Plan Review Details - Permit 12120635
Plan Review Stops For Permit 12120635
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-01-16 Cont ID  
Sent By jwitmer Date 2013-01-16 Time 17:00 Rev Time 0.00
Received By jwitmer Date 2013-01-16 Time 16:36 Sent To  
Notes
2013-01-16 16:35:25BUILDING PLAN REVIEW
 PERMIT: 12120635
 ADD: 2015 OKEECHOBEE BLVD.
 CONT: THE SINCLAIR GROUP
 TEL: (954)798-1421
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 BUILDING PROVISO:
  
 THE FOLLOWING LIST OF CODE ISSUES WILL NEED TO BE
 SATISFIED BY THE ROOF FRAMING AND DOOR / WINDOW BUCK
 INSPECTION, NO INTERIOR FRAMING AND OR TRADE WORK (MEP)
 ALLOWED BEFORE THESE CODE ISSUES ARE SATISFIED.
  
 1) COMPLIED 01/16/2013. MISSING SOILS REPORT. 2010
 FBC-B / 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1803.3.1 & 1803.6 REPORTING.
  
 2) SEMI-COMPLIED 01/16/ 2013. MISSING ENERGY
 CALCULATIONS. 2010 FBC-B 103.3 ENERGY CODE COMPLIANCE.
 ENERGY CALCULATIONS.
 EXAMINATION OF DOCUMENTS. THE CODE OFFICIAL SHALL
 EXAMINE OR CAUSE TO BE EXAMINED THE ACCOMPANYING
 CONSTRUCTION DOCUMENTS AND SHALL ASCERTAIN WHEATHER THE
 CONSTRUCTION INDICATED AND DESCRIBED IS IN ACCORDANCE
 WITH THE REQUIREMENTS OF THIS CODE AND OTHER PERTINENT
 LAWS OR ORDINANCES.
  
 2A) SHOW COMPLIANCE WITH 2010 ENERGY CODE 402.1.2.3
 MAXIMUM PER CENT WINDOW AREA.
  
 2B) PROVIDE COMPLIANCE WITH 2010 ENERGY CODE TABLE
 402.1.1 GLAZED FENESTRATION SHGC
  
 3) SHEET A-506 DETAIL # 2,:
  
 3A) INDICATES THE USE OF R-40 EXPANDABLE FOAM
 INSULATION, PLEASE PROVIDE WHAT THE THICKNESS OF THE
 EXPANDED FOAM WILL BE FOR THE ROOF INSULATION AND THE
 WALL INSULATION. PLEASE PROVIDE A PRODUCT APPROVAL FOR
 THIS PRODUCT.
  
 3B) PLANS FAIL TO IDENTIFY THE USE OF AN IGNITION
 BARRIER, PER 2010 FBC-B 2603.4.1.6 ALSO SEE BOAF
 INTERPRETATION 5416.
  
 3C) PLANS ALSO FAIL TO PROVIDE COMPLIANCE WITH 2010
 FBC-B 2603.4 THERMAL BARRIER. EXCEPT AS PROVIDED FOR IN
 SECTIONS 2603.4.1 AND 2603.9, FOAM PLASTIC SHALL BE
 SEPARATED FROM THE INTERIOR OF A BUILDING BY AN
 APPROVED THERMAL BARRIER OF 1/2-INCH (12.7 MM) GYPSUM
 WALLBOARD OR EQUIVALENT THERMAL BARRIER MATERIAL THAT
 WILL LIMIT THE AVERAGE TEMPERATURE RISE OF THE
 UNEXPOSED SURFACE TO NOT MORE THAN 250?F (120?C) AFTER
 15 MINUTES OF FIRE EXPOSURE, COMPLYING WITH THE
 STANDARD TIME-TEMPERATURE CURVE OF ASTM E 119 OR UL
 263. THE THERMAL BARRIER SHALL BE INSTALLED IN SUCH A
 MANNER THAT IT WILL REMAIN IN PLACE FOR 15 MINUTES
 BASED ON FM 4880, UL 1040, NFPA 286 OR UL 1715.
 COMBUSTIBLE CONCEALED SPACES SHALL COMPLY WITH SECTION
 717.
  
 THE PLANS INDICATE THE USE OF A BLACK FIBERGLASS
 INSULATION, PLEASE PROVIDE EQUIVALENCY.
  
 4) G-002 DOES PROVIDE A LIST OF PROPOSED PRODUCT
 APPROVALS BUT NO REPORTS WERE SUBMITTED. WITHOUT THE
 ACTUAL REPORTS REVIEW FOR CODE COMPLIANCE CAN NOT BE
 ACHIEVED.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) REPORTS FOR GLAZED OPENINGS, PLEASE CIRCLE THE TYPE
 OF GLAZING TO BE INSTALLED, CIRCLE MULLION TYPES AND IF
 REINFORCING IS REQUIRED, LENGTH & WIDTH OF OPENINGS,
 AND ASSOCATED PRESSURES.
  
 6) ROOFING REPORTS, WITHIN MANY ROOFING REPORTS, THERE
 ARE NUMEROUS SUB-SYSTEMS, PLEASE CIRCLE THE TYPE OF
 SUB-SYSTEM TO BE INSTALLED, REVIEW THE ASSOCATED
 PRESSURES, IF THE PRODUCT APPROVAL ALLOWS FOR ENHANCED
 FASTENING IN ZONES 2 & 3 OR NOT. SEE IF THE PRODUCT
 APPROVAL REQUIRES A DESIGN PROFESSIONAL FOR RAS 117
 CALCULATIONS.
  
 7)COMPLIED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-01-02 Cont ID  
Sent By jwitmer Date 2013-01-02 Time 11:21 Rev Time 0.00
Received By jwitmer Date 2013-01-02 Time 08:04 Sent To  
Notes
2013-01-02 09:24:41BUILDING PLAN REVIEW
 PERMIT: 12120635
 ADD: 2015 OKEECHOBEE BLVD.
 CONT: THE SINCLAIR GROUP
 TEL: (954)798-1421
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 JAN. 02/ 2013
 ACTION: DENIED
  
 1) MISSING SOILS REPORT. 2010 FBC-B / 1802.2.1
 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING POWER OF
 THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY
 INVESTIGATION BE MADE. SUCH INVESTIGATION SHALL COMPLY
 WITH THE PROVISIONS OF SECTIONS 1803.3.1 & 1803.6
 REPORTING.
  
 2) MISSING ENERGY CALCULATIONS. 2010 FBC-B 103.3 ENERGY
 CODE COMPLIANCE. ENERGY CALCULATIONS.
 EXAMINATION OF DOCUMENTS. THE CODE OFFICIAL SHALL
 EXAMINE OR CAUSE TO BE EXAMINED THE ACCOMPANYING
 CONSTRUCTION DOCUMENTS AND SHALL ASCERTAIN WHEATHER THE
 CONSTRUCTION INDICATED AND DESCRIBED IS IN ACCORDANCE
 WITH THE REQUIREMENTS OF THIS CODE AND OTHER PERTINENT
 LAWS OR ORDINANCES.
  
 2A) SHOW COMPLIANCE WITH 2010 ENERGY CODE 402.1.2.3
 MAXIMUM PER CENT WINDOW AREA.
  
 2B) PROVIDE COMPLIANCE WITH 2010 ENERGY CODE TABLE
 402.1.1 GLAZED FENESTRATION SHGC
  
 3) SHEET A-506 DETAIL # 2,:
  
 3A) INDICATES THE USE OF R-40 EXPANDABLE FOAM
 INSULATION, PLEASE PROVIDE WHAT THE THICKNESS OF THE
 EXPANDED FOAM WILL BE FOR THE ROOF INSULATION AND THE
 WALL INSULATION. PLEASE PROVIDE A PRODUCT APPROVAL FOR
 THIS PRODUCT.
  
 3B) PLANS FAIL TO IDENTIFY THE USE OF AN IGNITION
 BARRIER, PER 2010 FBC-B 2603.4.1.6 ALSO SEE BOAF
 INTERPRETATION 5416.
  
 3C) PLANS ALSO FAIL TO PROVIDE COMPLIANCE WITH 2010
 FBC-B 2603.4 THERMAL BARRIER. EXCEPT AS PROVIDED FOR IN
 SECTIONS 2603.4.1 AND 2603.9, FOAM PLASTIC SHALL BE
 SEPARATED FROM THE INTERIOR OF A BUILDING BY AN
 APPROVED THERMAL BARRIER OF 1/2-INCH (12.7 MM) GYPSUM
 WALLBOARD OR EQUIVALENT THERMAL BARRIER MATERIAL THAT
 WILL LIMIT THE AVERAGE TEMPERATURE RISE OF THE
 UNEXPOSED SURFACE TO NOT MORE THAN 250?F (120?C) AFTER
 15 MINUTES OF FIRE EXPOSURE, COMPLYING WITH THE
 STANDARD TIME-TEMPERATURE CURVE OF ASTM E 119 OR UL
 263. THE THERMAL BARRIER SHALL BE INSTALLED IN SUCH A
 MANNER THAT IT WILL REMAIN IN PLACE FOR 15 MINUTES
 BASED ON FM 4880, UL 1040, NFPA 286 OR UL 1715.
 COMBUSTIBLE CONCEALED SPACES SHALL COMPLY WITH SECTION
 717.
  
 THE PLANS INDICATE THE USE OF A BLACK FIBERGLASS
 INSULATION, PLEASE PROVIDE EQUIVALENCY.
  
 4) G-002 DOES PROVIDE A LIST OF PROPOSED PRODUCT
 APPROVALS BUT NO REPORTS WERE SUBMITTED. WITHOUT THE
 ACTUAL REPORTS REVIEW FOR CODE COMPLIANCE CAN NOT BE
 ACHIEVED.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) REPORTS FOR GLAZED OPENINGS, PLEASE CIRCLE THE TYPE
 OF GLAZING TO BE INSTALLED, CIRCLE MULLION TYPES AND IF
 REINFORCING IS REQUIRED, LENGTH & WIDTH OF OPENINGS,
 AND ASSOCATED PRESSURES.
  
 6) ROOFING REPORTS, WITHIN MANY ROOFING REPORTS, THERE
 ARE NUMEROUS SUB-SYSTEMS, PLEASE CIRCLE THE TYPE OF
 SUB-SYSTEM TO BE INSTALLED, REVIEW THE ASSOCATED
 PRESSURES, IF THE PRODUCT APPROVAL ALLOWS FOR ENHANCED
 FASTENING IN ZONES 2 & 3 OR NOT. SEE IF THE PRODUCT
 APPROVAL REQUIRES A DESIGN PROFESSIONAL FOR RAS 117
 CALCULATIONS.
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-01-16 Cont ID  
Sent By rlecky Date 2013-01-16 Time 09:47 Rev Time 0.00
Received By rlecky Date 2013-01-16 Time 09:47 Sent To  
Notes
2013-01-16 09:58:58AT THE REQUEST OF THE BUILDER THE FOLLOWING PROVISIO
 HAS BEEN APPLIED TO THE PLANS.
  
  
 PROVISO
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS:
 INDICATE THE FAULT CURRENT CAPABILITY OF THE SERVICE
 EQUIPMENT AND PANEL BOARDS. NEC 110.9
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
 PROVIDE A LIGHTING DENSITY SUMMARY SHOWING COMPLIANCE
 WITH THE FLORIDA BUILDING ENERGY CODE REQUIREMENTS. FBC
 ENERGY CONSERVATION 505.3
 PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL
 DISCONNECTS AND FOR FLASH PROTECTION. NEC 110.22,
 110.16
 INDICATE THE REQUIRED SAFE CLEARANCES TO THE CEILING
 FANS. NEC 110.3
  
 NOTE:
 SEPARATE PERMITS WITH PLANS ARE REQUIRED FOR VOICE,
 DATA, FIRE ALARM, SECURITY, SIGNAGE, AND SITE LIGHTING.
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-01-03 Cont ID  
Sent By rlecky Date 2013-01-03 Time 12:57 Rev Time 0.00
Received By rlecky Date 2013-01-03 Time 11:14 Sent To  
Notes
2013-01-03 12:58:51125120635
 2015 OKEECHOBEE BLVD.
 PDQ RESTAURANT
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 INDICATE THE REQUIRED FAULT CURRENT CAPABILITY OF THE
 SERVICE EQUIPMENT AND PANEL BOARDS. NEC 110.9
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
  
 PROVIDE A LIGHTING DENSITY SUMMARY SHOWING COMPLIANCE
 WITH THE FLORIDA BUILDING ENERGY CODE REQUIREMENTS. FBC
 ENERGY CONSERVATION 505.3
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL
 DISCONNECTS AND FOR FLASH PROTECTION. NEC 110.22,
 110.16
  
 INDICATE THE REQUIRED SAFE CLEARANCES TO THE CEILING
 FANS. NEC 110.3
  
 NOTE:
 SEPARATE PERMITS WITH PLANS ARE REQUIRED FOR VOICE,
 DATA, FIRE ALARM, SECURITY, SIGNAGE, AND SITE LIGHTING.
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2013-01-16 Cont ID  
Sent By Mgonzale Date 2013-01-16 Time   Rev Time 1.00
Received By mgonzale Date 2013-01-16 Time   Sent To I
Notes
2013-01-16 08:31:27PLANS ACCEPTED THRU ESD SITE DEVELOPMENT PERMIT - NO
 OBJECTIONS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-01-12 Cont ID  
Sent By wjolin Date 2013-01-12 Time 11:19 Rev Time 0.00
Received By wjolin Date 2013-01-11 Time 07:04 Sent To  
Notes
2013-01-12 11:19:122015 OKEECHOBEE BOULEVARD
 PERMIT #12120635
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 COVER SHEET: UPDATE THE CODE LIST TO REFERENCE THE 2010
 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS.
  
 SITE PLAN: FIRE LANES SHALL BE MARKED WITH PAINTED
 CURBS AND FREESTANDING SIGNS READING, ?FIRE LANE - NO
 PARKING BY ORDER OF THE FIRE DEPARTMENT.? SIGNS SHALL
 BE 12? X 18? WITH A WHITE BACKGROUND AND RED LETTERS
 AND SHALL BE A MAXIMUM OF SEVEN FEET IN HEIGHT TO THE
 BOTTOM OF THE SIGN. SIGNS SHALL BE WITHIN SIGHT OF THE
 TRAFFIC FLOW AND BE SPACED A MAXIMUM OF 60 FEET APART.
 FLORIDA FIRE PREVENTION CODE SECTION 18.2.3.5.3.
  
 DEMOLITION SHEET: ALL CONSTRUCTION AND DEMOLITION WORK
 SHALL CONFORM TO THE REQUIREMENTS OF NFPA 241. TRASH
 AND CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY. SMOKING SHALL BE PROHIBITED EXCEPT IN DESIGNATED
 EXTERIOR AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION
 AREAS SHALL HAVE "NO SMOKING" SIGNS POSTED. WHERE
 SMOKING IS PERMITTED, SAFE RECEPTACLES FOR SMOKING
 MATERIALS SHALL BE PROVIDED.
  
 SHEET A101: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED
 EXIT DOORS WITH EXIT SIGNS.
  
 SHEET A602: CONFIRM PROPOSED WOOD CEILING AND FINISH
 CAN MEET THE FLAME SPREAD AND SMOKE DEVELOPMENT
 CRITERIA FOR CLASS C FINISHES. THE INTERIOR FINISH
 MATERIALS FOR WALLS AND CEILINGS SHALL MEET THE SMOKE
 DEVELOPMENT (0-450) AND FLAME SPREAD (76-200)
 REQUIREMENTS FOR CLASS C INTERIOR FINISHES PER NFPA
 101.
  
 SHEET FP101: COMBUSTIBLE CONCEALED SPACES WILL REQUIRE
 SPRINKLER PROTECTION PER NFPA 13.
  
 KITCHEN EQUIPMENT: DEEP FAT FRYERS SHALL BE EQUIPPED
 WITH A SEPARATE HIGH-LIMIT CONTROL IN ADDITION TO THE
 ADJUSTABLE THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN
 THE FAT TEMPERATURE REACHES 475F DEGREES AT 1-INCH
 BELOW THE SURFACE.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 (561) 805-6730
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2012-12-31 Cont ID  
Sent By lwagner Date 2012-12-31 Time 08:13 Rev Time 0.00
Received By lwagner Date 2012-12-31 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-01-17 Cont ID  
Sent By shill Date 2013-01-17 Time 13:43 Rev Time 0.00
Received By shill Date 2012-12-26 Time 13:48 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2013-01-15 Cont ID  
Sent By rregueir Date 2013-01-15 Time 16:44 Rev Time 0.00
Received By rregueir Date 2013-01-15 Time 16:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-01-17 Cont ID  
Sent By shill Date 2013-01-17 Time 14:43 Rev Time 0.00
Received By shill Date 2013-01-08 Time 15:02 Sent To  
Notes
2013-02-05 08:36:23**KITCHEN HOOD, GREASE EXHAUST AND HOOD SUPPRESSION
 SYSTEMS EXCLUDED FROM THIS REVIEW. SEPARATE PLANS AND
 PERMIT APPLICATIONS REQUIRED**
2013-01-17 14:43:57***PASSED W/PROVISO***
 PER RON REGUEIRO
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-01-02 Cont ID  
Sent By lwagner Date 2013-01-02 Time 14:31 Rev Time 0.00
Received By lwagner Date 2012-12-31 Time 08:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2013-01-17 Cont ID  
Sent By shill Date 2013-01-17 Time 13:44 Rev Time 0.00
Received By shill Date 2013-01-17 Time 13:44 Sent To  
Notes
2013-01-17 13:44:44PEDDS RECEIVED BY RR
  

Review Stop Z ZONING
Rev No 1 Status P Date 2013-01-15 Cont ID  
Sent By mdekle Date 2013-01-15 Time   Rev Time  
Received By mdekle Date 2013-01-15 Time   Sent To  
Notes
2013-01-15 08:56:28PLEASE BE ADVISED -
 THE APPLICANT IS REQUIRED TO OBTAIN THE FOLLOWING
 SEPERATE PERMITS PRIOR TO THE FIRST BUILDING
 INSPECTION:
 1. LANDSCAPING
 2. SIGNAGE
 2. DUMPSTER
 3. DRIVEWAY
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME
 AND/OR CONSULT THE CITY'S ZONING AND LAND
 DEVELOPMENT REGULATIONS ONLINE @WWW.MUNICODE.COM.
  
 MURRIAH DEKLE, MPA, PLANNER
 PLANNING & ZONING DIVISION
 TEL: (561) 822-1442
 EMAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved