Plan Review Details - Permit 12110764
Plan Review Stops For Permit 12110764
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2012-12-07 Cont ID  
Sent By rmcdouga Date 2012-12-07 Time 14:26 Rev Time 0.00
Received By rmcdouga Date 2012-12-07 Time 14:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-12-07 Cont ID  
Sent By rmcdouga Date 2012-12-07 Time 14:28 Rev Time 0.00
Received By rmcdouga Date 2012-12-07 Time 14:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-01-04 Cont ID  
Sent By rmcdouga Date 2013-01-04 Time 09:04 Rev Time 0.00
Received By rmcdouga Date 2013-01-03 Time 14:04 Sent To  
Notes
2013-01-03 14:04:53SENT TO ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-12-10 Cont ID  
Sent By rmcdouga Date 2012-12-10 Time 09:26 Rev Time 0.00
Received By rmcdouga Date 2012-11-30 Time 13:35 Sent To  
Notes
2012-12-03 13:35:39SENT TO ZONING SHELF FOR REVIEW. JG.

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-01-04 Cont ID  
Sent By rmcdouga Date 2013-01-04 Time 09:04 Rev Time 0.00
Received By rmcdouga Date 2013-01-04 Time 09:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-12-10 Cont ID  
Sent By rmcdouga Date 2012-12-10 Time 09:26 Rev Time 0.00
Received By rmcdouga Date 2012-12-10 Time 09:26 Sent To  
Notes
2012-12-07 16:57:432010 FBC
  
 DENIED BY PLUMBING
  
 1) THE PLANS INDICATE THAT THE EXISTING POOL SINGLE
 MAIN DRAIN IS TO BE TIED IN WITH THE NEW SPA
 CIRCULATION SYSTEM USING ONE 2 H.P. VARIABLE SPEED
 JANDY STEALTH PRO SERIES PUMP. THIS MODIFICATION WILL
 INCREASE THE WATER VELOCITY AT THE EXISTING POOL DRAIN
 IN VIOLATION OF 2010 FBCR 4101.6.3 AND INCREASES THE
 CHANCES OF ENTRAPMENT. PLEASE CORRECT. NOTE: THE
 EXISTING BUILDING CODE ALLOWS THE EXISTING POOL
 CIRCULATION SYSTEM TO REMAIN AS IT IS, AS LONG AS NO
 CHANGES ARE MADE TO IT. THE NEW SPA IS REQUIRED TO
 COMPLY WITH THE 2010 FBCR.
  
 2) THE PUMP CURVE CHART THAT WAS SUBMITTED SHOWS A
 TOTAL DYNAMIC HEAD OF 73 FEET. THIS IS A LOT OF HEAD
 PRESSURE. SUBMIT THE TDH CALCULATIONS FROM THE ENGINEER
 THAT WERE USED TO ARRIVE AT THIS NUMBER. INCLUDE THE
 HEAD LOSS SPECS. FOR THE FILTER AND OTHER COMPONENTS.
 CITY AMENDMENTS 107.2.1.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2013-01-03 Cont ID  
Sent By mdekle Date 2013-01-03 Time   Rev Time 0.00
Received By mdekle Date 2013-01-03 Time 16:40 Sent To P
Notes
2013-01-03 16:38:21GAVE TO ROBERT MCD. - MD

Review Stop Z ZONING
Rev No 1 Status F Date 2012-12-07 Cont ID  
Sent By mdekle Date 2012-12-07 Time   Rev Time  
Received By mdekle Date 2012-12-03 Time   Sent To  
Notes
2012-12-07 09:55:36THE PROPOSED IMPROVEMENTS MUST BE LOCATED A MINIMUM OF
 FIVE (5') FEET FROM THE REAR PROPERTY LINE. PLEASE
 REVISE.
2012-12-07 09:53:51SENT TO 'RES. SWIMMING POOLS' BOX