| Plan Review Stops For Permit 12120131 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2013-12-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-02-07 |
Time |
11:45 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-02-07 |
Time |
11:45 |
Sent To |
|
|
| Notes |
| 2013-02-07 11:52:47 | REVISION REQUIRED | | | | | | THE FOLLOWING ITEMS HAVE BEEN DEEMED DEFICIENT OR WERE | | | NOTED TO BE MISSING UPON REVIEW. | | | | | | 1) THE WINDOW AND DOOR PRESSURES ON SHEET A1.1 WERE NOT | | | CHANGED TO REFLECT THE CHANGE IN EXPOSURE CATEGORY FROM | | | B TO C FROM THE PREVIOUS REVIEW. SUBMIT REVISED SHEET. | | | | | | 2) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE | | | STRUCTURAL MULLIONS OR PROVIDE SIGNED AND SEALED | | | STRUCTURAL DETAILS FOR THEM. DCA RULE 9N-3 AND CITY | | | AMENDMENTS 107.2.1.3 | | | | | | 3) THE MAXIMUM DESIGN PRESSURE FROM THE PRODUCT | | | APPROVAL FOR THE 5 V CRIMP METAL ROOF OF -52.5 PSF IS | | | TOO LOW FOR ROOF ZONES 2 AND 3. MEAN ROOF HEIGHT IS 20 | | | FT, SLOPE IS 6/12 AND EXPOSURE IS C. PLEASE SUBMIT | | | PRODUCT APPROVAL WITH HIGHER DESIGN PRESSURES. FBCR | | | 301.1.1 | | | | | | 4) THE WINDOW SCHEDULE ON SHEET A1.1 OF THE PLANS | | | SPECIFIES DOUBLE HUNG WINDOWS AND THE PRODUCT APPROVALS | | | THAT WERE SUBMITTED ARE FOR SINGLE HUNG WINDOWS. SUBMIT | | | REVISED SHEET. | | | | | | 5 SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE SOLID | | | CORE FIBERGLASS EXTERIOR DOORS ( #S 2, 7 IN THE DOOR | | | SCHEDULE) AS REQUIRED BY DCA RULE 9N-3. | | | | | | 6) THE PRODUCT APPROVAL FOR THE FIXED GLASS WINDOWS HAS | | | A MAXIMUM SIZE LIMIT OF 20.67 SQFT. THE 146" X 24" | | | TRANSOM WINDOW (F) AT THE MASTER BEDROOM APPEARS TO | | | EXCEED THE SIZE LIMITATIONS OF THE PRODUCT APPROVAL. | | | PLEASE CORRECT. | | | | | | 7) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE 90 | | | DEGREE CORNER CUSTOM EXTERIOR FOLDING DOORS. DCA RULE | | | 9N-3 | | | | | | 8) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE | | | STORM PANELS ARE MISSING THE INSTALLATION INSTRUCTIONS | | | REQUIRED BY DCA RULE 9N-3. A KEY PLAN AND AN | | | INSTALLATION SCHEDULE IS ALSO REQUIRED. SEE SAMPLE | | | INSTALLATION SCHEDULE AT HTTP://WPB.ORG/DEVELOPMENT/CON | | | STRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PDF NOTE: ALL | | | OF THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE LARGE | | | MISSILE IMPACT RATED AND DO NOT REQUIRE SHUTTERS. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2013-02-06 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-02-06 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-02-05 |
Time |
15:38 |
Sent To |
|
|
| Notes |
| 2013-02-06 10:45:35 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE WINDOW AND DOOR PRESSURES ON SHEET A1.1 WERE NOT | | | CHANGED TO REFLECT THE CHANGE IN EXPOSURE CATEGORY FROM | | | B TO C FROM THE PREVIOUS REVIEW. PLEASE CORRECT. FBCR | | | 301.2.1 | | | | | | 2) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE | | | ENERGY CALCULATION FORMS. FBC ENERGY CONSERVATION | | | 405.4.2 | | | | | | 3) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE | | | STRUCTURAL MULLIONS OR PROVIDE SIGNED AND SEALED | | | STRUCTURAL DETAILS FOR THEM. DCA RULE 9N-3 AND CITY | | | AMENDMENTS 107.2.1.3 | | | | | | 4) THE MAXIMUM DESIGN PRESSURE FORM THE PRODUCT | | | APPROVAL FOR THE 5 V CRIMP METAL ROOF OF -52.5 PSF IS | | | TOO LOW FOR ROOF ZONES 2 AND 3. MEAN ROOF HEIGHT IS 20 | | | FT, SLOPE IS 6/12 AND EXPOSURE IS C. PLEASE SUBMIT | | | PRODUCT APPROVAL WITH HIGHER DESIGN PRESSURES. FBCR | | | 301.1.1 | | | | | | 5) THE WINDOW SCHEDULE ON THE PLANS SPECIFIES DOUBLE | | | HUNG WINDOWS AND THE PRODUCT APPROVALS THAT WERE | | | SUBMITTED ARE FOR SINGLE HUNG WINDOWS. PLEASE CLARIFY | | | AND CORRECT. DCA RULE 9N-3 | | | | | | 6) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE SOLID | | | CORE FIBERGLASS EXTERIOR DOORS ( #S 2, 7 IN THE DOOR | | | SCHEDULE) AS REQUIRED BY DCA RULE 9N-3. | | | | | | 7) THE PRODUCT APPROVAL FOR THE FIXED GLASS WINDOWS HAS | | | A MAXIMUM SIZE LIMIT OF 20.67 SQFT. THE 146" X 24" | | | TRANSOM WINDOW (F) AT THE MASTER BEDROOM APPEARS TO | | | EXCEED THE SIZE LIMITATIONS OF THE PRODUCT APPROVAL. | | | PLEASE CORRECT. DCA RULE 9N-3 | | | | | | 8) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE 90 | | | DEGREE CORNER CUSTOM EXTERIOR FOLDING DOORS. DCA RULE | | | 9N-3 | | | | | | 9) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE | | | STORM PANELS ARE MISSING THE INSTALLATION INSTRUCTIONS | | | REQUIRED BY DCA RULE 9N-3. A KEY PLAN AND AN | | | INSTALLATION SCHEDULE IS ALSO REQUIRED. SEE SAMPLE | | | INSTALLATION SCHEDULE AT HTTP://WPB.ORG/DEVELOPMENT/CON | | | STRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PDF NOTE: ALL | | | OF THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE LARGE | | | MISSILE IMPACT RATED AND DO NOT REQUIRE SHUTTERS. | | | | | | 10) PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND | | | APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY | | | AMENDMENTS 107.3.4.1 | | | | | | 11) PLEASE PROVIDE A RESPONSE LETTER INDICATING HOW THE | | | REVIEW COMMENTS HAVE BEEN ADDRESSED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2012-12-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-12-19 |
Time |
16:05 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-12-19 |
Time |
16:05 |
Sent To |
|
|
| Notes |
| 2012-12-19 16:37:01 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE STRUCTURE IS LOCATED IN AN A5 FLOOD HAZARD ZONE. | | | THE LOWEST FINISHED FLOOR AND EQUIPMENT FOR THE | | | STRUCTURE IS REQUIRED TO BE AT OR ABOVE 7'-6" BFE. | | | SPECIFY THE PROPOSED ELEVATIONS ON THE PLANS. NOTE: THE | | | ATTACHED GARAGE IS REQUIRED TO BE AT OR ABOVE THIS | | | MINIMUM ELEVATION. CITY OF WEST PLAM BEACH MUNICIPLE | | | CODES AND FBCR322 | | | | | | 2) SUBMIT TWO COPIES OF A SURFACE WATER DRAINAGE PLAN | | | SHOWING COMPLIANCE WITH FBCR401.3. | | | | | | 3) SUBMIT TWO SETS OF A SIGNED AND SEALED SUB-SURFACE | | | SOIL BEARING REPORT AS REQUIRED BY FBCR401.4 | | | | | | 4) THE EXPOSURE CATEGORY IS INCORRECTLY LISTED AS B. | | | THE CORRECT EXPOSURE FOR THIS STRUCTURE IS C. FBCR | | | 301.2.1.4.3 | | | | | | 5) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE NEW | | | DWELLING AS REQUIRED BY FBC ENERGY CONSERVATION 401.2. | | | | | | 6) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE | | | WINDOWS, DOORS, ROOF COVERING, STORM PANELS, ETC. AS | | | REQUIRED BY DCA RULE 9N-3 AND FBCR301.2.1. | | | | | | 7) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR | | | THE PROJECT. CITY AMENDMENTS 107.3.4.1 | | | | | | 8) THE DESIGN INFORMATION ON SHEET C1 NEEDS TO BE | | | UPDATED TO THE REFERENCED EDITION OF ASCE7, WHICH IS | | | ASCE7-10. FBCR CHAPTER 43 | | | | | | 9) THE PROPOSED STRUCTURE IS LOCATED IN AN A5 FLOOD | | | ZONE THE CITY OF W.P.B. FLOOD ORDINANCE REQUIRES THE | | | LOWEST FLOOR TO HAVE A MINIMUM ELEVATION OF 7'-6" ABOVE | | | BFE. THE PLANS SHOW AN ELEVATION OF 8.0 MSL FOR THE | | | DWELLING NOT BFE AND THE PLANS SHOW THREE 8" STEPS DOWN | | | INTO THE GARAGE. THE GARAGE FLOOR AND EQUIPMENT ARE | | | REQUIRED TO COMPLY WITH THE MINIMUM ELEVATION | | | REQUIREMENT. FBCR322.1.4 | | | | | | 10) ON SHEET A3.0 ICYNENE SPRAY FOAM INSULATION IS | | | SPECIFIED AS WELL AS ATTIC VENTS. WHEN THE FOAM | | | INSULATION IS APPLIED TO THE UNDERSIDE OF THE ROOF | | | SHEATHING, THIS TYPE OF ATTIC IS REQUIRED TO BE | | | UNVENTED. PLEASE CORRECT. FBCR806.4 | | | | | | 11) SUBMIT TWO COPIES OF THE PRODUCT EVALUATIONS FOR | | | THE SPRAY FOAM INSULATION. FBCR316.3 | | | | | | 12) PROVIDE FOOTING DETAILS FOR THE PADS AT THE C4 (4 X | | | 4 WOOD) COLUMNS. FBCR401.2 | | | | | | 13) PROVIDE DETAILS FOR THE INTERIOR BEARING WALL | | | FOOTINGS AT THE GARAGE. FBCR401.2 | | | | | | 14) SPECIFY 8D RING SHANK NAILS FOR THE ROOF SHEATHING | | | AS REQUIRED BY FBCR 803.2.3.1. | | | | | | 15) PLEASE UPDATE THE WIND SPEED DATA ON SHEET S2.1 TO | | | EXPOSURE C, 170 MPH FBC. FBC R301.2.1 | | | | | | 16) ON SHEET S2.0 SPECIFY THE TRUSS ANCHOR TYPES AND | | | LOCATIONS. R802.1.6.5 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2013-02-01 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2013-02-01 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2013-02-01 |
Time |
14:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2012-12-20 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-12-20 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-12-20 |
Time |
14:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2013-02-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-02-08 |
Time |
16:23 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-02-08 |
Time |
12:39 |
Sent To |
|
|
| Notes |
| 2013-02-08 12:40:06 | IN ZONING BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2013-02-06 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-02-06 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-01-18 |
Time |
16:38 |
Sent To |
|
|
| Notes |
| 2013-01-18 16:38:56 | R-10 BOX. JW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2012-12-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2012-12-20 |
Time |
16:11 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2012-12-06 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2012-12-06 10:40:57 | INCOMING SENT TO R04 BOX. JW |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2013-02-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-02-08 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-02-08 |
Time |
16:24 |
Sent To |
|
|
| Notes |
| 2013-02-08 16:25:09 | MU-2013-002886 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2012-12-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-12-19 |
Time |
16:03 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-12-19 |
Time |
16:03 |
Sent To |
|
|
| Notes |
| 2012-12-19 16:05:09 | AN IMPACT FEE REVIEW BY PALM BEACH COUNTY IS REQUIRED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2013-02-06 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2013-02-06 |
Time |
13:34 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2013-02-06 |
Time |
13:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2013-01-22 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2013-01-22 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
tgordon |
Date |
2013-01-22 |
Time |
09:22 |
Sent To |
|
|
| Notes |
| 2013-01-22 09:24:29 | MECHANICAL CORRECTIONS NEED. | | | | | | 1) AS NOTED IN LAST REVIEW 12/19/12 NOTE #3, SUBMIT | | | DUCT DESIGN CAL'S. MANUAL D OR OTHER APPROVED METHODS, | | | SEE 2010 FBC/RES. M1601.1. (DUCT SIZES ON MECHANICAL | | | PLAN MAY NEED TO BE CHANCED AFTER SEEING MANUAL D | | | CAL'S.). | | | | | | MECHANICAL PLAN REVIEW BY: | | | TOM GORDON (HY-BYRD INC.) (561) 805-6732 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2012-12-19 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2012-12-19 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
tgordon |
Date |
2012-12-19 |
Time |
09:22 |
Sent To |
|
|
| Notes |
| 2012-12-19 10:31:45 | *** CORRECTIONS NEEDED FOR MECHANICAL REVIEW *** | | | | | | 1) SUBMIT ENERGY CALCULATIONS, SEE 2010 FBC/ENERGY | | | 401.2 & 405.4.2. | | | | | | 2) SUBMIT COOLING LOAD CAL'S., SEE 2010 FBC/ENERGY | | | 403.6.1. | | | | | | 3) SUBMIT DUCT DESIGN CAL'S. MANUAL D OR OTHER APPROVED | | | METHODS, SEE 2010 FBC/RES. M1601.1. | | | | | | 4) EQUIPMENT LISTING ON PLAN M1.0 SHOWS ALL THREE A/C | | | SYSTEMS AS UNIT #1, PLEASE CORRECT, PER 2010 CITY OF | | | WPB AMEND. 107.2.1 & 107.3.5.3 . | | | | | | 5) PLAN M1.0 SHOWS RETURN AIR GRILL NOT RETURNING TO | | | AHU #3, PLEASE CORRECT PER 2010 FBC/RES. M1602.4. | | | | | | 6) PLAN M1.0 SHOWS RETURN AIR GRILL RETURNING TO THE | | | SUPPLY SIDE OF AHU #2, PLEASE CORRECT PER 2010 FBC/RES. | | | M1602.4. | | | | | | 7) PLEASE SUBMIT DETAILED MANUFACTURER'S | | | SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR | | | RANGE/OVEN IN THE OUTDOOR BBQ SPACE. SEE 2010 FBC/RES. | | | M1901.1 & M1901.2. | | | | | | 8) SUBMIT COMBUSTION AIR CALCULATIONS AND MAKE UP AIR | | | FOR THE GAS CLOTHES DRYER, AND THE GAS WATER HEATER OR | | | PROVIDE FOR COMBUSTION AIR, SEE 2010 FBC/RES. G2407.1. | | | | | | MECHANICAL PLAN REVIEW BY: | | | TOM GORDON (HY-BYRD INC.) (561) 805-6732 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2013-02-05 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-02-05 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-02-05 |
Time |
15:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2012-12-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-12-10 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-12-10 |
Time |
15:10 |
Sent To |
|
|
| Notes |
| 2012-12-10 15:35:43 | PROVISO | | | | | | FBCR P3104.3 NO HORIZONTAL DRY VENTS ARE ALLOWED. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2013-02-08 |
|
|
Cont ID |
|
| Sent By |
mdekle |
Date |
2013-02-08 |
Time |
|
Rev Time |
0.00 |
| Received By |
mdekle |
Date |
2013-02-08 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2013-01-31 |
|
|
Cont ID |
|
| Sent By |
mdekle |
Date |
2013-01-31 |
Time |
|
Rev Time |
0.00 |
| Received By |
mdekle |
Date |
2013-01-31 |
Time |
|
Sent To |
|
|
| Notes |
| 2013-01-31 15:32:13 | ZONING: **** FAILED **** | | | | | | RESPOND TO COMMENTS IN WRITING. | | | | | | 1. IN ACCORDANCE WITH SECTION 94-482, THE MAXIMUM WIDTH | | | FOR A CIRCULAR DRIVEWAY IS 10 FEET. PLEASE REFER TO THE | | | GRAPHIC SENT TO THE PROPERTY OWNER ON 1/30/13 AND | | | REVISE THE PROPOSED SITE PLAN. | | | | | | PLEASE BE ADVISED; SEPERATE PERMITS ARE REQUIRED FOR | | | THE FOLLOWING: | | | 1. LANDSCAPING | | | 2. SWIMMING POOL/SPA | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME | | | AND/OR CONSULT THE CITY'S ZONING AND LAND | | | DEVELOPMENT REGULATIONS ONLINE @WWW.MUNICODE.COM. | | | | | | MURRIAH DEKLE, MPA, PLANNER | | | PLANNING & ZONING DIVISION | | | TEL: (561) 822-1442 | | | EMAIL: [email protected] | | | WWW.CITYOFWPB.COM | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2012-12-20 |
|
|
Cont ID |
|
| Sent By |
mdekle |
Date |
2012-12-20 |
Time |
|
Rev Time |
|
| Received By |
mdekle |
Date |
2012-12-20 |
Time |
|
Sent To |
|
|
| Notes |
| 2012-12-20 15:56:23 | | | | PLANNING: **** FAILED **** | | | | | | RESPOND TO COMMENTS IN WRITING. | | | | | | 1. IN ACCORDANCE WITH SECTION 94-482, THE MAXIMUM WIDTH | | | FOR A CIRCULAR DRIVEWAY IS 10 FEET IN WIDTH. THERE ARE | | | NO DIMENSIONS ON THE SITE PLAN FOR THE PROPOSED | | | DRIVEWAY. | | | 2. THE APPLICANT IS REQUIRED TO PROVIDE TWO COPIES OF | | | LANDSCAPE PLANS. THE LANDSCAPE PLAN MUST CONTAIN SITE | | | DATA IN ACCORDANCE WITH SECTION 94-442 OF THE CITY'S | | | ZLDR. ALSO, A CALCULATION FOR THE FRONT AREA NEED TO BE | | | PROVIDED BETWEEN THE FIRST 25 FEET OF LOT DEPTH FROM | | | THE FRONT PROPERTY LINE MULTIPLIED BY THE TOTAL WIDTH | | | OF THE PROPERTY. IF THE SQUARE FOOTAGE EXCEEDS 1,000 | | | SQ. FT. THE APPLICANT WILL ONLY BE REQUIRED TO MEET THE | | | MINIMUM 1,000 SQ. FT LANDSCAPE AREA. SHOW CALCULATION | | | OF LANDSCAPE AREA SQUARE FOOTAGE ON LANDSCAPE PLAN. | | | 3. THE PROPOSED POOL REQUIRES A SEPERATE PERMIT. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME | | | AND/OR CONSULT THE CITY?S ZONING AND LAND | | | DEVELOPMENT REGULATIONS ONLINE @WWW.MUNICODE.COM. | | | | | | MURRIAH DEKLE, MPA, PLANNER | | | PLANNING & ZONING DIVISION | | | TEL: (561) 822-1442 | | | EMAIL: [email protected] | | | WWW.CITYOFWPB.COM | | | | | | | | | |
|
|