Plan Review Details - Permit 12120395
Plan Review Stops For Permit 12120395
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-02-27 Cont ID  
Sent By jwitmer Date 2013-02-27 Time 14:39 Rev Time 0.00
Received By jwitmer Date 2013-02-27 Time 14:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-02-07 Cont ID  
Sent By jwitmer Date 2013-02-07 Time 09:59 Rev Time 0.00
Received By jwitmer Date 2013-02-07 Time 09:59 Sent To  
Notes
2013-02-07 11:07:38BUILDING PLAN REVIEW
 PERMIT: 12120395
 ADD: 1500 N DIXIE HWY SUITE # 100
 CONT: THOMAS ROGERS INC
 TEL: (561)324-6944
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 FEB. 07/2013
 ACTION: DENIED
  
 1-4) COMPLIED.
  
 5) 2010 FBC-ACCESSIBILITY CODE. 202.4.1
 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE
  
 COST OF THE ALTERATION TO THE PRIMARY FUNCTION AREA.
 COSTS THAT MAY BE COUNTED AS EXPENDITURES REQUIRED TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I)
 COSTS ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE
 AND AN ACCESSIBLE ROUTE TO THE ALTERED AREA; (II) COSTS
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 INSTALLING GRAB BARS, ENLARGING TOILET STALLS,
 INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET
 CONTROLS; (III) COSTS ASSOCIATED WITH PROVIDING
 ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE
 TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION
 DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV)
 COSTS ASSOCIATED WITH RELOCATING AN INACCESSIBLE
 DRINKING FOUNTAIN.
  
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 THE CONTRACT VALUE OFF $22,000.00 MEANS THAT AN
 ADDITIONAL $4,400.00 NEEDS TO BE INVESSTED INTO THE
 PROJECT TO BRING THIS PORTION IN TO CODE COMPLIANCE FOR
 THE 2010 FL ACCESSIBILITY CODE. THE PLANS APPEAR TO
 HAVE A ACCESSIBLE ENTRANCE, THE INTERIOR DOORS DO NOT
 COMPLY THE DOORS WITH THE 45% WALLS AND INSWING DOORS
 FAIL TO PROVIDE THE REQUIRED 18 INCHES LATCH SIDE OF
 THE DOOR. 2010 FL ACCESSIBILITY CODE 404.2.4, FIGURE
 404.2.4.1.(A).
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-12-13 Cont ID  
Sent By jwitmer Date 2012-12-13 Time 13:04 Rev Time 0.00
Received By jwitmer Date 2012-12-13 Time 12:11 Sent To  
Notes
2012-12-13 13:04:00BUILDING PLAN REVIEW
 PERMIT: 12120395
 ADD: 1500 N DIXIE HWY SUITE # 100
 CONT: THOMAS ROGERS INC
 TEL: (561)324-6944
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DEC. 13/2012
 ACTION: DENIED
  
 1) THIS WILL BE CONSIDERED A PHASED PERMIT. THE
 BUILDING PERMIT WILL NOT BE ISSUED UNTIL THE MEP TRADES
 HAVE MADE APPLICATION FO PREMIT, AT THAT TIME IF ALL
 OTHER REQUIREMENTS ARE MET THE BUILDING PERMIT WILL BE
 ISSUED.
  
 2) THIS IS A COMMERCIAL CONDOMINIUM, PLEASE PROVIDE THE
 WHOLE FLOOR PLAN OF THIS FLOOR TO SEE WHAT WALLS
 REQUIRE FIRE RATED WALLS, TENANT SEPERATION WALLS,
 CORRIDOR WALLS, IS THE FIRST FLOOR CEILING BEING
 REMOVED, THIS WOULD BE A ONE HOUR RATED FLOOR / CEILING
 ASSEMBLY, IF THIS BUILDING IS FIRE SPRINKLERED OR NOT?
 2010 FBC- ADMINISTRATIVE CODE 107.3.5.1.1. MINIMUM
 CRITERIA FOR COMMERCIAL PLAN REVIEW
  
 1006.3 EXIT SIGNS. 1006.3.1
 EXITS SHALL BE MARKED BY AN APPROVED SIGN READILY
 VISIBLE FROM ANY DIRECTION OF EXIT ACCESS. EVERY EXIT
 SIGN SHALL BE SUITABLY ILLUMINATED BY A RELIABLE LIGHT
 SOURCE. EXTERNALLY AND INTERNALLY ILLUMINATED SIGNS
 SHALL BE VISIBLE IN BOTH NORMAL AND EMERGENCY LIGHTING.
  
  
 . PLEASE NOTE THE NOTE FOR WALL TYPES ARE NOT LEGABLE
 AND FOR RECORD RETENSION, (SCANNING) WILL NOT SHOW UP,
 THEY WILL NEED TO BE BETTER IDENTIED, BOLDER, BLACK
 INK. 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING
 PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT.
  
 3) THE DESIGNER OF RECORD SHALL SIGN AND PRINT THEIR
 NAME AND LICENSE NUMBER ON THE PLANS, 107.3.4.3
 CERTIFICATIONS BY CONTRACTORS AUTHORIZED UNDER THE
 PROVISIONS OF SECTION 489.115 FLORIDA STATUTES, SHALL
 BE CONSIDERED EQUIVALENT TO SEALED PLANS AND
 SPECIFICATIONS BY A PERSON LICENSED UNDER CHAPTER 471,
 FLORIDA STATUTES, OR CHAPTER 481 FLORIDA STATUTES, BY
 LOCAL ENFORCEMENT AGENCIES ...
  
 4) THE DESIGNER OF RECORD, SHALL SELECT A COMPLIANCE
 METHOD UNDER THE 2010 FBC-EXISSTING BUILDING CODE,
 101.5 COMPLIANCE METHODS.
  
 5) 2010 FBC-ACCESSIBILITY CODE. 202.4.1
 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE
  
 COST OF THE ALTERATION TO THE PRIMARY FUNCTION AREA.
 COSTS THAT MAY BE COUNTED AS EXPENDITURES REQUIRED TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I)
 COSTS ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE
 AND AN ACCESSIBLE ROUTE TO THE ALTERED AREA; (II) COSTS
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 INSTALLING GRAB BARS, ENLARGING TOILET STALLS,
 INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET
 CONTROLS; (III) COSTS ASSOCIATED WITH PROVIDING
 ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE
 TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION
 DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV)
 COSTS ASSOCIATED WITH RELOCATING AN INACCESSIBLE
 DRINKING FOUNTAIN.
  
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2013-02-27 Cont ID  
Sent By rlecky Date 2013-02-27 Time 14:18 Rev Time 0.00
Received By rlecky Date 2013-02-27 Time 14:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-02-07 Cont ID  
Sent By rlecky Date 2013-02-07 Time 16:22 Rev Time 0.00
Received By rlecky Date 2013-02-07 Time 14:40 Sent To  
Notes
2013-02-07 16:22:5612120395
 1500 N. DIXIE HIGHWAY # 100
 INTERIOR REPAIR OF WATER DAMAGE
  
 THE FOLLOWING WAS NOTED ON THE PLANS.
  
 PROVISO
 THE SCOPE OF THE ELECTRICAL WORK IS LIMITED TO REPAIR
 OF WATER DAMAGED EQUIPMENT.
 A SEPARATE ELECTRIC PERMIT IS REQUIRED.
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-12-17 Cont ID  
Sent By rlecky Date 2012-12-17 Time 08:00 Rev Time 0.00
Received By rlecky Date 2012-12-17 Time 07:58 Sent To  
Notes
2012-12-17 08:03:23SCOPE OF ELECTRICAL WORK NOT SHOWN.
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-02-12 Cont ID  
Sent By wjolin Date 2013-02-12 Time 12:40 Rev Time 0.00
Received By wjolin Date 2013-02-04 Time 13:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-12-14 Cont ID  
Sent By wjolin Date 2012-12-14 Time 08:56 Rev Time 0.00
Received By wjolin Date 2012-12-14 Time 08:40 Sent To E
Notes
2012-12-14 08:56:241500 NORTH DIXIE HIGHWAY - SUITE #100
 PERMIT #12120395
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DETAILED PLANS SHOWING THE SCOPE OF THE MECHANICAL,
 ELECTRICAL, AND DRYWALL WORK NEED TO BE SUBMITTED.
 SIMPLY STATING "REPLACE" ON THE PERMIT APPLICATION IS
 TOO GENERAL.
  
 INDICATE ON THE PLANS, THE HOURLY FLOOR-TO-FLOOR FIRE
 SEPARATION.
  
 THE WALL TYPE TAGS ARE ILLEGIBLE.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-02-27 Cont ID  
Sent By jwitmer Date 2013-02-27 Time 14:39 Rev Time 0.00
Received By jwitmer Date 2013-02-27 Time 14:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-02-12 Cont ID  
Sent By wjolin Date 2013-02-12 Time 12:40 Rev Time 0.00
Received By wjolin Date 2013-01-31 Time 14:42 Sent To  
Notes
2013-01-31 14:45:09EXPEDITED, 2ND RUN
 B--10
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-12-17 Cont ID  
Sent By rlecky Date 2012-12-17 Time 08:01 Rev Time 0.00
Received By rlecky Date 2012-12-12 Time 08:01 Sent To  
Notes
***NONE***