENTS TO FBC TO $315,000. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL
 INCLUDE THE VALUE FOR STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT, EXCLUDING ONLY LAND VALUE. THE
 REMAINING PERMIT FEE BALANCE IS $7623.49.
  
 5- PROVIDE PRODUCT APPROVALS ( 2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) GLASS BLOCK AS SHOWN ON PLANS.
 B) PRECAST LINTELS AS SHOWN ON PLANS.
 C) ALL SEMCO (SEE DETAIL 10/D-1) AND ALL SIMPSON
 STRUCTURAL CONNECTORS AS SHOWN ON
 PLANS/DETAILS/SPECIFICATIONS.
 D) STORM SHUTTERS IF DOORS/WINDOWS DON'T HAVE IMPACT
 GLASS. AND, PROVIDE COMPLETE INSTALLATION SCHEDULE.
 E) ROOF TILE AS SHOWN ON PLANS.
 F) ROOF TILE ADHESIVE AS SHOWN ON PLANS. SEE CONCRETE
 TILE PRODUCT APPROVAL FOR LISTED ADHESIVES.
 G) ALL WINDOWS AS SHOWN ON PLANS. SINGLE HUNG, FIXED,
 ROUND AND ARCHED WINDOWS.
 H) ALL DOORS AS SHOWN ON PLANS. ENTRY DOOR WITH
 SIDELITE, ETC. AND, CLEARLY IDENTIFY WHICH PRODUCT
 APPROVAL IS FOR EACH DOOR. EX: ENTRY DOOR, CABANA BATH
 DOOR, MASTER BEDROOM EXTERIOR SWING DOOR, ETC.
 I) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY
 SPECIFY MULLION SIZE TO VERIFY COMPLIANCE WITH THE
 CALCULATED DESIGN PRESSURES.
 J) DECORATIVE COLONIAL SHUTTERS AS SHOWN ON EXTERIOR
 ELEVATION.
 K) GARAGE DOORS FOR SIZES SHOWN ON PLANS.
  
 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL OF THE ABOVE PRODUCT
 APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS TO FBC.
  
 7- PROVIDE COMPLETE MANUFACTURER SPECS FOR APPLIANCES
 DESIGNED TO BE USED IN THE OUTDOOR SUMMER KITCHEN. SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
  
 8- ENGINEER OF RECORD TO PROVIDE SPECIFIC ROOF TILE
 ROOF FASTENING METHOD AS REQUIRED BY SEC. 107.2.1.2
 CITY AMENDMENTS TO FBC.
  
 9- STRUCTURAL DOOR BUCK DETAIL 4/D-1. PROVIDE
 CALCULATIONS SHOWING HOW THE STRUCTURAL 2X4 BUCK
 FASTENED WITH 3/16" TAPCONS SPACED AT 36" O.C. WILL
 MEET THE DESIGN PRESSURES REQUIRED BY ITEM #3 ABOVE.
 SEC. 107.2.1.3 CITY AMENDMENTS TO FBC. (NOTE: FASTENERS
 SPECIFIED FOR WINDOW BUCKS SEEMS TO BE STRONGER THAN
 THE ONE FOR THE DOORS). ALSO, CHECK SIZE OF BUCK WITH
 SIZE REQUIRED BY THE DOOR PRODUCT APPROVAL. REMEMBER
 THAT BUCK MUST PROVIDE FULL SUPPORT TO THE DOOR FRAME.
 2X4 BUCK MAY NOT BE WIDE ENOUGH.
  
 10- SHEET S-2: REVISE ROOF FRAMING NOTE REGARDING THE
 MINIMUM LIVE LOAD FOR THE BOTTOM CHORD OF THE TRUSS.
 SEE FOOTNOTES B AND G OF TABLE R301.5 OF 2010
 FBC-RESIDENTIAL AND REVISE AS REQUIRED.
  
 10- TRUSS PACKAGE SUBMITTED.
 A) REVISE DESIGN CRITERIA TO EXPOSURE "C" AS REQUIRED
 BY SEC. R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL.
  
 B) REVISE DESIGN LOADS TO MATCH DESIGN LOADS SPECIFIED
 BY THE ENGINEER OF RECORD ON SHEET S-2. SEC. 107.2.1
 CITY AMENDMENTS TO FBC.
  
 C) THERE IS AN ENGINEER OF RECORD FOR THIS BUILDING.
 COVER SHEETS SAYS N/A. REVISE COVER SHEET AS REQUIRED.
 SEC. 107.3.4.1 CITY AMENDMENTS.
  
 11- ENGINEER OF RECORD TO REVIEW AND APPROVE TRUSS
 PACKAGE PRIOR TO SUBMITTAL TO THIS OFFICE. SEC.
 107.3.4.1 CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-01-16 Cont ID  
Sent By rlecky Date 2013-01-16 Time 16:01 Rev Time 0.00
Received By rlecky Date 2013-01-16 Time 15:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-01-02 Cont ID  
Sent By rlecky Date 2013-01-02 Time 11:46 Rev Time 0.00
Received By rlecky Date 2013-01-02 Time 11:23 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2013-03-06 Cont ID  
Sent By LWARNER Date 2013-03-06 Time 11:59 Rev Time 0.00
Received By jgomez Date 2013-03-06 Time 11:59 Sent To  
Notes
2013-02-21 10:30:49NEW SHEETS SUBMITTED. JG.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2013-01-23 Cont ID  
Sent By lwagner Date 2013-01-23 Time 13:56 Rev Time 0.00
Received By lwagner Date 2013-01-23 Time 13:56 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2013-01-04 Cont ID  
Sent By lwagner Date 2013-01-04 Time 15:44 Rev Time 0.00
Received By lwagner Date 2013-01-04 Time 15:15 Sent To  
Notes
2013-01-04 15:43:39FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. TABLE 402.4(2) AT 90'
 LONGEST LENGTH METHOD REQUIRES 1 1/4" PIPE FROM THE
 METER UP TO THE TEE FOR THE GAS RANGE. (THE SPECIFIC
 GRAVITY FOR THIS TABLE IS .60)
  
 **NOTE**
 WAS THE APPLIANCE LABELED GAS WASHER MEANT TO BE GAS
 DRYER?
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-03-06 Cont ID  
Sent By jgomez Date 2013-03-06 Time 11:59 Rev Time 0.00
Received By jgomez Date 2013-02-20 Time 17:08 Sent To  
Notes
2013-02-20 17:09:01GAVE TO JULIO

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-02-05 Cont ID  
Sent By mdekle Date 2013-02-05 Time   Rev Time 0.00
Received By mdekle Date 2013-01-14 Time 16:45 Sent To  
Notes
2013-01-14 16:46:07R05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-01-09 Cont ID  
Sent By rmcdouga Date 2013-01-09 Time 09:05 Rev Time 0.00
Received By rmcdouga Date 2012-12-21 Time 09:11 Sent To  
Notes
2012-12-26 09:12:21SENT TO R4 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2013-03-05 Cont ID  
Sent By jgomez Date 2013-03-05 Time 17:53 Rev Time 0.00
Received By jgomez Date 2013-03-05 Time 17:53 Sent To  
Notes
2013-03-05 17:54:25MU-2013-000498. JG

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2013-01-22 Cont ID  
Sent By jgomez Date 2013-01-22 Time 15:48 Rev Time 0.00
Received By jgomez Date 2013-01-22 Time 15:48 Sent To  
Notes
2013-01-22 15:48:28BRING PLANS TO PALM BEACH COUNTY BUILDING TO PAY IMPACT
 FEES. BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-01-03 Cont ID  
Sent By jgomez Date 2013-01-03 Time 08:59 Rev Time 0.00
Received By jgomez Date 2013-01-03 Time 08:59 Sent To  
Notes
2013-01-03 09:01:12BRING PLANS TO PALM BEACH COUNTY BUILDING TO PAY IMPACT
 FEES. BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-12-27 Cont ID  
Sent By tgordon Date 2012-12-27 Time 09:01 Rev Time 0.00
Received By tgordon Date 2012-12-27 Time 07:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2013-03-06 Cont ID  
Sent By jgomez Date 2013-03-06 Time 11:59 Rev Time 0.00
Received By jgomez Date 2013-03-06 Time 11:59 Sent To  
Notes
2013-02-21 10:31:40NEW SHEETS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-01-23 Cont ID  
Sent By rmcdouga Date 2013-01-23 Time 13:22 Rev Time 0.00
Received By rmcdouga Date 2013-01-23 Time 13:22 Sent To  
Notes
2013-01-22 16:43:41NEW SHEETS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-01-09 Cont ID  
Sent By rmcdouga Date 2013-01-09 Time 09:05 Rev Time 0.00
Received By rmcdouga Date 2013-01-09 Time 09:05 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2013-02-05 Cont ID  
Sent By mdekle Date 2013-02-05 Time   Rev Time 0.00
Received By mdekle Date 2013-02-05 Time   Sent To  
Notes
2013-02-05 10:01:19PLANNING: **** PASSED W/PROVISO ****
  
 1. PRIOR TO THE FIRST INSPECTION, THE APPLICANT MUST
 HAVE AN APPROVED, SEPERATE PERMIT FOR LANDSCAPING WHICH
 DEMONSTRATES COMPLIANCE WITH SECTIONS 94-442 AND 94-445
 OF THE ZLDR. PLEASE PROVIDE CALCULATIONS ON THE PLAN
 FOR THE FRONT AREA BETWEEN THE FIRST 25 FEET OF LOT
 DEPTH FROM THE FRONT PROPERTY LINE MULTIPLIED BY THE
 TOTAL WIDTH OF THE PROPERTY.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME AND/OR
 CONSULT THE CITY?S ZONING AND LAND DEVELOPMENT
 REGULATIONS ONLINE @WWW.MUNICODE.COM.
  
 MURRIAH DEKLE, MPA, PLANNER
 PLANNING & ZONING DIVISION
 TEL: (561) 822-1442
 EMAIL: [email protected]
 WWW.CITYOFWPB.COM
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2012-12-28 Cont ID  
Sent By mdekle Date 2012-12-28 Time   Rev Time 0.00
Received By mdekle Date 2012-12-28 Time 16:07 Sent To  
Notes
2012-12-28 16:14:021. THE MAXIMUM WIDTH FOR A DRIVEWAY IS 20 FEET IN
 WIDTH. THERE ARE NO DIMENSIONS ON THE PROPOSED
 DRIVEWAY. PLEASE PROVIDE PROPOSED DIMENSIONS. PLEASE BE
 ADVISED; IF THE TOTAL WIDTH OF THE DRIVE EXCEEDS 20
 FEET, THEN THE ADDITIONAL WORK WILL NOT BE ALLOWED.
  
 2. PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR. PLEASE PROVIDE A CALCULATION ON THE PLAN FOR
 THE FRONT AREA BETWEEN THE FIRST 25 FEET OF LOT DEPTH
 FROM THE FRONT PROPERTY LINE MULTIPLIED BY THE TOTAL
 WIDTH OF THE PROPERTY.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME AND/OR
 CONSULT THE CITY?S ZONING AND LAND DEVELOPMENT
 REGULATIONS ONLINE @WWW.MUNICODE.COM.
  
 MURRIAH DEKLE, MPA, PLANNER
 PLANNING & ZONING DIVISION
 TEL: (561) 822-1442
 EMAIL: [email protected]
 WWW.CITYOFWPB.COM
  