Plan Review Details - Permit 12110756
Plan Review Stops For Permit 12110756
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2012-12-10 Cont ID  
Sent By JWITMER Date 2012-12-10 Time 12:43 Rev Time 0.00
Received By jwitmer Date 2012-12-10 Time 11:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-12-05 Cont ID  
Sent By RLECKY Date 2012-12-05 Time 13:13 Rev Time 0.00
Received By rlecky Date 2012-12-05 Time 11:50 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2013-03-03 Cont ID  
Sent By MGONZALE Date 2013-03-03 Time   Rev Time 1.00
Received By mgonzale Date 2013-03-03 Time   Sent To I
Notes
2013-03-03 11:50:18PASSED WITH PROVISO:
  
 #1 SOURCE OF DOMESTIC WATER FOR MAKE-UP WATER MUST
 EITHER HAVE AN AIR GAP OR A UNIVERSITY OF SOUTHERN
 CALIFORNIA CERTIFIED BACKFLOW DEVICE.
  
 #2 SUBMETERING MAY ASSIST WITH BILLING WHEN COMPARING
 WATER USE -VS- EVAPORATED WATER CONSUMED BY CHILLER
 PROCESS. A SEPARATE CITY METER MAY BE REQUESTED SHOULD
 YOU CHOOSE TO HAVE A DEDICATED DOMESTIC WATER SOURCE.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-12-08 Cont ID  
Sent By WJOLIN Date 2012-12-08 Time 19:58 Rev Time 0.00
Received By wjolin Date 2012-12-08 Time 19:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-03-05 Cont ID  
Sent By shill Date 2013-03-05 Time 17:44 Rev Time 0.00
Received By shill Date 2012-11-30 Time 15:58 Sent To  
Notes
2012-12-03 16:00:38SENT TO C14 SHELF FOR REVIEW. JG.

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2012-12-14 Cont ID  
Sent By ajones Date 2012-12-14 Time 08:21 Rev Time 0.00
Received By ajones Date 2012-12-14 Time 08:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-12-14 Cont ID  
Sent By HMOSER Date 2012-12-14 Time 11:08 Rev Time 0.00
Received By lmartine Date 2012-12-14 Time 11:08 Sent To  
Notes
2012-12-14 11:12:45REVISION TO PLANS M0.1, M1.1, M2.1A, M2.1B, M2.2A,
 M2.3, * M3.2 .

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status P Date 2012-12-11 Cont ID  
Sent By lwagner Date 2012-12-11 Time 09:13 Rev Time 0.00
Received By lwagner Date 2012-12-11 Time 09:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-12-11 Cont ID  
Sent By LWAGNER Date 2012-12-11 Time 09:13 Rev Time 0.00
Received By lwagner Date 2012-12-11 Time 08:33 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2012-12-14 Cont ID  
Sent By avann Date 2012-12-14 Time 08:21 Rev Time 0.00
Received By ajones Date 2012-12-14 Time 08:21 Sent To  
Notes
2012-12-07 15:51:2112/10/12