Plan Review Details - Permit 12120268
Plan Review Stops For Permit 12120268
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-12-19 Cont ID  
Sent By wjolin Date 2012-12-19 Time 11:48 Rev Time 0.00
Received By wjolin Date 2012-12-19 Time 11:44 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-12-11 Cont ID  
Sent By wjolin Date 2012-12-11 Time 10:23 Rev Time 0.00
Received By wjolin Date 2012-12-11 Time 10:19 Sent To M
Notes
2012-12-11 10:22:561475 CENTREPARK BLVD - #130
 PERMIT #12120268
 MASTER #12100851
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FOUR SPRINKLERS ARE LOCATED MORE THAN 9'-0" (MEASURED
 PERPENDICULAR) IN "SMALL ROOMS" #128 AND #129.
  
 FOR SYSTEM PRESSURES EXCEEDING 100 PSI, ARMOVERS AND
 END OF BRANCH LINE PENDENT SPRINKLERS SHALL BE
 PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL BE
 LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE
 THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING
 UPWARD MOVEMENT.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-12-19 Cont ID  
Sent By tgordon Date 2012-12-19 Time 15:53 Rev Time 0.00
Received By tgordon Date 2012-12-18 Time 14:48 Sent To  
Notes
2012-12-18 14:48:08TO FIRE
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-12-12 Cont ID  
Sent By lmartine Date 2012-12-12 Time 15:34 Rev Time 0.00
Received By lmartine Date 2012-12-10 Time 15:25 Sent To  
Notes
2012-12-10 15:25:45TO FIRE
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-12-19 Cont ID  
Sent By tgordon Date 2012-12-19 Time 15:53 Rev Time 0.00
Received By tgordon Date 2012-12-19 Time 15:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-12-12 Cont ID  
Sent By lmartine Date 2012-12-12 Time 15:33 Rev Time 0.00
Received By lmartine Date 2012-12-12 Time 15:33 Sent To  
Notes
2012-12-12 15:34:29SEE FIRE REVIEW NOTES AND MAKE CORRECTIONS.