Plan Review Details - Permit 12120394
Plan Review Stops For Permit 12120394
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-03-04 Cont ID  
Sent By jgomez Date 2013-03-04 Time 15:53 Rev Time 0.00
Received By jgomez Date 2013-03-04 Time 15:52 Sent To  
Notes
2013-03-04 15:56:33BUILDING REVIEW APPROVED WITH PROVISO:
 1- REVISE ENERGY CALCULATIONS: A) ITEM #7 EXCEEDS THE
 20% OF GLASS AREA. FORM 402-2010 CAN'T BE USED. SEE
 GENERAL INSTRUCTIONS #1 ON TOP OF FORM. B) ITEM #9A2
 AND ARCHITECTURAL PLANS NEED TO BE COORDINATED AND
 MATCH. C) PROVIDE NAME OF BUILDER ON TOP OF FORM.
 2- PROVIDE SOIL TEST REPORT (2 COPIES). SEC. R401.4 OF
 2010 FBC-RESIDENTIAL.
 ***NOTE: THIS MAY BE SUBMITTED LATER, BUT IT WILL BE ON
 CONTRACTOR'S OWN RISK IF FOOTINGS NEED TO BE
 RE-DESIGNED.
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) CONCRETE TILE TO BE USED ON 2:12 PITCH. NOA
 12-0529.12 DOESN'T ALLOW 2:12 PITCH.
 B) CONCRETE TILE ADHESIVE AS LISTED ON CONCRETE TILE
 PRODUCT APPROVAL.
 C) SIMPSON CONNECTOR HGAM10. OR, APPLY FOR LOCAL
 PRODUCT APPROVAL.
 D) DOORS WITH SIDELITES AS SHOWN ON PLANS. NEED DOORS
 THAT MEET THE CALCULATED DESIGN PRESSURES.
 E) PRECAST LINTELS AS SPECIFIED ON PLANS. NEED 8"
 PRECAST LINTELS.
 4- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ABOVE PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS
 TO FBC.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-02-26 Cont ID  
Sent By jgomez Date 2013-02-26 Time 09:41 Rev Time 0.00
Received By jgomez Date 2013-02-26 Time 09:41 Sent To  
Notes
2013-02-26 10:07:30BUILDING REVIEW COMMENTS:
  
 1-REVISE ENERGY CALCULATIONS: A) ITEM #7 EXCEEDS THE
 20% OF GLASS AREA. FORM 402-2010 CAN'T BE USED. SEE
 GENERAL INSTRUCTIONS #1 ON TOP OF FORM. B) ITEM #9A2
 AND ARCHITECTURAL PLANS NEED TO BE COORDINATED AND
 MATCH. C) PROVIDE NAME OF BUILDER ON TOP OF FORM.
  
 2- PROVIDE SOIL TEST REPORT (2 COPIES). SEC. R401.4 OF
 2010 FBC-RESIDENTIAL.
 ***NOTE: THIS MAY BE SUBMITTED LATER, BUT IT WILL BE ON
 CONTRACTOR'S OWN RISK IF FOOTINGS NEED TO BE
 RE-DESIGNED.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) FLAT ROOF. RAS 117 CALCULATIONS NEED TO HAVE
 ENGINEER'S ORIGINAL SEAL AND SIGNATURE, NOT COPY.
 B) CONCRETE TILE TO BE USED ON 2:12 PITCH. NOA
 12-0529.12 DOESN'T ALLOW 2:12 PITCH.
 C) CONCRETE TILE ADHESIVE AS LISTED ON CONCRETE TILE
 PRODUCT APPROVAL.
 D) SIMPSON CONNECTOR HGAM10. OR, APPLY FOR LOCAL
 PRODUCT APPROVAL.
 E) DOORS WITH SIDELITES AS SHOWN ON PLANS. NEED DOORS
 THAT MEET THE CALCULATED DESIGN PRESSURES.
 F) PRECAST LINTELS AS SPECIFIED ON PLANS. NEED 8"
 PRECAST LINTELS.
  
 4- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ABOVE PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS
 TO FBC.
  
 ***NOTE:
 NEED IMPACT FEES STAMP AND PAID RECEIPT IF FEES ARE
 DUE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-12-27 Cont ID  
Sent By jgomez Date 2012-12-27 Time 15:54 Rev Time 0.00
Received By jgomez Date 2012-12-27 Time 12:04 Sent To  
Notes
2012-12-27 16:24:58RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC
  
 1- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY BUILDING (2300 N. JOG RD.) TO VERIFY IF IMPACT
 FEES ARE DUE. BRING BACK COUNTY STAMPED PLANS AND COPY
 OF PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 101.4.3 AND SEC. 103.2.1 OF 2010 FBC-ENERGY
 CONSERVATION. PLEASE MAKE SURE FORM IS COORDINATED WITH
 ARCHITECT'S PLANS, COMPLETED COMPLETELY AND SIGNED BY
 ALL THE REQUIRED PARTIES.
  
 3- DESIGN PRESSURES SHOWN FOR SECOND FLOOR WINDOWS
 LOCATED ON THE END ZONE ARE LOW. ACCORDING TO SEC.
 R301.2.1.4.3 THIS HOUSE IS LOCATED ON EXPOSURE "D".
 PROVIDE CALCULATIONS THAT REFLECT THE WIND EXPOSURE,
 THE BUILDING HEIGHT AND LOCATION OF OPENINGS (INTERIOR
 OR END LOCATION). SEC. 107.2.1.3 CITY AMENDMENTS TO
 FBC.
  
 4- PROVIDE SOIL TEST REPORT (2 COPIES). SEC. R401.4 OF
 2010 FBC-RESIDENTIAL.
  
 5- SHEET SP-1: NOTE LOCATED BELOW THE LOCATION MAP
 STATES THAT PURSUANT TO THE EXISTING BUILDING CODE THE
 LEVEL OF ALTERATION SHALL COMPLY WITH SECTION 305 AND
 ALTERATION LEVEL 3. REVISE THIS STATEMENT BECAUSE
 SECTION 305 REFERS TO FIRE ESCAPES AND THIS DOESN'T
 APPLY TO THIS PROJECT. AND, THIS IS NOT LEVEL 3
 ALTERATION. THIS IS AN ADDITION AND NEEDS TO COMPLY
 WITH CHAPTER 10. REVISE AS REQUIRED.
  
 6- NEED CARBON MONOXIDE ALARMS INSTALLED WITHIN 10 FEET
 OF EACH SLEEPING ROOM. SEC. R315 OF 2010 FBC-2010.
 CARBON MONOXIDE ALARM SHOWN ON SHEET ME-2 IS NOT
 SHOWING ALARM WITH 10 FEET OF MASTER BEDROOM. REVISE AS
 REQUIRED.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) FLAT ROOF. AND CLEARLY IDENTIFY SELECTED APPROVED
 ASSEMBLY (NOTE THAT ARCHITECT IS SPECIFYING INSULATION
 ON THE FLAT ROOF ASSEMBLY. SEE SEC. B/A-4 AND WALL
 SECTION D-4/A-5). AND, PROVIDE SIGNED AND SEALED RAS
 117 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND
 CORNER AREAS AS REQUIRED BY GENERAL LIMITATION #7.
 THESE CALCULATIONS ARE REQUIRED TO COMPLY WITH THE
 DESIGN PRESSURES FOR WIND EXPOSURE "D" AS REQUIRED BY
 SEC. R301.2.4.3 OF 2010 FBC-RESIDENTIAL.
  
 B) CONCRETE TILE.
  
 ***NOTE: TAKE INTO CONSIDERATION THAT PLANS CALL FOR
 2:12 PITCH. NEED PRODUCT APPROVAL FOR CONCRETE TILE
 THAT IS DESIGNED FOR A 2:12 PITCH.
  
 C) CONCRETE TILE ADHESIVE AS LISTED ON CONCRETE TILE
 PRODUCT APPROVAL.
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS. PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE AND
 PAGE SHOWING THE SPECIFIED CONNECTOR.
  
 E) ALL DOORS AS SHOWN ON PLANS. INCLUDING DOORS WITH
 SIDELITES.
  
 F) ALL WINDOWS AS SHOWN ON PLANS.
  
 G) SHUTTERS IF DOOR AND WINDOWS DON'T HAVE IMPACT
 GLASS. AND, PROVIDE COMPLETE INSTALLATION SCHEDULE.
  
 H) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL THE PRODUCT APPROVALS.
 SEC. 107.3.4.1 CITY AMENDMENTS TO FBC.
  
 9- PROVIDE ICYNENE INSULATION MANUFACTURER SPECS TO
 VERIFY COMPLIANCE WITH SEC. R316 OF 2010
 FBC-RESIDENTIAL.
  
 10- THERE ARE TWO SHEETS LABELED A-4. IT LOOKS LIKE ONE
 OF THEM SHOULD BE LABELED A-2 AS SHOWN ON THE DRAWING
 LIST. CLARIFY AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 11- SHEET A-8: CLARIFY INFORMATION. ROOF FRAMING PLAN
 SHOWS SPECIFICATIONS FOR FOUNDATION PLAN. AND, CORRECT
 LABELING OF THE WALL SECTIONS. SECTION A/A-4 AND
 SECTION B/A-4 ON SHEET A-10 ARE CONFLICTING.
 REVISE/COORDINATE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 12- SHEET A-9:
 A) ROOF PLAN. EMERGENCY ROOF SCUPPER AND PRIMARY ROOF
 SCUPPER ARE SHOWN ON TWO DIFFERENT LOW POINT LOCATIONS.
 THIS DOESN'T COMPLY WITH SEC. R903.4 AND SEC. R903.4.1
 OF 2010 FBC-RESIDENTIAL. EMERGENCY SCUPPER NEEDS TO BE
 NOT LESS THAN 2" ABOVE THE FINISHED ROOF COVERING. AND
 SHALL BE LOCATED AS CLOSE AS POSSIBLE TO THE PRIMARY
 ROOF SCUPPER. REVISE AS REQUIRED.
  
 B) REVISE NOTE #2 ON THE ROOF ZONES FOR C & C. THE
 MINIMUM DIMENSION FOR "A" IS 4'-0". SEE FOOTNOTE ON
 FIGURE R301.2.(7) OF 2010 FBC-RESIDENTIAL AND REVISE AS
 REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-03-01 Cont ID  
Sent By RLECKY Date 2013-03-01 Time 09:28 Rev Time 0.00
Received By rlecky Date 2013-03-01 Time 08:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-12-28 Cont ID  
Sent By rlecky Date 2012-12-28 Time 13:48 Rev Time 0.00
Received By rlecky Date 2012-12-28 Time 11:55 Sent To  
Notes
2012-12-28 13:48:48THE FOLLOWING CODE REQUIREMENTS WERE NOTED ON THE PLAN.
  
 PROVISO:
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS. NEC 210.12
 GFCI PROTECTION IS REQUIRED FOR ALL OUTDOOR
 RECEPTACLES. NEC 210.8
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-03-04 Cont ID  
Sent By jgomez Date 2013-03-04 Time 15:53 Rev Time 0.00
Received By jgomez Date 2013-03-04 Time 15:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-03-01 Cont ID  
Sent By rlecky Date 2013-03-01 Time 09:29 Rev Time 0.00
Received By rlecky Date 2013-02-06 Time 17:00 Sent To  
Notes
2013-02-06 17:00:47SENT TO R7 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-12-28 Cont ID  
Sent By rlecky Date 2012-12-28 Time 13:49 Rev Time 0.00
Received By rlecky Date 2012-12-12 Time 11:28 Sent To  
Notes
2012-12-13 11:30:11INCOMING SENT TO R-6. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2013-03-04 Cont ID  
Sent By jgomez Date 2013-03-04 Time 15:59 Rev Time 0.00
Received By jgomez Date 2013-03-04 Time 15:59 Sent To  
Notes
2013-03-04 16:00:18MU-2013-4922. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2013-02-26 Cont ID  
Sent By jgomez Date 2013-02-26 Time 15:05 Rev Time 0.00
Received By jgomez Date 2013-02-26 Time 15:05 Sent To  
Notes
2013-02-26 15:06:12BRING PLANS TO PALM BEACH COUNTY TO VERIFY IF IMPACT
 FEES ARE DUE. BRING BACK COUNTY STAMPED PLANS AND COPY
 OF PAID RECEIPT IF FEES ARE DUE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-12-27 Cont ID  
Sent By jgomez Date 2012-12-27 Time 13:23 Rev Time 0.00
Received By jgomez Date 2012-12-27 Time 13:23 Sent To  
Notes
2012-12-27 13:24:53BRING PLANS TO PALM BEACH COUNTY TO VERIFY IF IMPACT
 FEES ARE DUE. BRING BACK COUNTY STAMPED PLANS AND COPY
 OF PAID RECEIPT IF FEES ARE DUE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-02-26 Cont ID  
Sent By jgomez Date 2013-02-26 Time 15:25 Rev Time 0.00
Received By jgomez Date 2013-02-26 Time 15:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-12-19 Cont ID  
Sent By tgordon Date 2012-12-19 Time 09:04 Rev Time 0.00
Received By tgordon Date 2012-12-19 Time 07:42 Sent To  
Notes
2012-12-19 09:04:13** CORRECTIONS NEEDED FOR MECHANICAL PLAN REVIEW ***
  
 1) PLEASE SUBMIT ENERGY CALCULATIONS, SEE 2010
 FBC/ENERGY 401.2.
  
 2) SUBMIT COOLING LOAD CAL'S. PER 2010 FBC/ENERGY
 403.6.1.
  
 3) SHOW ON MECHANICAL PLAN THE LOCATION OF THE
 CONDENSER UNIT. ALSO SHOW AN A/C EQUIPMENT LISTING WITH
 MAKE, SIZE, SEER, BTU'S TOTAL & SENSIBLE, ETC. PER 2010
 CITY OF WPB AMEND. 107.3.5.3 (10).
  
 MECHANICAL PLAN REVIEW BY:
 TOM GORDON (HY-BYRD INC.) (561) 805-6732

Review Stop P PLUMBING
Rev No 1 Status N Date 2012-12-27 Cont ID  
Sent By jgomez Date 2012-12-27 Time 15:28 Rev Time 0.00
Received By jgomez Date 2012-12-27 Time 15:28 Sent To  
Notes
2012-12-27 15:29:28NO PLUMBING WORK SHOWN. JG.

Review Stop Z ZONING
Rev No 2 Status P Date 2013-02-08 Cont ID  
Sent By mdekle Date 2013-02-08 Time   Rev Time 0.00
Received By mdekle Date 2013-02-08 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2012-12-20 Cont ID  
Sent By mdekle Date 2012-12-20 Time   Rev Time  
Received By mdekle Date 2012-12-20 Time   Sent To  
Notes
2012-12-20 10:48:40PLANNING AND ZONING: ***** FAILED****
  
 1. PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE VALUE OF
 THE PROPOSED WORK ($162,119.00) EXCEEDS 50%
 ($155,633.00 ) OF THE STRUCTURE'S VALUE (LISTED AS
 "IMPROVEMENT VALUE" ($311,266.00) WITH THE P.B.C.
 PROPERTY APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN
 COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR.
  
 2. PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME
 AND/OR CONSULT THE CITY?S ZONING AND LAND
 DEVELOPMENT REGULATIONS ONLINE @WWW.MUNICODE.COM.
  
 MURRIAH DEKLE, MPA, PLANNER
 PLANNING & ZONING DIVISION
 TEL: (561) 822-1442
 EMAIL: [email protected]
 WWW.CITYOFWPB.COM
  
2012-12-18 17:16:1912/18/12