Plan Review Details - Permit 12120370
Plan Review Stops For Permit 12120370
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-01-07 Cont ID  
Sent By jwitmer Date 2013-01-07 Time 15:34 Rev Time 0.00
Received By jwitmer Date 2013-01-07 Time 15:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-12-20 Cont ID  
Sent By jwitmer Date 2012-12-20 Time 13:27 Rev Time 0.00
Received By jwitmer Date 2012-12-20 Time 13:27 Sent To  
Notes
2012-12-20 13:46:52BUILDING PLAN REVIEW
 PERMIT: 12120370
 ADD: 777 S FLAGLER DR
 CONT: JTL A/C & REFRIGARATION
 TEL: 954-584-0070
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET P2.0 & P5.2 PRIVACY WALL DETAIL HAS STRUCTURAL
 DETAILS FOR THE BUILDING OF A 10 X 10 FOOT PRIVACY WALL
 AND FOOTER. THE PRIVACY WALL FOOTER APPEARS TO HAVE A
 SLAB
 AT THE SAME LEVEL OF THE FOOTER? IT ALSO APPEARS TO
 HAVE REINFORCEMENT IN IT? ADDITIONAL INFORMATION
 REQUIRED? 107.1.2.
  
 2) IN BOTH SHEET P2.0 & P5.2 IT APPEARS THAT THE
 RETAINING WALLS ARE BUILT UP TO A SECONDARY SLAB POUR,
 THEN ONLY 3 WALLS CONTINUE 2'-0" ABOVE THE SECONDARY
 SLAB, PLEASE PROVIDE THE DIRECTION NORTH IN THE DETAIL
 TO KNOW WHICH WALL STOPS AT THE SLAB. ADDITIONAL
 INFORMATION IS REQUIRED? 107.1.2.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-12-21 Cont ID  
Sent By rlecky Date 2012-12-21 Time 14:35 Rev Time 0.00
Received By rlecky Date 2012-12-21 Time 14:28 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-01-08 Cont ID  
Sent By tgordon Date 2013-01-08 Time 08:08 Rev Time 0.00
Received By tgordon Date 2013-01-03 Time 08:10 Sent To  
Notes
2013-01-04 08:11:13SENT TO PLUMBING BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-12-26 Cont ID  
Sent By lwagner Date 2012-12-26 Time 08:28 Rev Time 0.00
Received By lwagner Date 2012-12-13 Time 11:23 Sent To  
Notes
2012-12-13 11:24:24INCOMING SENT TO MECHANICAL BOX. JW

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-01-08 Cont ID  
Sent By tgordon Date 2013-01-08 Time 08:08 Rev Time 0.00
Received By tgordon Date 2013-01-08 Time 08:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-12-18 Cont ID  
Sent By tgordon Date 2012-12-18 Time 11:19 Rev Time 0.00
Received By tgordon Date 2012-12-18 Time 11:19 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-01-04 Cont ID  
Sent By lwagner Date 2013-01-04 Time 13:10 Rev Time 0.00
Received By lwagner Date 2013-01-04 Time 12:29 Sent To B
Notes
2013-01-04 12:35:40**PROVISO**
 A WELL PERMIT FROM PALM BEACH COUNTY HEALTH DEPT. IS
 REQUIRED FOR THE WELL. A COPY OF THE PERMIT IS REQUIRED
 ONSITE AT TIME OF INSPECTION.
 HTTP://WWW.PBCHD.COM/ENV/ENVIRONMENTAL.HTML

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-12-26 Cont ID  
Sent By lwagner Date 2012-12-26 Time 08:27 Rev Time 0.00
Received By lwagner Date 2012-12-18 Time 13:45 Sent To  
Notes
2012-12-19 09:20:59 
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
  
 1. THE WATER SOFTENER BACK WASH DRAIN IS REQUIRED TO
 DRAIN TO THE SANITARY.
 SEC. 90-203. - PROHIBITED DISCHARGES; ILLICIT
 CONNECTIONS.
 (A)
 GENERAL PROHIBITION. EXCEPT AS PROVIDED IN SECTION
 90-205, AND EXCEPT PURSUANT TO A VALID NPDES PERMIT, IT
 SHALL BE UNLAWFUL FOR ANY PERSON TO DIRECTLY OR
 INDIRECTLY DEPOSIT, DISCHARGE, SPILL, OR DUMP INTO ANY
 OF THE PUBLIC WATERS OR MUNICIPAL SEPARATE STORM SEWER
 SYSTEM WITHIN THE CITY, ANY SUBSTANCE OTHER THAN THAT
 COMPOSED ENTIRELY OF STORMWATER.
  
 2. THE WELL WATER CAN NOT INTERCONNECT WITH THE CITY
 WATER FOR THE IRRIGATION SYSTEM. THE COOLING TOWERS
 WILL BE OK IF THERE IS AN AIR GAP.
 SEC. 90-33. - REGULATION OF CROSS CONNECTION.
 AS USED IN THIS SECTION, THE TERM "CROSS CONNECTION"
 MEANS ANY PHYSICAL ARRANGEMENT WHEREBY THE CITY'S
 PUBLIC WATER SYSTEM IS CONNECTED, DIRECTLY OR
 INDIRECTLY, WITH ANY OTHER WATER SUPPLY SYSTEM...
  
 NOTE** A WELL PERMIT FROM PALM BEACH COUNTY HEALTH
 DEPT. IS REQUIRED FOR THE WELL. A COPY OF THE PERMIT IS
 REQUIRED ONSITE AT TIME OF INSPECTION.
 HTTP://WWW.PBCHD.COM/ENV/ENVIRONMENTAL.HTML
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  