Plan Review Details - Permit 12120148
Plan Review Stops For Permit 12120148
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-01-23 Cont ID  
Sent By rlecky Date 2013-01-23 Time 13:12 Rev Time 0.00
Received By rlecky Date 2013-01-23 Time 11:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-12-18 Cont ID  
Sent By rlecky Date 2012-12-18 Time 16:22 Rev Time 0.00
Received By rlecky Date 2012-12-17 Time 16:56 Sent To  
Notes
2012-12-18 16:28:1012120148
 8130 N. JOG ROAD
 NEW GENERATOR TRANSFER SWITCH
  
 PLEASE REVISE/CLARIFY THE PLANS IN RESPONSE TO THE
 FOLLOWING REVIEW COMMENTS.
  
 EITHER A SERVICE RATED TRANSFER SWITCH WITH OVER
 CURRENT PROTECTION OR A SERVICE RATED MANUAL DISCONNECT
 WITH OVERCURRENT PROTECTION IS REQUIRED. NEC 230.66,
 225.36
  
 THE MAXIMUM OVER CURRENT PROTECTION ALLOWED FOR 3/0
 FEEDERS IS 200 AMPERES. NEC
 T 310.16
  
 PROVIDE A GROUNDING AND BONDING SYSTEM FOR THE DERIVED
 SYSTEM. VERIFY THE EXISTING SERVICE IS PROPERLY BONDED
 AND GROUNDED AT THE BUILDING. NEC 250.20
  
 PLEASE CALL IF THERE ARE ANY QUESTIONS.
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-01-23 Cont ID  
Sent By rlecky Date 2013-01-23 Time 13:12 Rev Time 0.00
Received By rlecky Date 2013-01-22 Time 08:38 Sent To  
Notes
2013-01-23 08:39:06SENT TO R LECKY.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-12-18 Cont ID  
Sent By rlecky Date 2012-12-18 Time 16:28 Rev Time 0.00
Received By rlecky Date 2012-12-06 Time 11:11 Sent To  
Notes
2012-12-07 11:12:29IN ELECTRIC BOX