Plan Review Details - Permit 12120366
Plan Review Stops For Permit 12120366
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-01-07 Cont ID  
Sent By shill Date 2013-01-07 Time 10:53 Rev Time 0.00
Received By shill Date 2013-01-07 Time 10:53 Sent To  
Notes
2013-01-07 11:14:02****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. SCREEN ROOF PLAN IS TOO SMALL TO READ AND SCAN,
 WALLS DO NOT SHOW DIMENSIONS OF ALUMINUM MEMBERS AND
 SPANS. PROVIDE A PLAN, 1/8" SCALE MINIMUM, FBC 107.
  
 2. PLAN REQUIRES A MINIMUM 8X8 FOOTER. NO FOOTER
 PROPOSED ON THE PLAN, SO HOW HAVE YOU DETERMINED THAT
 AN 8X8 FOOTER WITH 1 #5 IS EXISTING? FBC 301.
  
 3. IT IS NOT CLEAR WHERE THE SCREEN ROOF WILL BE
 INSTALLED. PLAN SHOWS A HATCHED 12X12 AREA, NON
 CONSISTENT WITH THE ROOF PLAN. PROVIDE A SITE PLAN
 WHICH CLEARLY SHOWS EXISTING AND PROPOSED. A SURVEY
 WOULD BE HELPFUL. FBC 106.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-01-07 Cont ID  
Sent By shill Date 2013-01-07 Time 11:14 Rev Time 0.00
Received By shill Date 2013-01-02 Time 12:47 Sent To  
Notes
2013-01-02 12:47:31IN ZONING BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2013-01-03 Cont ID  
Sent By mdekle Date 2013-01-03 Time   Rev Time  
Received By mdekle Date 2013-01-02 Time   Sent To B
Notes
2013-01-03 15:13:02PROVISO: ALL IMPROVEMENTS MUST BE LOCATED WITHIN/ON THE
 EXISTING FRONT AND REAR BUILDING SLABS.