Plan Review Details - Permit 12120102
Plan Review Stops For Permit 12120102
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2013-05-20 Time   Rev Time 0.00
Received By   Date 2013-05-20 Time   Sent To  
Notes
2013-05-20 17:03:10PASSED UNDER REV #13050179 (OK TO PUT IN NOTES PER R
 MCDOUGAL)

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-12-18 Cont ID  
Sent By shill Date 2012-12-18 Time 11:27 Rev Time 0.00
Received By shill Date 2012-12-18 Time 11:27 Sent To  
Notes
2012-12-18 11:32:55****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. PROVIDE A FIRE RATED ASSEMBLY IN ACCORDANCE WITH FBC
 703.2 OR 703.3. AS DISCUSSED, IT APPEARS THAT THE FIRE
 RATED WALL BETWEEN THE HIGHER AND LOWER PORTIONS OF THE
 STRUCTURE WAS COMPROMISED WITH A DOOR, AND A NON
 COMPLIANT WALL (WHICH DOES NOT EXTEND TO THE UNDERSIDE
 OF THE DECK ABOVE) WAS INSTALLED.
  
 2. PLANS ARE TO INCLUDE PRINTED NAME AND THE SIGNATURE
 OF THE INDIVIDUAL TAKING RESPONSIBILITY FOR THE DESIGN,
 FBC 106. IF A TESTED ASSEMBLY IS NOT PROPOSED,
 ENGINEERING REQUIRED.
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-05-20 Cont ID  
Sent By wlehnhar Date 2013-05-20 Time 17:03 Rev Time 0.00
Received By wlehnhar Date 2013-05-20 Time   Sent To  
Notes
2013-05-20 17:03:54PASSED UNDER REV #13050179 (OK TO PUT IN NOTES PER R
 MCDOUGAL)

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-12-06 Cont ID  
Sent By wjolin Date 2012-12-06 Time 11:34 Rev Time 0.00
Received By wjolin Date 2012-12-06 Time 11:28 Sent To B
Notes
2012-12-06 11:34:574705 BROADWAY
 PERMIT #12080060
 TRACKING #12120102
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE BARRIERS SEPARATING DIFFERENT OCCUPANCY TYPES
 SHALL EXTEND FROM THE TOP OF THE FOUNDATION OR
 FLOOR/CEILING ASSEMBLY BELOW TO THE UNDERSIDE OF THE
 FLOOR OR ROOF SHEATHING, SLAB OR DECK ABOVE AND SHALL
 BE SECURELY ATTACHED THERETO. SUCH FIRE BARRIERS SHALL
 BE CONTINUOUS THROUGH CONCEALED SPACES, SUCH AS THE
 SPACE ABOVE A CEILING.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-12-18 Cont ID  
Sent By shill Date 2012-12-18 Time 11:33 Rev Time 0.00
Received By shill Date 2012-12-04 Time 16:44 Sent To  
Notes
2012-12-04 16:45:16SENT TO FIRE BOX