Plan Review Details - Permit 12120131
Plan Review Stops For Permit 12120131
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-12-14 Cont ID  
Sent By rmcdouga Date 2013-02-07 Time 11:45 Rev Time 0.00
Received By rmcdouga Date 2013-02-07 Time 11:45 Sent To  
Notes
2013-02-07 11:52:47REVISION REQUIRED
  
 THE FOLLOWING ITEMS HAVE BEEN DEEMED DEFICIENT OR WERE
 NOTED TO BE MISSING UPON REVIEW.
  
 1) THE WINDOW AND DOOR PRESSURES ON SHEET A1.1 WERE NOT
 CHANGED TO REFLECT THE CHANGE IN EXPOSURE CATEGORY FROM
 B TO C FROM THE PREVIOUS REVIEW. SUBMIT REVISED SHEET.
  
 2) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE
 STRUCTURAL MULLIONS OR PROVIDE SIGNED AND SEALED
 STRUCTURAL DETAILS FOR THEM. DCA RULE 9N-3 AND CITY
 AMENDMENTS 107.2.1.3
  
 3) THE MAXIMUM DESIGN PRESSURE FROM THE PRODUCT
 APPROVAL FOR THE 5 V CRIMP METAL ROOF OF -52.5 PSF IS
 TOO LOW FOR ROOF ZONES 2 AND 3. MEAN ROOF HEIGHT IS 20
 FT, SLOPE IS 6/12 AND EXPOSURE IS C. PLEASE SUBMIT
 PRODUCT APPROVAL WITH HIGHER DESIGN PRESSURES. FBCR
 301.1.1
  
 4) THE WINDOW SCHEDULE ON SHEET A1.1 OF THE PLANS
 SPECIFIES DOUBLE HUNG WINDOWS AND THE PRODUCT APPROVALS
 THAT WERE SUBMITTED ARE FOR SINGLE HUNG WINDOWS. SUBMIT
 REVISED SHEET.
  
 5 SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE SOLID
 CORE FIBERGLASS EXTERIOR DOORS ( #S 2, 7 IN THE DOOR
 SCHEDULE) AS REQUIRED BY DCA RULE 9N-3.
  
 6) THE PRODUCT APPROVAL FOR THE FIXED GLASS WINDOWS HAS
 A MAXIMUM SIZE LIMIT OF 20.67 SQFT. THE 146" X 24"
 TRANSOM WINDOW (F) AT THE MASTER BEDROOM APPEARS TO
 EXCEED THE SIZE LIMITATIONS OF THE PRODUCT APPROVAL.
 PLEASE CORRECT.
  
 7) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE 90
 DEGREE CORNER CUSTOM EXTERIOR FOLDING DOORS. DCA RULE
 9N-3
  
 8) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 STORM PANELS ARE MISSING THE INSTALLATION INSTRUCTIONS
 REQUIRED BY DCA RULE 9N-3. A KEY PLAN AND AN
 INSTALLATION SCHEDULE IS ALSO REQUIRED. SEE SAMPLE
 INSTALLATION SCHEDULE AT HTTP://WPB.ORG/DEVELOPMENT/CON
 STRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PDF NOTE: ALL
 OF THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE LARGE
 MISSILE IMPACT RATED AND DO NOT REQUIRE SHUTTERS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-02-06 Cont ID  
Sent By rmcdouga Date 2013-02-06 Time 16:26 Rev Time 0.00
Received By rmcdouga Date 2013-02-05 Time 15:38 Sent To  
Notes
2013-02-06 10:45:352010 FBC
  
 DENIED BY BUILDING
  
 1) THE WINDOW AND DOOR PRESSURES ON SHEET A1.1 WERE NOT
 CHANGED TO REFLECT THE CHANGE IN EXPOSURE CATEGORY FROM
 B TO C FROM THE PREVIOUS REVIEW. PLEASE CORRECT. FBCR
 301.2.1
  
 2) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE
 ENERGY CALCULATION FORMS. FBC ENERGY CONSERVATION
 405.4.2
  
 3) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE
 STRUCTURAL MULLIONS OR PROVIDE SIGNED AND SEALED
 STRUCTURAL DETAILS FOR THEM. DCA RULE 9N-3 AND CITY
 AMENDMENTS 107.2.1.3
  
 4) THE MAXIMUM DESIGN PRESSURE FORM THE PRODUCT
 APPROVAL FOR THE 5 V CRIMP METAL ROOF OF -52.5 PSF IS
 TOO LOW FOR ROOF ZONES 2 AND 3. MEAN ROOF HEIGHT IS 20
 FT, SLOPE IS 6/12 AND EXPOSURE IS C. PLEASE SUBMIT
 PRODUCT APPROVAL WITH HIGHER DESIGN PRESSURES. FBCR
 301.1.1
  
 5) THE WINDOW SCHEDULE ON THE PLANS SPECIFIES DOUBLE
 HUNG WINDOWS AND THE PRODUCT APPROVALS THAT WERE
 SUBMITTED ARE FOR SINGLE HUNG WINDOWS. PLEASE CLARIFY
 AND CORRECT. DCA RULE 9N-3
  
 6) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE SOLID
 CORE FIBERGLASS EXTERIOR DOORS ( #S 2, 7 IN THE DOOR
 SCHEDULE) AS REQUIRED BY DCA RULE 9N-3.
  
 7) THE PRODUCT APPROVAL FOR THE FIXED GLASS WINDOWS HAS
 A MAXIMUM SIZE LIMIT OF 20.67 SQFT. THE 146" X 24"
 TRANSOM WINDOW (F) AT THE MASTER BEDROOM APPEARS TO
 EXCEED THE SIZE LIMITATIONS OF THE PRODUCT APPROVAL.
 PLEASE CORRECT. DCA RULE 9N-3
  
 8) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE 90
 DEGREE CORNER CUSTOM EXTERIOR FOLDING DOORS. DCA RULE
 9N-3
  
 9) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 STORM PANELS ARE MISSING THE INSTALLATION INSTRUCTIONS
 REQUIRED BY DCA RULE 9N-3. A KEY PLAN AND AN
 INSTALLATION SCHEDULE IS ALSO REQUIRED. SEE SAMPLE
 INSTALLATION SCHEDULE AT HTTP://WPB.ORG/DEVELOPMENT/CON
 STRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PDF NOTE: ALL
 OF THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE LARGE
 MISSILE IMPACT RATED AND DO NOT REQUIRE SHUTTERS.
  
 10) PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 107.3.4.1
  
 11) PLEASE PROVIDE A RESPONSE LETTER INDICATING HOW THE
 REVIEW COMMENTS HAVE BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-12-19 Cont ID  
Sent By rmcdouga Date 2012-12-19 Time 16:05 Rev Time 0.00
Received By rmcdouga Date 2012-12-19 Time 16:05 Sent To  
Notes
2012-12-19 16:37:012010 FBC
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED IN AN A5 FLOOD HAZARD ZONE.
 THE LOWEST FINISHED FLOOR AND EQUIPMENT FOR THE
 STRUCTURE IS REQUIRED TO BE AT OR ABOVE 7'-6" BFE.
 SPECIFY THE PROPOSED ELEVATIONS ON THE PLANS. NOTE: THE
 ATTACHED GARAGE IS REQUIRED TO BE AT OR ABOVE THIS
 MINIMUM ELEVATION. CITY OF WEST PLAM BEACH MUNICIPLE
 CODES AND FBCR322
  
 2) SUBMIT TWO COPIES OF A SURFACE WATER DRAINAGE PLAN
 SHOWING COMPLIANCE WITH FBCR401.3.
  
 3) SUBMIT TWO SETS OF A SIGNED AND SEALED SUB-SURFACE
 SOIL BEARING REPORT AS REQUIRED BY FBCR401.4
  
 4) THE EXPOSURE CATEGORY IS INCORRECTLY LISTED AS B.
 THE CORRECT EXPOSURE FOR THIS STRUCTURE IS C. FBCR
 301.2.1.4.3
  
 5) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE NEW
 DWELLING AS REQUIRED BY FBC ENERGY CONSERVATION 401.2.
  
 6) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 WINDOWS, DOORS, ROOF COVERING, STORM PANELS, ETC. AS
 REQUIRED BY DCA RULE 9N-3 AND FBCR301.2.1.
  
 7) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT. CITY AMENDMENTS 107.3.4.1
  
 8) THE DESIGN INFORMATION ON SHEET C1 NEEDS TO BE
 UPDATED TO THE REFERENCED EDITION OF ASCE7, WHICH IS
 ASCE7-10. FBCR CHAPTER 43
  
 9) THE PROPOSED STRUCTURE IS LOCATED IN AN A5 FLOOD
 ZONE THE CITY OF W.P.B. FLOOD ORDINANCE REQUIRES THE
 LOWEST FLOOR TO HAVE A MINIMUM ELEVATION OF 7'-6" ABOVE
 BFE. THE PLANS SHOW AN ELEVATION OF 8.0 MSL FOR THE
 DWELLING NOT BFE AND THE PLANS SHOW THREE 8" STEPS DOWN
 INTO THE GARAGE. THE GARAGE FLOOR AND EQUIPMENT ARE
 REQUIRED TO COMPLY WITH THE MINIMUM ELEVATION
 REQUIREMENT. FBCR322.1.4
  
 10) ON SHEET A3.0 ICYNENE SPRAY FOAM INSULATION IS
 SPECIFIED AS WELL AS ATTIC VENTS. WHEN THE FOAM
 INSULATION IS APPLIED TO THE UNDERSIDE OF THE ROOF
 SHEATHING, THIS TYPE OF ATTIC IS REQUIRED TO BE
 UNVENTED. PLEASE CORRECT. FBCR806.4
  
 11) SUBMIT TWO COPIES OF THE PRODUCT EVALUATIONS FOR
 THE SPRAY FOAM INSULATION. FBCR316.3
  
 12) PROVIDE FOOTING DETAILS FOR THE PADS AT THE C4 (4 X
 4 WOOD) COLUMNS. FBCR401.2
  
 13) PROVIDE DETAILS FOR THE INTERIOR BEARING WALL
 FOOTINGS AT THE GARAGE. FBCR401.2
  
 14) SPECIFY 8D RING SHANK NAILS FOR THE ROOF SHEATHING
 AS REQUIRED BY FBCR 803.2.3.1.
  
 15) PLEASE UPDATE THE WIND SPEED DATA ON SHEET S2.1 TO
 EXPOSURE C, 170 MPH FBC. FBC R301.2.1
  
 16) ON SHEET S2.0 SPECIFY THE TRUSS ANCHOR TYPES AND
 LOCATIONS. R802.1.6.5
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-02-01 Cont ID  
Sent By rlecky Date 2013-02-01 Time 14:52 Rev Time 0.00
Received By rlecky Date 2013-02-01 Time 14:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-12-20 Cont ID  
Sent By rlecky Date 2012-12-20 Time 14:40 Rev Time 0.00
Received By rlecky Date 2012-12-20 Time 14:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-02-08 Cont ID  
Sent By rmcdouga Date 2013-02-08 Time 16:23 Rev Time 0.00
Received By rmcdouga Date 2013-02-08 Time 12:39 Sent To  
Notes
2013-02-08 12:40:06IN ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-02-06 Cont ID  
Sent By rmcdouga Date 2013-02-06 Time 16:26 Rev Time 0.00
Received By rmcdouga Date 2013-01-18 Time 16:38 Sent To  
Notes
2013-01-18 16:38:56R-10 BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-12-20 Cont ID  
Sent By jwitmer Date 2012-12-20 Time 16:11 Rev Time 0.00
Received By jwitmer Date 2012-12-06 Time 10:40 Sent To  
Notes
2012-12-06 10:40:57INCOMING SENT TO R04 BOX. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2013-02-08 Cont ID  
Sent By rmcdouga Date 2013-02-08 Time 16:24 Rev Time 0.00
Received By rmcdouga Date 2013-02-08 Time 16:24 Sent To  
Notes
2013-02-08 16:25:09MU-2013-002886

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-12-19 Cont ID  
Sent By rmcdouga Date 2012-12-19 Time 16:03 Rev Time 0.00
Received By rmcdouga Date 2012-12-19 Time 16:03 Sent To  
Notes
2012-12-19 16:05:09AN IMPACT FEE REVIEW BY PALM BEACH COUNTY IS REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2013-02-06 Cont ID  
Sent By hmoser Date 2013-02-06 Time 13:34 Rev Time 0.00
Received By hmoser Date 2013-02-06 Time 13:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2013-01-22 Cont ID  
Sent By tgordon Date 2013-01-22 Time 09:22 Rev Time 0.00
Received By tgordon Date 2013-01-22 Time 09:22 Sent To  
Notes
2013-01-22 09:24:29MECHANICAL CORRECTIONS NEED.
  
 1) AS NOTED IN LAST REVIEW 12/19/12 NOTE #3, SUBMIT
 DUCT DESIGN CAL'S. MANUAL D OR OTHER APPROVED METHODS,
 SEE 2010 FBC/RES. M1601.1. (DUCT SIZES ON MECHANICAL
 PLAN MAY NEED TO BE CHANCED AFTER SEEING MANUAL D
 CAL'S.).
  
 MECHANICAL PLAN REVIEW BY:
 TOM GORDON (HY-BYRD INC.) (561) 805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-12-19 Cont ID  
Sent By tgordon Date 2012-12-19 Time 09:22 Rev Time 0.00
Received By tgordon Date 2012-12-19 Time 09:22 Sent To  
Notes
2012-12-19 10:31:45*** CORRECTIONS NEEDED FOR MECHANICAL REVIEW ***
  
 1) SUBMIT ENERGY CALCULATIONS, SEE 2010 FBC/ENERGY
 401.2 & 405.4.2.
  
 2) SUBMIT COOLING LOAD CAL'S., SEE 2010 FBC/ENERGY
 403.6.1.
  
 3) SUBMIT DUCT DESIGN CAL'S. MANUAL D OR OTHER APPROVED
 METHODS, SEE 2010 FBC/RES. M1601.1.
  
 4) EQUIPMENT LISTING ON PLAN M1.0 SHOWS ALL THREE A/C
 SYSTEMS AS UNIT #1, PLEASE CORRECT, PER 2010 CITY OF
 WPB AMEND. 107.2.1 & 107.3.5.3 .
  
 5) PLAN M1.0 SHOWS RETURN AIR GRILL NOT RETURNING TO
 AHU #3, PLEASE CORRECT PER 2010 FBC/RES. M1602.4.
  
 6) PLAN M1.0 SHOWS RETURN AIR GRILL RETURNING TO THE
 SUPPLY SIDE OF AHU #2, PLEASE CORRECT PER 2010 FBC/RES.
 M1602.4.
  
 7) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR
 RANGE/OVEN IN THE OUTDOOR BBQ SPACE. SEE 2010 FBC/RES.
 M1901.1 & M1901.2.
  
 8) SUBMIT COMBUSTION AIR CALCULATIONS AND MAKE UP AIR
 FOR THE GAS CLOTHES DRYER, AND THE GAS WATER HEATER OR
 PROVIDE FOR COMBUSTION AIR, SEE 2010 FBC/RES. G2407.1.
  
 MECHANICAL PLAN REVIEW BY:
 TOM GORDON (HY-BYRD INC.) (561) 805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-02-05 Cont ID  
Sent By rmcdouga Date 2013-02-05 Time 15:38 Rev Time 0.00
Received By rmcdouga Date 2013-02-05 Time 15:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-12-10 Cont ID  
Sent By rmcdouga Date 2012-12-10 Time 15:10 Rev Time 0.00
Received By rmcdouga Date 2012-12-10 Time 15:10 Sent To  
Notes
2012-12-10 15:35:43PROVISO
  
 FBCR P3104.3 NO HORIZONTAL DRY VENTS ARE ALLOWED.

Review Stop Z ZONING
Rev No 3 Status P Date 2013-02-08 Cont ID  
Sent By mdekle Date 2013-02-08 Time   Rev Time 0.00
Received By mdekle Date 2013-02-08 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2013-01-31 Cont ID  
Sent By mdekle Date 2013-01-31 Time   Rev Time 0.00
Received By mdekle Date 2013-01-31 Time   Sent To  
Notes
2013-01-31 15:32:13ZONING: **** FAILED ****
  
 RESPOND TO COMMENTS IN WRITING.
  
 1. IN ACCORDANCE WITH SECTION 94-482, THE MAXIMUM WIDTH
 FOR A CIRCULAR DRIVEWAY IS 10 FEET. PLEASE REFER TO THE
 GRAPHIC SENT TO THE PROPERTY OWNER ON 1/30/13 AND
 REVISE THE PROPOSED SITE PLAN.
  
 PLEASE BE ADVISED; SEPERATE PERMITS ARE REQUIRED FOR
 THE FOLLOWING:
 1. LANDSCAPING
 2. SWIMMING POOL/SPA
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME
 AND/OR CONSULT THE CITY'S ZONING AND LAND
 DEVELOPMENT REGULATIONS ONLINE @WWW.MUNICODE.COM.
  
 MURRIAH DEKLE, MPA, PLANNER
 PLANNING & ZONING DIVISION
 TEL: (561) 822-1442
 EMAIL: [email protected]
 WWW.CITYOFWPB.COM
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2012-12-20 Cont ID  
Sent By mdekle Date 2012-12-20 Time   Rev Time  
Received By mdekle Date 2012-12-20 Time   Sent To  
Notes
2012-12-20 15:56:23 
 PLANNING: **** FAILED ****
  
 RESPOND TO COMMENTS IN WRITING.
  
 1. IN ACCORDANCE WITH SECTION 94-482, THE MAXIMUM WIDTH
 FOR A CIRCULAR DRIVEWAY IS 10 FEET IN WIDTH. THERE ARE
 NO DIMENSIONS ON THE SITE PLAN FOR THE PROPOSED
 DRIVEWAY.
 2. THE APPLICANT IS REQUIRED TO PROVIDE TWO COPIES OF
 LANDSCAPE PLANS. THE LANDSCAPE PLAN MUST CONTAIN SITE
 DATA IN ACCORDANCE WITH SECTION 94-442 OF THE CITY'S
 ZLDR. ALSO, A CALCULATION FOR THE FRONT AREA NEED TO BE
 PROVIDED BETWEEN THE FIRST 25 FEET OF LOT DEPTH FROM
 THE FRONT PROPERTY LINE MULTIPLIED BY THE TOTAL WIDTH
 OF THE PROPERTY. IF THE SQUARE FOOTAGE EXCEEDS 1,000
 SQ. FT. THE APPLICANT WILL ONLY BE REQUIRED TO MEET THE
 MINIMUM 1,000 SQ. FT LANDSCAPE AREA. SHOW CALCULATION
 OF LANDSCAPE AREA SQUARE FOOTAGE ON LANDSCAPE PLAN.
 3. THE PROPOSED POOL REQUIRES A SEPERATE PERMIT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME
 AND/OR CONSULT THE CITY?S ZONING AND LAND
 DEVELOPMENT REGULATIONS ONLINE @WWW.MUNICODE.COM.
  
 MURRIAH DEKLE, MPA, PLANNER
 PLANNING & ZONING DIVISION
 TEL: (561) 822-1442
 EMAIL: [email protected]
 WWW.CITYOFWPB.COM
  
  
  