Plan Review Details - Permit 12120223
Plan Review Stops For Permit 12120223
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2013-01-31 Cont ID  
Sent By shill Date 2013-01-31 Time 15:49 Rev Time 0.00
Received By shill Date 2013-01-31 Time 15:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2013-01-29 Cont ID  
Sent By shill Date 2013-01-29 Time 15:55 Rev Time 0.00
Received By shill Date 2013-01-29 Time 15:55 Sent To  
Notes
2013-01-29 16:30:27****PROVISOS****
 ****REVISION REQUIRED PRIOR TO INSPECTION****
 ****ISSUED AT CONTRACTOR'S RISK****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. ENGINEERING TO BE SIGNED, SEALED, DATED ORIGINALS
 FS471. THE LETTER FROM THE ENGINEER WHICH STATES THAT
 THE DESIGN IS FOR FRAMES WITH STAPLED FABRIC IS TO HAVE
 AN ORIGINAL SIGNATURE AND A FLORIDA SEAL (CALIFORNIA
 SEAL PROVIDED).
  
 2. ENGINEER TO REVIEW THE SHOP DRAWINGS FOR VALANCE AND
 IS TO SPECIFY STAPLES (SIZE, SPACING) WHICH IS REQUIRED
 TO RESIST WIND LOADS FBC 1609.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2013-01-16 Cont ID  
Sent By shill Date 2013-01-16 Time 10:41 Rev Time 0.00
Received By shill Date 2013-01-16 Time 10:37 Sent To  
Notes
2013-01-16 10:41:56****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 2ND RESUB (SUBMITTED PRIOR TO 2ND REVIEW)
 INCLUDED CITY PLACE STAMP ONLY
  
 FROM PREVIOUS LIST:
  
 1.) DESIGN CRITERIA STATED BUT NOT CLEAR WHETHER THIS
 IS WITH AWNING COVER IN PLACE, SEE FBC3105.4.
  
 2ND REVIEW, A NEW SHEET INDICATES THAT CANVAS AWNING IS
 PROPOSED. REVISE ENGINEERING TO CLARIFY DESIGN CRITERIA
 PER FBC 3105.4.
  
 2.) IF DESIGNED FOR FABRIC REMOVAL WHEN WINDS EXCEED
 75MPH, PROVIDE AWNING FABRIC REMOVAL INSTRUCTIONS TO
 SHOW COMPLIANCE WITH FBC3105.4.2.1, QUICK RELEASE. THE
 INSTRUCTIONS SHOULD CONSIST OF A SERIES OF PHOTOGRAPHS.
 THIS IS TO BE APPROVED BY THE BUILDING OFFICIAL.
  
 3.) IF DESIGNED FOR FABRIC REMOVAL WHEN WINDS EXCEED
 75MPH, PER BUILDING OFFICIAL, WE ARE TO PUT ON THE
 PERMIT FILE A LETTER, OR CONTRACTORS FORM, SIGNED BY
 THE OWNER (NOT THE TENANT) TO ACKNOWLEDGE THEIR
 RESPONSIBILITY TO HAVE THE AWNING COVER REMOVED PRIOR
 TO ANY WIND EVENT WITH PROJECTED WIND SPEEDS OF 75 MPH
 OR GREATER. THE LETTER/FORM MUST BE SIGNED BY THE OWNER
 BUT IT NEED NOT BE NOTARIZED.
  
 4.) FBC3501.3.5, PROVIDE DOCUMENTATION TO SHOW THAT THE
 FABRIC MEETS THE REQUIREMENT OF NFPA701.
  
 5.) FBC3105.1.1, FBC 1003.3.1, PROVIDE HEIGHT OF LOWEST
 PORTION OF AWNING AS WELL AS A SITE PLAN TO SHOW
 PROPOSED LOCATIONS.
  
 THE FONT WHICH STATES THAT THIS IS 8'6" MIN IS SO SMALL
 THAT IT CANNOT BE SCANNED. IT APPEARS THAT THIS PLAN
 MAY HAVE BEEN A LARGER PLAN WHICH WAS REDUCED TO 8 1/2
 X 11. LEGIBLE PLANS REQUIRED, FBC 107.
  
 6.) OK.
  
 7.) OK
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-01-16 Cont ID  
Sent By shill Date 2013-01-16 Time 10:21 Rev Time 0.00
Received By shill Date 2013-01-16 Time 10:21 Sent To  
Notes
2013-01-16 10:36:20****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 1.) DESIGN CRITERIA STATED BUT NOT CLEAR WHETHER THIS
 IS WITH AWNING COVER IN PLACE, SEE FBC3105.4.
  
 2ND REVIEW, A NEW SHEET INDICATES THAT CANVAS AWNING IS
 PROPOSED. REVISE ENGINEERING TO CLARIFY DESIGN CRITERIA
 PER FBC 3105.4.
  
 2.) IF DESIGNED FOR FABRIC REMOVAL WHEN WINDS EXCEED
 75MPH, PROVIDE AWNING FABRIC REMOVAL INSTRUCTIONS TO
 SHOW COMPLIANCE WITH FBC3105.4.2.1, QUICK RELEASE. THE
 INSTRUCTIONS SHOULD CONSIST OF A SERIES OF PHOTOGRAPHS.
 THIS IS TO BE APPROVED BY THE BUILDING OFFICIAL.
  
 3.) IF DESIGNED FOR FABRIC REMOVAL WHEN WINDS EXCEED
 75MPH, PER BUILDING OFFICIAL, WE ARE TO PUT ON THE
 PERMIT FILE A LETTER, OR CONTRACTORS FORM, SIGNED BY
 THE OWNER (NOT THE TENANT) TO ACKNOWLEDGE THEIR
 RESPONSIBILITY TO HAVE THE AWNING COVER REMOVED PRIOR
 TO ANY WIND EVENT WITH PROJECTED WIND SPEEDS OF 75 MPH
 OR GREATER. THE LETTER/FORM MUST BE SIGNED BY THE OWNER
 BUT IT NEED NOT BE NOTARIZED.
  
 4.) FBC3501.3.5, PROVIDE DOCUMENTATION TO SHOW THAT THE
 FABRIC MEETS THE REQUIREMENT OF NFPA701.
  
 5.) FBC3105.1.1, FBC 1003.3.1, PROVIDE HEIGHT OF LOWEST
 PORTION OF AWNING AS WELL AS A SITE PLAN TO SHOW
 PROPOSED LOCATIONS.
  
 THE FONT WHICH STATES THAT THIS IS 8'6" MIN IS SO SMALL
 THAT IT CANNOT BE SCANNED. IT APPEARS THAT THIS PLAN
 MAY HAVE BEEN A LARGER PLAN WHICH WAS REDUCED TO 8 1/2
 X 11. LEGIBLE PLANS REQUIRED, FBC 107.
  
 6.) OK.
  
 7.) CITY PLACE APPROVAL STAMP REQUIRED ON PLANS, SEE
 ZONING COMMENTS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-12-20 Cont ID  
Sent By shill Date 2012-12-20 Time 09:30 Rev Time 0.00
Received By shill Date 2012-12-20 Time 09:30 Sent To  
Notes
2012-12-20 09:37:37****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1.) DESIGN CRITERIA STATED BUT NOT CLEAR WHETHER THIS
 IS WITH AWNING COVER IN PLACE, SEE FBC3105.4.
  
 2.) IF DESIGNED FOR FABRIC REMOVAL WHEN WINDS EXCEED
 75MPH, PROVIDE AWNING FABRIC REMOVAL INSTRUCTIONS TO
 SHOW COMPLIANCE WITH FBC3105.4.2.1, QUICK RELEASE. THE
 INSTRUCTIONS SHOULD CONSIST OF A SERIES OF PHOTOGRAPHS.
 THIS IS TO BE APPROVED BY THE BUILDING OFFICIAL.
  
 3.) IF DESIGNED FOR FABRIC REMOVAL WHEN WINDS EXCEED
 75MPH, PER BUILDING OFFICIAL, WE ARE TO PUT ON THE
 PERMIT FILE A LETTER, OR CONTRACTORS FORM, SIGNED BY
 THE OWNER (NOT THE TENANT) TO ACKNOWLEDGE THEIR
 RESPONSIBILITY TO HAVE THE AWNING COVER REMOVED PRIOR
 TO ANY WIND EVENT WITH PROJECTED WIND SPEEDS OF 75 MPH
 OR GREATER. THE LETTER/FORM MUST BE SIGNED BY THE OWNER
 BUT IT NEED NOT BE NOTARIZED.
  
 4.) FBC3501.3.5, PROVIDE DOCUMENTATION TO SHOW THAT THE
 FABRIC MEETS THE REQUIREMENT OF NFPA701.
  
 5.) FBC3105.1.1, FBC 1003.3.1, PROVIDE HEIGHT OF LOWEST
 PORTION OF AWNING AS WELL AS A SITE PLAN TO SHOW
 PROPOSED LOCATIONS.
  
 6.) NO INFORMATION PROVIDED REGARDING AWNING COVER,
 REVISE PLAN TO INCLUDE, FBC 3501, 106.
  
 7.) CITY PLACE APPROVAL STAMP REQUIRED ON PLANS, SEE
 ZONING COMMENTS.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2013-01-31 Cont ID  
Sent By shill Date 2013-01-31 Time 15:49 Rev Time 0.00
Received By shill Date 2013-01-31 Time 10:43 Sent To  
Notes
2013-01-31 10:44:19****EXPEDITED****
  
 TO ZONING
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-01-30 Cont ID  
Sent By eschneid Date 2013-01-30 Time 10:42 Rev Time 0.00
Received By eschneid Date 2013-01-29 Time 14:44 Sent To  
Notes
2013-01-29 16:31:03**** EXPEDITED ****
 1/29 TO ZONING
  
2013-01-29 14:46:43EXPEDITED
 GAVE TO SAMANTHA

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-01-16 Cont ID  
Sent By shill Date 2013-01-16 Time 10:36 Rev Time 0.00
Received By shill Date 2012-12-21 Time 13:53 Sent To  
Notes
2012-12-21 13:54:09SENT TO ZONING SHELF FOR ERIC'S REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-12-20 Cont ID  
Sent By shill Date 2012-12-20 Time 09:38 Rev Time 0.00
Received By shill Date 2012-12-07 Time 16:47 Sent To  
Notes
2012-12-14 16:48:04SENT TO ZONING SHELF FOR REVIEW. JG.

Review Stop Z ZONING
Rev No 4 Status P Date 2013-01-31 Cont ID  
Sent By eschneid Date 2013-01-31 Time 15:24 Rev Time 0.50
Received By eschneid Date 2013-01-31 Time 15:24 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2013-01-30 Cont ID  
Sent By eschneid Date 2013-01-30 Time 10:42 Rev Time 0.50
Received By eschneid Date 2013-01-30 Time 09:29 Sent To  
Notes
2013-01-30 10:42:11FAILED
  
 1) REPEAT COMMENT: THE AWNINGS ARE SHOWN WITH A 10 INCH
 VALANCE. THE CITYPLACE MASTER SIGN PLAN REQUIRES THAT
 ALL AWNINGS ON STREET LEVEL MUST HAVE AN EIGHT (8) INCH
 VERTICAL VALANCE ALONG THE FRONT OF THE AWNING.
  
 A COPY OF THESE COMMENTS HAVE BEEN PROVIDED TO CARLOS
 BERNAL OF CITYPLACE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2013-01-08 Cont ID  
Sent By eschneid Date 2013-01-08 Time 08:51 Rev Time 0.50
Received By eschneid Date 2013-01-08 Time 08:51 Sent To B
Notes
2013-01-08 09:45:16FAILED
  
 1) REPEAT COMMENT: THE PROPOSED AWNING MATERIAL WAS NOT
 PROVIDED. PLEASE NOTE THAT THE CITYPLACE MASTER SIGN
 PLAN REQUIRES THAT AWNINGS SHALL BE A SUNBRELLA 100%
 SOLUTION DYED ACRYLIC OR SUNBRELLA FIRESIST 100%
 SOLUTION DYED MODACRYLIC MATERIAL (OR EQUIVALENT
 APPROVED BY CITYPLACE RETAIL IN WRITING). VINYL AWNINGS
 ARE PROHIBITED.
  
 2) REPEAT COMMENT: THE CITYPLACE MASTER SIGN PLAN
 REQUIRES THAT THE AWNING COLORS, COPY AND/OR LOGO SHALL
 BE APPROVED BY CITYPLACE RETAIL IN WRITING. PROVIDE A
 NOTARIZED LETTER FROM CITYPLACE THAT THEY HAVE APPROVED
 THE SPECIFIC AWNING COLORS.
  
 3) REPEAT COMMENT: NO DETAILS OF THE AWNING HEIGHT WERE
 PROVIDED. THE CITYPLACE MASTER SIGN PLAN REQUIRES THAT
 AWNINGS SHALL PROVIDE A MINIMUM OF EIGHT (8) FEET OF
 CLEARANCE BETWEEN THE FLOOR AND THE LOWEST POINT OF THE
 AWNING.
  
 4) REPEAT COMMENT: THE PROPOSED AWNINGS ARE SHOWN WITH
 5' (AWINING TYPES D & E) AND EITHER 2'-11" OR 3 FEET
 (AWNING TYPE F) PROJECTIONS. THE CITYPLACE MASTER SIGN
 PLAN REQUIRES THAT AWNINGS ON THE STREET LEVEL SHALL
 PROJECT FOUR (4) FEET FROM THE BUILDING FACADE, UNLESS
 OTHERWISE APPROVED BY CITYPLACE RETAIL IN WRITING.
 PROVIDE A NOTARIZED LETTER FROM CITYPLACE THAT THEY
 HAVE GRANTED THE SPECIFIC VARIANCES NEEDED TO CONSTRUCT
 THE PROPOSED AWNINGS.
  
 5) AWNING TYPE F IS SHOWN WITH TWO DIFFERENT
 PROJECTIONS - 2'11" ON THE ENGINEERING PLANS AND 3 FEET
 ON THE ARCHITECTURAL PLAN. PLEASE CLARIFY WHICH IS
 CORRECT AND ENSURE THAT ALL PLANS SHOW THE SAME
 DIMENSION CONDITION.
  
 6) REPEAT COMMENT: THE AWNINGS ARE SHOWN WITH A 10 INCH
 VALANCE. THE CITYPLACE MASTER SIGN PLAN REQUIRES THAT
 ALL AWNINGS ON STREET LEVEL MUST HAVE AN EIGHT (8) INCH
 VERTICAL VALANCE ALONG THE FRONT OF THE AWNING. THE
 VALANCE MUST BE PROVIDED WITH CONCEALED WEIGHT OR OTHER
 METHOD TO PREVENT EXCESSIVE MOVEMENT IN HIGH WINDS.
  
 A COPY OF THESE COMMENTS HAVE BEEN PROVIDED TO CARLOS
 BERNAL OF CITYPLACE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
  
  
2012-12-27 16:20:58GAVE TO E.S. - MD

Review Stop Z ZONING
Rev No 1 Status F Date 2012-12-20 Cont ID  
Sent By eschneid Date 2012-12-20 Time 08:48 Rev Time 0.50
Received By eschneid Date 2012-12-19 Time   Sent To B
Notes
2012-12-20 09:19:20FAILED
  
 1) NO PLANS WERE PROVIDED TO SHOW WHERE THE AWNINGS ARE
 TO GO.
  
 2) THE PROPOSED AWNING MATERIAL WAS NOT PROVIDED.
 PLEASE NOTE THAT THE CITYPLACE MASTER SIGN PLAN
 REQUIRES THAT AWNINGS SHALL BE A SUNBRELLA 100%
 SOLUTION DYED ACRYLIC OR SUNBRELLA FIRESIST 100%
 SOLUTION DYED MODACRYLIC MATERIAL (OR EQUIVALENT
 APPROVED BY CITYPLACE RETAIL IN WRITING). VINYL AWNINGS
 ARE PROHIBITED.
  
 3) THE PROPOSED AWNING COLOR WAS NOT PROVIDED. THE
 CITYPLACE MASTER SIGN PLAN REQUIRES THAT THE AWNING
 COLORS, COPY AND/OR LOGO SHALL BE APPROVED BY CITYPLACE
 RETAIL IN WRITING.
  
 4) NO DETAILS OF THE AWNING HEIGHT WERE PROVIDED. THE
 CITYPLACE MASTER SIGN PLAN REQUIRES THAT AWNINGS SHALL
 PROVIDE A MINIMUM OF EIGHT (8) FEET OF CLEARANCE
 BETWEEN THE FLOOR AND THE LOWEST POINT OF THE AWNING.
  
 5) THE PROPOSED AWNINGS ARE SHOWN WITH 5'-11" AND
 2'-11" PROJECTIONS. THE CITYPLACE MASTER SIGN PLAN
 REQUIRES THAT AWNINGS ON THE STREET LEVEL SHALL PROJECT
 FOUR (4) FEET FROM THE BUILDING FACADE, UNLESS
 OTHERWISE APPROVED BY CITYPLACE RETAIL IN WRITING.
  
 6) NO INFORMATION WAS PROVIDED ON THE AWNING COVERING.
 THE CITYPLACE MASTER SIGN PLAN REQUIRES THAT BOTH SIDES
 OF A SHED AWNING MUST BE OPEN, UNLESS OTHERWISE
 APPROVED BY CITYPLACE RETAIL IN WRITING.
  
 7) THE AWNINGS ARE SHOWN WITH A 10 INCH VALANCE. THE
 CITYPLACE MASTER SIGN PLAN REQUIRES THAT ALL AWNINGS ON
 STREET LEVEL MUST HAVE AN EIGHT (8) INCH VERTICAL
 VALANCE ALONG THE FRONT OF THE AWNING. THE VALANCE MUST
 BE PROVIDED WITH CONCEALED WEIGHT TO PREVENT EXCESSIVE
 MOVEMENT IN HIGH WINDS.
  
 8) THE CITYPLACE MANAGEMENT STAMP IS REQUIRED ON THE
 PLANS.
  
 A COPY OF THESE COMMENTS HAVE BEEN PROVIDED TO CARLOS
 BERNAL OF CITYPLACE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
  
2012-12-19 08:20:30GAVE TO E.S.