Plan Review Details - Permit 12120090
Plan Review Stops For Permit 12120090
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-01-11 Cont ID  
Sent By rmcdouga Date 2013-01-11 Time 15:19 Rev Time 0.00
Received By rmcdouga Date 2013-01-11 Time 15:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-12-05 Cont ID  
Sent By rmcdouga Date 2012-12-05 Time 07:59 Rev Time 0.00
Received By rmcdouga Date 2012-12-05 Time 07:58 Sent To  
Notes
2012-12-05 08:21:512010 FBC
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C WITH
 A WIND SPEED OF 170 MPH VULT UPLIFT / 132 MPH VASD. THE
 COMPONENT AND CLADDING UPLIFT PRESSURES FOR THE
 PERIMETER AND CORNER AREAS EXCEED THE MAXIMUM DESIGN
 PRESSURE OF -52.5 PSF FOR THE PROPOSED ROOF SYSTEM ON
 PAGE 18 OF THE NOA USING JM ULTRAFAST SCREWS AND 3"
 PLATES. LIMITATION #7 ON PAGE 20 ALLOWS FOR INCREASED
 FASTENER DENSITIES IN THESE AREAS TO MEET THE ENHANCED
 UPLIFT PRESSURES. SIGNED AND SEALED RAS 117
 CALCULATIONS FROM A FLORIDA REGISTERED PROFESSIONAL
 ENGINEER, REGISTERED ARCHITECT OR REGISTERED ROOF
 CONSULTANT IS REQUIRED. FBCR301.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-01-11 Cont ID  
Sent By rmcdouga Date 2013-01-11 Time 15:19 Rev Time 0.00
Received By rmcdouga Date 2013-01-10 Time 13:14 Sent To  
Notes
2013-01-11 13:14:54GAVE TO ROBBIE