Plan Review Details - Permit 12120434
Plan Review Stops For Permit 12120434
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-05-02 Cont ID  
Sent By jwitmer Date 2013-05-02 Time 10:59 Rev Time 0.00
Received By jwitmer Date 2013-05-02 Time 10:59 Sent To  
Notes
2013-05-02 10:59:42BUILDING PROVISO:
 2010 FBC-B 1816.1.4
 IF SOIL TREATMENT IS USED FOR SUBTERRANEAN TERMITE
 PREVENTION, CHEMICALLY TREATED SOIL SHALL BE PROTECTED
 WITH A MINIMUM 6 MILLIMETER VAPOR RETARDER TO PROTECT
 AGAINST RAINFALL DILUTION. IF RAINFALL OCCURS BEFORE
 VAPOR RETARDER PLACEMENT, RETREATMENT IS REQUIRED. ANY
 WORK, INCLUDING PLACEMENT OF REINFORCING STEEL, DONE
 AFTER CHEMICAL TREATMENT UNTIL THE CONCRETE FLOOR IS
 POURED, SHALL BE DONE IN SUCH MANNER AS TO AVOID
 PENETRATING OR DISTURBING TREATED SOIL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2012-12-27 Cont ID  
Sent By jwitmer Date 2012-12-27 Time 09:55 Rev Time 0.00
Received By jwitmer Date 2012-12-26 Time 11:00 Sent To  
Notes
2012-12-27 10:39:56BUILDING PROVISO:
 2010 FBC-B 1816.1.4
 IF SOIL TREATMENT IS USED FOR SUBTERRANEAN TERMITE
 PREVENTION, CHEMICALLY TREATED SOIL SHALL BE PROTECTED
 WITH A MINIMUM 6 MILLIMETER VAPOR RETARDER TO PROTECT
 AGAINST RAINFALL DILUTION. IF RAINFALL OCCURS BEFORE
 VAPOR RETARDER PLACEMENT, RETREATMENT IS REQUIRED. ANY
 WORK, INCLUDING PLACEMENT OF REINFORCING STEEL, DONE
 AFTER CHEMICAL TREATMENT UNTIL THE CONCRETE FLOOR IS
 POURED, SHALL BE DONE IN SUCH MANNER AS TO AVOID
 PENETRATING OR DISTURBING TREATED SOIL

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-05-13 Cont ID  
Sent By dharvey Date 2013-05-13 Time 16:52 Rev Time 0.00
Received By dharvey Date 2013-05-13 Time 16:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-12-31 Cont ID  
Sent By rlecky Date 2012-12-31 Time 16:13 Rev Time 0.00
Received By rlecky Date 2012-12-31 Time 15:16 Sent To  
Notes
2012-12-31 16:14:1012120434
 1921 SOUTH DIXIE HIGHWAY
 COMMERCIAL RENOVATION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENT.
  
 VERIFY THE NEW AND EXISTING SERVICE EQUIPMENT IS
 SUFFICIENT TO HANDLE THE AVAILABLE FAULT CURRENT. NEC
 110.9
  
 PROVIDE DEDICATED 20 AMPERE BRANCH CIRCUIT (S) FOR
 SIGNAGE. NEC 600.5
  
 GFCI PROTECTION IS REQUIRED FOR WATER COOLERS. NEC
 422.52
  
 THE GENERATOR REQUIRES A SEPARATE PERMIT WITH PLANS AND
 SPECIFICATIONS. PLEASE INCLUDE CONDUIT SUPPORT AND
 FLASHING DETAIL FOR ALL CONDUIT AND EQUIPMENT. INCLUDE
 ENGINEERING FOR THE SUPPORT AND ANCHORAGE OF THE
 GENERATOR. FBC 105.1
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-05-06 Cont ID  
Sent By wjolin Date 2013-05-06 Time 10:00 Rev Time 0.00
Received By wjolin Date 2013-05-04 Time 12:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-12-19 Cont ID  
Sent By wjolin Date 2012-12-19 Time 12:37 Rev Time 0.00
Received By wjolin Date 2012-12-19 Time 12:13 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2012-12-17 Cont ID  
Sent By lwagner Date 2012-12-17 Time 14:54 Rev Time 0.00
Received By lwagner Date 2012-12-17 Time 14:00 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2013-05-10 Cont ID  
Sent By jroach Date 2013-05-10 Time 17:03 Rev Time 0.00
Received By jroach Date 2013-05-10 Time 17:03 Sent To  
Notes
2013-05-10 17:04:11NO HISTORIC REVIEW REQUIRED (INTERIOR AND MECHANICAL
 WORK ONLY).
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL
 PLANNER, AT (561) 822-1448.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-05-16 Cont ID  
Sent By hmoser Date 2013-05-16 Time 14:52 Rev Time 0.00
Received By hmoser Date 2013-04-23 Time 10:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-12-31 Cont ID  
Sent By rlecky Date 2012-12-31 Time 16:14 Rev Time 0.00
Received By rlecky Date 2012-12-13 Time 14:16 Sent To  
Notes
2012-12-14 14:34:57B02

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-05-16 Cont ID  
Sent By hmoser Date 2013-05-16 Time 14:51 Rev Time 0.00
Received By hmoser Date 2013-05-16 Time 14:22 Sent To  
Notes
2013-05-16 14:54:49SEPARATE PERMIT REQUIRED FOR GENERATOR
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-12-19 Cont ID  
Sent By tgordon Date 2012-12-19 Time 14:22 Rev Time 0.00
Received By tgordon Date 2012-12-19 Time 13:28 Sent To  
Notes
2012-12-19 14:21:56NOTE: THE GENERATOR WILL REQUIRE IT'S OWN PERMIT.
 SUBMIT PLANS, ENGINEERING, AND DETAILED MANUFACTURER'S
 SPECIFICATION'S WHEN APPLYING.

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-04-26 Cont ID  
Sent By lwagner Date 2013-04-26 Time 09:08 Rev Time 0.00
Received By lwagner Date 2013-04-26 Time 08:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-12-17 Cont ID  
Sent By lwagner Date 2012-12-17 Time 14:54 Rev Time 0.00
Received By lwagner Date 2012-12-17 Time 11:50 Sent To  
Notes
2012-12-17 14:40:37***PROVISO***
 FBC PLUMBING 314.2.1 CONDENSATE DISPOSAL.
 ...CONDENSATE SHALL NOT DISCHARGE INTO A STREET, ALLEY
 OR OTHER AREAS SO AS TO CAUSE A NUISANCE.

Review Stop Z ZONING
Rev No 2 Status P Date 2013-05-10 Cont ID  
Sent By jroach Date 2013-05-10 Time 17:03 Rev Time 0.00
Received By jroach Date 2013-05-06 Time 14:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2012-12-21 Cont ID  
Sent By fmitter Date 2012-12-21 Time 15:55 Rev Time 0.00
Received By jroach Date 2012-12-21 Time 15:55 Sent To  
Notes
2012-12-21 16:47:13ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 12.21.2012
 PERMIT NO.: 12120434
 ADDRESS: 1921 SOUTH DIXIE HIGHWAY
 CONTRACTOR/CONTACT:
 TELEPHONE NO.: 561.436.3370
 SCOPE OF REVIEW: NEW CONCRETE FLOOR, NEW ELECTRIC, A/C
 AND HVAC.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PLANS INDICATE THE ADDITION OF A/C MECHANICAL
 EQUIPMENT, AS WELL AS A GENERATOR, ON TOP OF THE
 EXISTING ROOF. PLEASE PROVIDE ADDITIONAL INFORMATION,
 SECTIONS, DETAILS, ETC. TO ENSURE THAT THE EQUIPMENT IS
 NOT VISIBLE FROM SURROUNDING PROPERTIES AND/OR THE
 PUBLIC RIGHT-OF-WAY. IT IS UNCLEAR AS TO THE SIZE OF
 THE EQUIPMENT, HEIGHT UPON WHICH IS MOUNTED ABOVE THE
 ROOF, ETC.
  
 2. THE PLANS SHOW ?EXISTING? TILE ROOFING ALONG THE
 EAST AND SOUTH PARAPETS, HOWEVER, AERIAL PHOTOS OF THE
 PROPERTY DO NOT SHOW THIS. PLEASE EXPLAIN. IS THIS WORK
 PART OF THE SCOPE OF THE RENOVATIONS?
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  
2012-12-18 17:22:3712/18/12