| Plan Review Stops For Permit 12120506 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2012-12-20 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-12-20 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-12-20 |
Time |
16:34 |
Sent To |
|
|
| Notes |
| 2012-12-20 16:05:26 | 12100672 | | | 153 WORTH CT S. | | | SFD RENOVATION | | | | | | | | | THE FOLLOWING CODE REQUIREMENTS WERE NOTED ON THE PLAN. | | | | | | PROVISO: | | | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND | | | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS | | | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON | | | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH | | | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | THE NEW BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH | | | CIRCUIT. NEC 210.11 (C) (3) | | | ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW | | | GENERAL PURPOSE OUTLETS. | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2012-12-20 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-12-20 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-12-18 |
Time |
11:16 |
Sent To |
|
|
| Notes |
| 2012-12-18 11:17:05 | INCOMING SENT TO <$5K ELEC. BOX. JW |
|
|
|