Plan Review Details - Permit 12120102
| Plan Review Stops For Permit 12120102 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2013-05-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
2013-05-20 |
Time |
|
Sent To |
|
|
| Notes |
| 2013-05-20 17:03:10 | PASSED UNDER REV #13050179 (OK TO PUT IN NOTES PER R | | | MCDOUGAL) |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2012-12-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2012-12-18 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2012-12-18 |
Time |
11:27 |
Sent To |
|
|
| Notes |
| 2012-12-18 11:32:55 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. PROVIDE A FIRE RATED ASSEMBLY IN ACCORDANCE WITH FBC | | | 703.2 OR 703.3. AS DISCUSSED, IT APPEARS THAT THE FIRE | | | RATED WALL BETWEEN THE HIGHER AND LOWER PORTIONS OF THE | | | STRUCTURE WAS COMPROMISED WITH A DOOR, AND A NON | | | COMPLIANT WALL (WHICH DOES NOT EXTEND TO THE UNDERSIDE | | | OF THE DECK ABOVE) WAS INSTALLED. | | | | | | 2. PLANS ARE TO INCLUDE PRINTED NAME AND THE SIGNATURE | | | OF THE INDIVIDUAL TAKING RESPONSIBILITY FOR THE DESIGN, | | | FBC 106. IF A TESTED ASSEMBLY IS NOT PROPOSED, | | | ENGINEERING REQUIRED. | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2013-05-20 |
|
|
Cont ID |
|
| Sent By |
wlehnhar |
Date |
2013-05-20 |
Time |
17:03 |
Rev Time |
0.00 |
| Received By |
wlehnhar |
Date |
2013-05-20 |
Time |
|
Sent To |
|
|
| Notes |
| 2013-05-20 17:03:54 | PASSED UNDER REV #13050179 (OK TO PUT IN NOTES PER R | | | MCDOUGAL) |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2012-12-06 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2012-12-06 |
Time |
11:34 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2012-12-06 |
Time |
11:28 |
Sent To |
B |
|
| Notes |
| 2012-12-06 11:34:57 | 4705 BROADWAY | | | PERMIT #12080060 | | | TRACKING #12120102 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | FIRE BARRIERS SEPARATING DIFFERENT OCCUPANCY TYPES | | | SHALL EXTEND FROM THE TOP OF THE FOUNDATION OR | | | FLOOR/CEILING ASSEMBLY BELOW TO THE UNDERSIDE OF THE | | | FLOOR OR ROOF SHEATHING, SLAB OR DECK ABOVE AND SHALL | | | BE SECURELY ATTACHED THERETO. SUCH FIRE BARRIERS SHALL | | | BE CONTINUOUS THROUGH CONCEALED SPACES, SUCH AS THE | | | SPACE ABOVE A CEILING. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2012-12-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2012-12-18 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2012-12-04 |
Time |
16:44 |
Sent To |
|
|
| Notes |
| 2012-12-04 16:45:16 | SENT TO FIRE BOX |
|
|
|