| 2012-12-20 14:11:18 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE FLAT ROOFING SYSTEM THAT WAS SUBMITTED ON PAGE 9 | | | OF THE NOA HAS A MAXIMUM DESIGN PRESSURE OF -45 PSF. | | | SUBMIT 2 SETS OF SIGNED AND SEALED RAS 117 CALCULATIONS | | | FOR ENHANCED FASTENING OF THE BASE SHEET AS REQUIRED BY | | | LIMITATION NUMBER 7 ON PAGE 31 OF NOA #09-0224.01. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
|