Plan Review Details - Permit 12120211
Plan Review Stops For Permit 12120211
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-05-14 Cont ID  
Sent By JWITMER Date 2013-05-14 Time 13:01 Rev Time 0.00
Received By jwitmer Date 2013-05-14 Time 12:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-04-13 Cont ID  
Sent By jwitmer Date 2013-04-13 Time 14:00 Rev Time 0.00
Received By jwitmer Date 2013-04-13 Time 13:02 Sent To  
Notes
2013-04-13 14:23:44BUILDING PLAN REVIEW
 PERMIT: 12120211
 ADD: 424 PALM ST
 CONT: BENITZ BUILDING LLC
 TEL: (561)659-4024
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
  
 1A) COMPLIED.
  
 1B)2ND REQUEST, IS THIS A CHANGE OF OCCUPANCY? THE
 PLANS APPEAR TO HAVE GONE FROM A WAREHOUSE AND AN
 ACCESSORY BUSINESS OCCUPANCY TO A MIXED USE MERCANTILE
 AND WAREHOUSE TYPE OCCUPANCY. THE DESIGNER REFERS TO
 INTERIOR DESIGN OFFICE BUT THE PLANS SHOW MORE THAN 50%
 OF THE FLOOR PLAN AS SHOW ROOMS AND A DISPLAY KITCHEN.
 THIS WOULD MAKE IT A MERCANTILE OCCUPANCY, ARE CLIENTS
 ALLOWED TO VIEW FURNATURE IN THE WAREHOUSE SUCH AS A
 COSTCO OR SAMS CLUB OR IS THIS AREA FOR EMPLOYEES ONLY.
 WHAT TYPE OF GOODS WILL BE STORED IN THE WAREHOUSE?
 WILL THIS AREA BE CONSIDERED A S1 OR S2 OCCUPANCY?
 DEPENDING ON THE TYPE OF STORAGE THERE MAY OR MAYNOT
 REQUIRE A FIRE RATING BETWEEN THE OCCUPANCIES PER 2010
 FBC-B TABLE 508.4.
  
 2010 EXISTING BUILDING CODE 901.3 CHANGE OF OCCUPANCY
 CLASSIFICATION.
 WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912
 SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY
 CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF
 OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT
 GROUP.
  
 2) SHEET A2.1 THE ACCESSIBLE RESTROOMS:
 2A-D) COMPLIED .
  
 2E) COMPLIED.
  
 3) SEE COMMENT 1B, SHEET A1.1 INDICATES THIS BUILDING
 AS A MIXED OCCUPANCY INTERIOR DESIGN OFFICE (BUSINESS)
 & STORAGE OCCUPANCIES THE PLANS JUST STATE WAREHOUSE
 NOT THE S1 OR S2 OCCUPANCY TYPE.
 DEPENDING ON THE TYPE OF MATERIALS STORAGED TABLE 508.4
 MAY REQUIRE OCCUPANCY SEPERATION AND OPENING
 PROTECTIVES TABLE 715.4.
  
 4) 2ND REQUEST, THIS DEPENDS ON THE ABOVE
 COMMENTRESPONCES.IN RATED FIRE RATED WALLS : 713.6 FIRE
 WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS
 AND SMOKE PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE
 PROTECTED OPENINGS SHALL BE EFFECTIVELY AND PERMANENTLY
 IDENTIFIED WITH SIGNS OR STENCILING IN A MANNER
 ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION. SUCH
 IDENTIFICATION SHALL BE ABOVE ANY DECORATIVE CEILING
 AND IN CONCEALED SPACES. SUGGESTED WORDING FOR FIRE AND
 SMOKE BARRIERS: ?FIRE AND SMOKE BARRIER ? PROTECT ALL
 OPENINGS.?
  
 5) COMPLIED.
  
 6) 2ND REQUEST. SHEET A5.1 INDICATES THE USE OF
 POLYICYNENE INSULATION UNDER THE ROOF SLAB SYSTEM AND
 NO IGNITION BARRIER. 2010 FBC-B 2603.4.1.6 REQUIRES A
 IGNITION BARRIER TO SEPERATE THE INSULATION FROM THE
 AREA ABOVE THE CEILING. A IGNITION BARRIER IS DIFFERENT
 FROM A THERMOBARRIER THAT IS REQUIRED UNDER 2603.4.
 PLEASE PROVIDE THE MANUFACTURERS TESTING, THEY DO HAVE
 A ES LEGACY REPORT NER-420.
  
 7) 2ND REQUEST SHEET A5.1 DETAIL #4 IS MISSING THE BOND
 BREAK (SLIP SHEET) AS PER REQUIREMENT 2010 FBC-B
 1402.2.1.
 RESPONCE INDICATES COMPLIANCE WITH ASTM D 226, THIS
 STANDARD DOES NOT DEAL WITH THE TWO LAYERS OF WHATEVER
 MATERIAL THAT IS BEING SPECED OUT, ONE THE STUCCO GRABS
 THE FIRST LAYER OF FELT IN THIS CASE IT WILL NOT MOVE,
 THE REQUIRED SECOND LAYER IS THE BOND BREAK THAT ALLOWS
 FOR MOVEMENT OF THE UNDER LAYER THE BOND BREAK, NEW TO
 THE 2007 FBC.
  
 8) COMPLIED.
  
 9)2ND REQUEST, PLEASE STAMP THE PRODUCT APPROVALS WITH
 A SHOP DRAWING TYPE STAMP THAT THE DESIGN PROFESSIONAL
 HAS REVIEWED THE APPROVAL AND FOUND THEM MEETING THE
 WIND AND ASSOCIATED PRESSURES.
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 10) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. NEEDS TO BE REVIEWED BY
 THEDESIGNER OF RECORD.
 (B) WINDOWS, NEEDS TO BE REVIEWED BY THE DESIGNER OF
 RECORD.
 (D) ROOFING PRODUCTS AND ASSEMBLIES, NO PRODUCT
 APPROVAL WAS SUBMITTED.
 (F) SKYLIGHT, NO PRODUCT APPROVAL WAS SUBMITTED
  
 11) SHEET A7.2 IN THE SAMPLE AND CONFERENCE ROOM IT
 APPEARS A NEW SKYLIGHT IS TO BE INSTALLED ALSO IN THE
 ENERGY CALCS BUT NO INFORMATION AS TO PRODUCT APPROVALS
 OR ROOF PRESSURES FOR THIS SKYLIGHT WERE PROVIDED OR
 ROOF FRAMING DETAILS.
  
 12) 2ND REQUEST , THE MECHANICAL SHEET M2.1 DETAIL # 1
 INDICATES THAT THE ROOF A/C STANDS ARE EXISTING, SHEET
 A1.1 INDICATES NEW A/C ROOF TOP EQUIPMENT NEXT TO THE
 NEW SKYLIGHT. IF THE COMPRESSORS ARE GOINGTO BE
 INSTALLED ON THE ROOF TOP AND PRE-ENGINEERED A/C STANDS
 ARE GOING TO BE INSTALLED RULE 9N-3 REQUIRES PRODUCT
 APPROVALS TO BE SUBMITTED. IF ROOF TOP PACKAGE UNITS
 ARE TO BE INSTALLED THEN STRUCTURAL PLANS WILL NEED
 DETAILS ON THE OPENING SIZES, REINFORCEMENT AND HOW THE
 ROOF TOP CURBS WILL BE FASTENED TO THE ROOF FRAMING. WE
 WILL ALSO NEED HOW THE ROOF TOP EQUIPMENT WILL BE
 FASTENED TO THE CURB. 1609.8.
  
 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-12-19 Cont ID  
Sent By jwitmer Date 2012-12-19 Time 13:16 Rev Time 0.00
Received By jwitmer Date 2012-12-19 Time 11:16 Sent To  
Notes
2012-12-19 13:23:04BUILDING PLAN REVIEW
 PERMIT: 12120211
 ADD: 424 PALM ST
 CONT: BENITZ BUILDING LLC
 TEL: (561)659-4024
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) THE COVER SHEET A1.1UNDER THE HEADING OF TYPE OF
 BUILDING LIST THIS BUILDING AS A TYPE VA, THE PLANS DO
 NOT PROVIDE ANY COMPLIANCE WITH THE 2010 FBC-B TABLE
 601 FOR 1 HOUR RATING, TABLE 602 NOR TABLE 705.8. THIS
 BUILDING CAN BE A BUILDING TYPE VB WITH THE AREA
 FRONTAGE INCREASE TAKEN SEE 2010 FBC-B 506.2.
  
 1B) IS THIS A CHANGE OF OCCUPANCY? 2010 EXISTING
 BUILDING CODE 901.3 CHANGE OF OCCUPANCY CLASSIFICATION.
 WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912
 SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY
 CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF
 OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT
 GROUP.
  
 2) SHEET A2.1 THE ACCESSIBLE RESTROOMS:
 2A) 118 & 119 PLEASE REVIEW THE REQUIRED SIZE OF
 RESTROOMS UNDER THE 2010 FL ACCESSIBILITY CODE FIGURE
 604.8.1.6 AND CODE SECTION 604.3.2 .
 2B) RESTROOM WITH DOOR # 133 THE DOOR SWINGS IN OVER
 THE 60 INCH CLEAR FLOOR SPACE REQUIRED BY ACC CODE
 604.3.2.
 2C) RESTROOM WWITH DOOR # 133 PLEASE PROVIDE DETAILS
 FOR THE LOCATION OF WATER CLOSET INCOMPLIANCE WITH ACC
 CODE 604.2 WATER CLOSET LOCATION & GRAB BARS IN
 COMPLIANCE WITH 604.5.
 2D) RESTROOM WITH DOOR # 133 PLEASE PROVIDE DETAILS FOR
 THE LAVATORY THAT SHOW COMPLIANCE WITH 606.1-5.
 2E) SHEET A2.1 & A5.2 THE OFFICE RESTROOM IS ACTUALLY
 CONSIDERED A BATHROOM SINCE IT CONTAINS A SHOWER AND
 WOULD BE REQUIRED TO BE ACCESSIBLE. EVEN IF THIS WAS TO
 BE VIEWED AS 213.2 EXCEPTION # 4 THE 50 % RULE WAS NOT
 MET. 213.2 TOILET ROOMS AND BATHING ROOMS. WHERE TOILET
 ROOMS ARE PROVIDED, EACH TOILET ROOM SHALL COMPLY WITH
 603. WHERE BATHING ROOMS ARE PROVIDED, EACH BATHING
 ROOM SHALL COMPLY WITH 603.
  
 3) SHEET A1.1 INDICATES THIS BUILDING AS A MIXED
 OCCUPANCY MERCANTILE & STORAGE OCCUPANCIES THE PLANS
 JUST STATE WAREHOUSE NOT THE S1 OR S2 OCCUPANCY TYPE.
 DEPENDING ON THE TYPE OF MATERIALS STORAGED TABLE 508.4
 MAY REQUIRE OCCUPANCY SEPERATION AND OPENING
 PROTECTIVES TABLE 715.4.
  
 4) IN RATED FIRE RATED WALLS : 713.6 FIRE WALLS, FIRE
 BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS AND SMOKE
 PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND PERMANENTLY
 IDENTIFIED WITH SIGNS OR STENCILING IN A MANNER
 ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION. SUCH
 IDENTIFICATION SHALL BE ABOVE ANY DECORATIVE CEILING
 AND IN CONCEALED SPACES. SUGGESTED WORDING FOR FIRE AND
 SMOKE BARRIERS: ?FIRE AND SMOKE BARRIER ? PROTECT ALL
 OPENINGS.?
  
 5) PLEASE PROVIDE ADDITIONAL INFORMATION ON THE WARMING
 KITCHEN, STUDIO 1 & STUDIO 2, WHAT ARE THESE AREAS
 GOING TO BE USED FOR? WILL THE KITCHEN BE USED FOR
 COOKING?
 107.2.1 ADDITIONAL INFORMATION REQUIRED. 2010
 ACCESSIBILITY CODE 606.1-5.
  
 6) SHEET A5.1 INDICATES THE USE OF POLYICYNENE
 INSULATION UNDER THE ROOF SLAB SYSTEM AND NO IGNITION
 BARRIER. 2010 FBC-B 2603.4.1.6 REQUIRES A IGNITION
 BARRIER TO SEPERATE THE INSULATION FROM THE AREA ABOVE
 THE CEILING.
  
 7) SHEET A5.1 DETAIL #4 IS MISSING THE BOND BREAK (SLIP
 SHEET) AS PER REQUIREMENT 2010 FBC-B 1402.2.1.
  
 8) SHEET A5.1 & A2.1 BOTH INDICATE NEW PORTICOS, BUT
 THE PLANS FAIL TO PROVIDE ROOF DRAINAGE 2010 FBC-B
 1503.4.
  
 9) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 10) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. NEEDS TO BE REVIEWED BY
 THEDESIGNER OF RECORD.
 (B) WINDOWS, NEEDS TO BE REVIEWED BY THE DESIGNER OF
 RECORD.
 (D) ROOFING PRODUCTS AND ASSEMBLIES, NO PRODUCT
 APPROVAL WAS SUBMITTED.
 (F) SKYLIGHT, NO PRODUCT APPROVAL WAS SUBMITTED
  
 11) SHEET A7.2 IN THE SAMPLE AND CONFERENCE ROOM IT
 APPEARS A NEW SKYLIGHT IS TO BE INSTALLED ALSO IN THE
 ENERGY CALCS BUT NO INFORMATION AS TO PRODUCT APPROVALS
 OR ROOF PRESSURES FOR THIS SKYLIGHT WERE PROVIDED OR
 ROOF FRAMING DETAILS.
  
 12) NOTE NO MECHANICAL PLANS WERE PART OF THIS
 SUBMITTAL IF THE COMPRESSORS ARE GOINGTO BE INSTALLED
 ON THE ROOF TOP AND PRE-ENGINEERED A/C STANDS ARE GOING
 TO BE INSTALLED RULE 9N-3 REQUIRES PRODUCT APPROVALS TO
 BE SUBMITTED. IF ROOF TOP PACKAGE UNITS ARE TO BE
 INSTALLED THEN STRUCTURAL PLANS WILL NEED DETAILS ON
 THE OPENING SIZES, REINFORCEMENT AND HOW THE ROOF TOP
 CURBS WILL BE FASTENED TO THE ROOF FRAMING. WE WILL
 ALSO NEED HOW THE ROOF TOP EQUIPMENT WILL BE FASTENED
 TO THE CURB. 1609.8.
  
 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-04-01 Cont ID  
Sent By rlecky Date 2013-04-01 Time 13:48 Rev Time 0.00
Received By rlecky Date 2013-04-01 Time 13:37 Sent To  
Notes
2013-03-29 14:29:41NEW SHEETS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-12-28 Cont ID  
Sent By rlecky Date 2012-12-28 Time 14:59 Rev Time 0.00
Received By rlecky Date 2012-12-28 Time 14:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2013-05-18 Cont ID  
Sent By WJOLIN Date 2013-05-18 Time 19:27 Rev Time 0.00
Received By wjolin Date 2013-05-18 Time 19:05 Sent To  
Notes
2013-05-18 19:21:18424 PALM STREET
 PERMIT #12120211
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISION*****
  
 THE FIRE-RATED HAZARD SEPARATION APPLIES TO THE WALL
 AND DOORS BETWEEN WAREHOUSE #118 (STORAGE) AND
 SHOWROOMS #113, #114 & #117 (MERCANTILE/BUSINESS). THE
 OTHER WALLS AND DOORS DO NOT NEED TO BE FIRE RATED!
  
 ANY AREA (STORAGE) HAVING A DEGREE OF HAZARD GREATER
 THAN NORMAL TO THE GENERAL OCCUPANCY
 (MERCANTILE/BUSINESS) OF THE BUILDING, SHALL BE
 SEPARATED FROM NON-STORAGE AREAS WITH A 1-HOUR
 FIRE-RATED BARRIER. DOORS SHALL BE SELF CLOSING,
 POSITIVE LATCHING, AND FIRE-RATED FOR AT LEAST
 45-MINUTES PER SECTION 8.7 OF NFPA 101.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-04-03 Cont ID  
Sent By wjolin Date 2013-04-03 Time 11:09 Rev Time 0.00
Received By wjolin Date 2013-04-03 Time 10:55 Sent To  
Notes
2013-04-03 11:09:28424 PALM STREET
 PERMIT #12120211
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT - PROVIDE DRAWING NOTE: DESIGN SHALL
 CONFORM TO THE 2010 EDITION OF THE FLORIDA FIRE
 PREVENTION CODE WHICH CONTAINS THE 2009 EDITION OF BOTH
 NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS.
  
 REPEAT COMMENT - PROVIDE DRAWING NOTE: ALL CONSTRUCTION
 AND DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 RESPONSE COMMENT: THE LIFE SAFETY CODE REQUIRES A
 1-HOUR HAZARD SEPARATION WHICH IS DIFFERENT THAN AN
 OCCUPANCY SEPARATION (WHICH WOULD BE A 2-HOUR FIRE
 BARRIER).
 ORIGINAL COMMENT: ANY AREA (STORAGE) HAVING A DEGREE OF
 HAZARD GREATER THAN NORMAL TO THE GENERAL OCCUPANCY
 (MERCANTILE/BUSINESS) OF THE BUILDING, SHALL BE
 SEPARATED FROM NON-STORAGE AREAS WITH A 1-HOUR
 FIRE-RATED BARRIER. DOORS SHALL BE SELF CLOSING,
 POSITIVE LATCHING, AND FIRE-RATED FOR AT LEAST
 45-MINUTES PER SECTION 8.7 OF NFPA 101.
  
 SHEET A1.1: THE RESUBMITTED PLANS HAVE INCORRECTLY
 CHANGED THE FURNITURE SHOWROOM FROM MERCANTILE
 OCCUPANCY TO STORAGE OCCUPANCY.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-12-17 Cont ID  
Sent By wjolin Date 2012-12-17 Time 12:41 Rev Time 0.00
Received By wjolin Date 2012-12-17 Time 11:54 Sent To  
Notes
2012-12-17 12:40:59424 PALM STREET
 PERMIT #12120211
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE FLORIDA
 FIRE PREVENTION CODE WHICH CONTAINS THE 2009 EDITION OF
 BOTH NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR
 AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL
 HAVE "NO SMOKING" SIGNS POSTED. WHERE SMOKING IS
 PERMITTED, SAFE RECEPTACLES FOR SMOKING MATERIALS SHALL
 BE PROVIDED.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 ANY AREA (STORAGE) HAVING A DEGREE OF HAZARD GREATER
 THAN NORMAL TO THE GENERAL OCCUPANCY (MERCANTILE) OF
 THE BUILDING, SHALL BE SEPARATED FROM NON-STORAGE AREAS
 WITH A 1-HOUR FIRE-RATED BARRIER. DOORS SHALL BE SELF
 CLOSING, POSITIVE LATCHING, AND FIRE-RATED FOR AT LEAST
 45-MINUTES PER SECTION 8.7 OF NFPA 101.
  
 INDICATE THE INTENDED USAGE OF THE OVEN LOCATED IN THE
 WARMING KITCHEN.
  
 THE EGRESS PLAN SHOWN ON DRAWING A2.1 DOES NOT COINCIDE
 WITH THE EXIT SIGNAGE PROVIDED ON E2.1.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-05-20 Cont ID  
Sent By jwitmer Date 2013-05-20 Time 16:12 Rev Time 0.00
Received By jwitmer Date 2013-05-09 Time 09:50 Sent To  
Notes
2013-05-10 09:50:23C01

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-04-18 Cont ID  
Sent By lmartine Date 2013-04-18 Time 15:59 Rev Time 0.00
Received By lmartine Date 2013-03-28 Time 14:15 Sent To  
Notes
2013-04-10 15:41:374/10 EXPEDITED REQUEST
  
  
2013-03-29 14:15:56SENT TO C9 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-01-03 Cont ID  
Sent By jwitmer Date 2013-01-03 Time 09:17 Rev Time 0.00
Received By jwitmer Date 2012-12-07 Time 09:18 Sent To  
Notes
2012-12-17 09:18:31SENT TO C9 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2013-05-14 Cont ID  
Sent By jwitmer Date 2013-05-14 Time 12:06 Rev Time 0.00
Received By jwitmer Date 2013-05-14 Time 12:06 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2013-04-13 Cont ID  
Sent By jwitmer Date 2013-04-13 Time 14:24 Rev Time 0.00
Received By jwitmer Date 2013-04-13 Time 14:23 Sent To  
Notes
2013-04-13 14:24:34BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-01-03 Cont ID  
Sent By jwitmer Date 2013-01-03 Time 09:17 Rev Time 0.00
Received By jwitmer Date 2013-01-03 Time 09:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2013-05-15 Cont ID  
Sent By HMOSER Date 2013-05-15 Time 09:23 Rev Time 0.00
Received By hmoser Date 2013-05-15 Time 08:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2013-04-08 Cont ID  
Sent By hmoser Date 2013-04-08 Time 15:38 Rev Time 0.00
Received By hmoser Date 2013-04-08 Time 14:38 Sent To  
Notes
2013-04-08 15:38:07PLANS DENIED
 PROVIDE AN UP DATED PRODUCT APPROVAL FOR THE
 CONDENSER STANDS. PER SECTION 107 FBC 2010 .
 PRODUCT INFORMATION FOR NOA # 09-0804.05
 SHOWS FILE CLOSED.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-12-20 Cont ID  
Sent By tgordon Date 2012-12-20 Time 11:02 Rev Time 0.00
Received By tgordon Date 2012-12-20 Time 07:53 Sent To  
Notes
2012-12-20 10:19:00*** CORRECTIONS NEED FOR MECHANICAL REVIEW ***
  
 1) SUBMIT AN UP TO DATE PRODUCT APPROVAL FOR THE A/C
 CONDENSER STANDS. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 1, 2010, (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS: (G) EXTERIOR COOLER, FREEZERS &
 "PER-ENGINEERED A/C STANDS". ALSO SEE 2010 FBC
 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 2) PLAN M1.1, SHOW THE SIZE OF THE RETURN AIR FLEX DUCT
 GOING FROM THE OWNERS OFFICE & CONFERENCE ROOM TO AHU
 #5, SEE 2010 FBC/M 601.4.
  
 MECHANICAL PLAN REVIEW BY:
 TOM GORDON (HY-BYRD INC.) (561) 805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-04-09 Cont ID  
Sent By lwagner Date 2013-04-09 Time 14:18 Rev Time 0.00
Received By lwagner Date 2013-04-09 Time 13:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-12-26 Cont ID  
Sent By lwagner Date 2012-12-26 Time 14:31 Rev Time 0.00
Received By lwagner Date 2012-12-17 Time 15:04 Sent To  
Notes
2012-12-17 15:26:09FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 PLUMBING DRAWINGS ARE OK
  
 1. THE SHOWROOM RESTROOMS WILL BE REQUIRED TO BE A
 MINIMUM OF 7'-1" WIDE TO ACHIEVE THE REQUIRED 60" CLEAR
 SPACE FOR THE WATER CLOSET. (OTHER CONFIGURATIONS ARE
 ALSO POSSIBLE). ALSO, PLEASE SEE BUILDING REVIEW NOTES
 CONCERNING THE WAREHOUSE AND OFFICE RESTROOMS.
 FBC ACCESSIBILITY CODE 2010 604.3.1 A 60" CLEAR SPACE
 IS REQUIRED FOR WATER CLOSET FROM SIDE WALL.
 FBC ACCESSIBILITY CODE 2010 604.3.2 THE LAVATORY WILL
 NOT BE PERMITTED IN THE 60" SPACE.
  
 2. BUSINESS/ MERCANTILE OCCUPANCIES WITH OVER 15
 OCCUPANTS REQUIRE A HIGH/LO DRINKING FOUNTAIN OR EQUAL
 (ALSO SEE EXCEPTION).
 PLUMBING TABLE 403.1 (E) (F)
 FBC ACCESSIBILITY CODE 2010 211.2 MINIMUM NUMBER. NO
 FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2013-05-20 Cont ID  
Sent By ESCHNEID Date 2013-05-20 Time 12:10 Rev Time 0.75
Received By eschneid Date 2013-05-20 Time 12:10 Sent To  
Notes
2013-05-20 14:01:32PASSED
  
 1) SCOPE OF WORK REDUCED - NO LONGER 50% OF THE
 STRUCTURE VALUE FOR THIS PERMIT. ADDITIONAL PERMIT WORK
 WITHIN NEXT YEAR WHICH WOULD EXCEED 50% WILL REQUIRE
 LANDSCAPE COMPLIANCE.
  
 2) SEPARATE PERMITS, INCLUDING PLANS, ARE REQUIRED FOR
 THE FOLLOWING:
  
 A. WORK THAT IS SHOWN ON THE SITE PLAN IN THE PARKING
 AREA. THIS PERMIT MAY INCLUDE THE PARKING LOT STRIPING.
 B. SITE LIGHTING
 C. ANY NEW/REPLACEMENT FENCE AND GATES
 D. THE DUMPSTER ENCLOSURE, INCLUDING THE REQUIRED
 LANDSCAPE SCREENING AROUND THE DUMPSTER ENCLOSURE
 E. AWNINGS
 F. SIGNAGE.
 G. LANDSCAPE
  
 3) PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF
 COMPLETION, THE DUMPSTER ENCLOSURE AND THE LANDSCAPE
 SCREENING FOR THE DUMPSTER ENCLOSURE SHALL BE
 INSTALLED.
  
 4) INCLUDED WITH THE DUMPSTER ENCLOSURE PERMIT SHALL BE
 VERIFICATION FROM THE CITY'S SANITATION DIVISION THAT
 THE PROPOSED DUMPSTER'S ORIENTATION ALLOWS THE TRUCKS
 TO EMPTY THE DUMPSTER. NOT PROVIDED AS STATED IN THE
 REVEIW COMMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 1.00
Received By eschneid Date 2013-04-18 Time 09:30 Sent To  
Notes
2013-04-18 11:13:26FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES.
  
 1) REPEAT COMMENT: THE VALUE OF THE CONSTRUCTION
 ($250,000) EXCEEDS 50% OF THE STRUCTURE'S VALUE
 ($370,000) ACCORDING TO THE P.B.C. PROPERTY APPRAISER'S
 OFFICE; THEREFORE, PURSUANT TO SECTION 94-441(C)(2) OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR), THE
 LANDSCAPE ON THE SITE SHALL BE IN COMPLIANCE WITH ALL
 APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF THE
 ZLDR. IF THE SITE CONFORMS TO ARTICLE XIV, THEN TWO (2)
 COPIES OF A LANDSCAPE PLAN DEMONSTRATING COMPLIANCE
 SHALL BE INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE
 SITE DOES NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE
 ZONING APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE
 PERMIT AND IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING
 MATERIAL TO BRING THE SITE INTO CONFORMITY.
  
 2) A SEPARATE PERMIT IS REQUIRED FOR THE WORK THAT IS
 SHOWN ON THE SITE PLAN IN THE PARKING AREA. THIS PERMIT
 MAY INCLUDE THE PARKING LOT STRIPING.
  
 3) WHILE A FULL REVIEW OF THE PARKING LOT WILL BE
 PERFORMED AS PART OF THE PARKING LOT AND LANDSCAPE
 PERMITS, STAFF HAS IDENTIFIED THE FOLLOWING ITEMS WHICH
 NEED TO BE ADDRESSED:
  
 A) REPEAT COMMENT: THE RECONFIGURED PARKING LOT DOES
 NOT COMPLY WITH THE TERMINAL LANDSCAPE ISLAND
 REQUIREMENTS FOR THE PARKING SPACES ADJACENT TO THE
 BUILDING.
 B) REPEAT COMMENT: THE PARKING SPACES NEED EITHER WHEEL
 STOPS OR CURBING WITH A TWO (2) FOOT OVERHANG FOR THE
 END OF THE SPACE. NEITHER OF THESE ARE SHOWN.
 C) REPEAT COMMENT: A LANDSCAPE BUFFER IS REQUIRED TO
 THE REAR (SOUTH) OF THE SITE.
 D) THE WESTERN PARKING ROW MAY NOT HAVE MORE THAN 10
 SPACES WITHOUT AN INTERIOR LANDSCAPE ISLAND. THE
 PREVIOUS VERSION OF THE PLANS INCLUDED INTERIOR
 ISLANDS.
 E) THE PREVIOUS PLANS CORRECTLY CALLED OUT THE SHOWROOM
 PARKING AT 1 SPACE PER 500 SQUARE FEET. THE RESUBMITTED
 PLANS INCORRECTLY SHIFTED THE SHOWROOM SQUARE FOOTAGE
 TO WAREHOUSE SQUARE FOOTAGE.
 F) THE DUMPSTER DOES NOT APPEAR TO MEET THE SCREENING
 REQUIREMENTS.
  
 4) A SEPARATE PERMIT IS REQUIRED FOR THE SITE LIGHTING
 ANY NEW/REPLACEMENT FENCE AND GATES, THE DUMPSTER
 ENCLOSURE, AWNINGS AND SIGNAGE.
  
 5) PLEASE PROVIDE VERIFICATION FROM THE CITY'S
 SANITATION DIVISION THAT THE PROPOSED DUMPSTER'S
 ORIENTATION ALLOWS THE TRUCKS TO EMPTY THE DUMPSTER.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2013-01-02 Cont ID  
Sent By escheide Date 2013-01-02 Time 09:28 Rev Time 2.00
Received By eschneid Date 2013-01-02 Time 09:28 Sent To  
Notes
2013-01-02 13:34:25FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES.
  
 1) THE VALUE OF THE CONSTRUCTION ($250,000) EXCEEDS 50%
 OF THE STRUCTURE'S VALUE ($370,000) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY.
  
 2) THE SITE CURRENTLY EXCEEDS THE IMPERVIOUS AREA;
 THEREFORE, NO INCREASE IN IMPERVIOUS AREA IS PERMITTED
 AS SHOWN ON THE AREA CALCULATIONS CHART.
  
 3) THE SITE IS CURRENTLY DEFICIENT IN LANDSCAPE AREA.
 PLEASE EXPLAIN HOW THE ADDITION OF IMPERVIOUS AREA WILL
 RESULT IN AN INCREASE IN LANDSCAPE AREA. THESE 2 ARE
 OPPOSING CONDITIONS.
  
 4) A SEPARATE PERMIT IS REQUIRED FOR THE WORK THAT IS
 SHOWN ON THE SITE PLAN IN THE PARKING AREA. THIS PERMIT
 MAY INCLUDE THE PARKING LOT STRIPING.
  
 5) WHILE A FULL REVIEW OF THE PARKING LOT WILL BE
 PERFORMED AS PART OF THE PARKING LOT AND LANDSCAPE
 PERMITS, STAFF HAS IDENTIFIED THE FOLLOWING ITEMS WHICH
 NEED TO BE ADDRESSED:
  
 A) THE RECONFIGURED PARKING LOT DOES NOT COMPLY WITH
 THE TERMINAL LANDSCAPE ISLAND REQUIREMENTS FOR THE
 PARKING SPACES ADJACENT TO THE BUILDING.
 B) PARKING SPACES 2, 3 AND 20 DO NOT FUNCTION WITH THE
 GATE ARM SWING BLOCKING THEM. FOR THESE SPACES TO BE
 COUNTED, THE GATES NEED TO BE SIDE ROLLING GATES NOT
 SWING GATES.
 C) IF WHEEL STOPS ARE USED, CURBING DOES NOT NEED TO BE
 INSTALLED AT THE HEAD OF THE SPACE. ALTERNATIVELY,
 CURBING MAY BE USED IN PLACE OF THE WHEEL STOPS, WITH A
 TWO (2) FOOT OVERHANG FOR THE END OF THE SPACE WHICH
 COULD BE USED TO INCREASE THE PERVIOUS/LANDSCAPE AREA
 ON SITE.
 D) A LANDSCAPE BUFFER IS REQUIRED TO THE READ OF THE
 SITE.
 E) WHERE IS THE DUMPSTER ENCLOSURE?
 F) THE LANDSCAPE BUFFER ADJACENT TO SPACE NUMBER 20
 SHALL BE FIVE (5) FEET WIDE, EXCLUSIVE OF CURBING.
 G) NO DIMENSIONS WERE SHOWN ON THE PLANS FOR THE
 PARKING AND LANDSCAPE AREAS.
 H) PLEASE NOTE THAT THE WPB ZONING AND LAND DEVELOPMNET
 REGULATIONS REQUIRE OFFICE SPACE PARKING AT 1 PER 350
 AND WAREHOUSING AT 1 PER 1,000. NOTE: THE NUMBER OF
 REQUIRED SPACES SHOULD BE THE SAME AFTER RECALCULATING.
  
 6) PLEASE EXPLAIN WHY THE SURVEY SHOWS THE AUXILIARY
 STRUCTURE AS UNATTACHED, YET THE EXISTING SITE PLAN
 SHOWS IT AS ATTACHED.
  
 7) A SEPARATE PERMIT IS REQUIRED FOR THE SITE LIGHTING.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2012-12-18 17:11:1912/18/12