Plan Review Details - Permit 12120454
Plan Review Stops For Permit 12120454
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-02-27 Cont ID  
Sent By jgomez Date 2013-02-27 Time 17:08 Rev Time 0.00
Received By jgomez Date 2013-02-27 Time 17:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-12-19 Cont ID  
Sent By jgomez Date 2012-12-19 Time 12:32 Rev Time 0.00
Received By jgomez Date 2012-12-19 Time 11:24 Sent To  
Notes
2012-12-19 14:10:19RESIDENTIAL (R3) REVISION BUILDING REVIEW COMMENTS.
 CODE: 2007 FBC.
  
 1- A) ENTRY DOOR PRODUCT APPROVAL FL11916 SUBMITTED
 DOESN'T MEET THE DESIGN PRESSURES CALCULATED BY THE
 ENGINEER OF RECORD. NEED TO PROVIDE PRODUCT APPROVAL
 THAT MEETS OR EXCEEDS THE CALCULATED DESIGN PRESSURES.
 SEC. R301 OF 2007 FBC-RESIDENTIAL.
  
 B) ENTRY DOOR PRODUCT APPROVAL FL11916 SUBMITTED IS NOT
 LISTED IN THE FLORIDA PRODUCT APPROVAL WEBSITE. PROVIDE
 LISTED PRODUCT APPROVAL. REQUIRED BY DCA RULE 9N-3.
  
 C) ENGINEER OF RECORD TO REVIEW AND APPROVE ABOVE
 PRODUCT APPROVAL. SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 2- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE
 INSTALLATION OF STORM SHUTTERS. SEC. 106.1.1 CITY
 AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-02-27 Cont ID  
Sent By jgomez Date 2013-02-27 Time 17:08 Rev Time 0.00
Received By jgomez Date 2013-02-27 Time 17:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-12-19 Cont ID  
Sent By jgomez Date 2012-12-19 Time 12:32 Rev Time 0.00
Received By jgomez Date 2012-12-14 Time 12:46 Sent To  
Notes
2012-12-14 12:46:49TO JG