| 2013-02-13 12:49:41 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2010 |
| | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 1. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS, |
| | SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING |
| | CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR |
| | BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING |
| | CANNOT BE REDUCED BY MORE THAN 5%. |
| | |
| | 2ND REVIEW, CODE COMPLIANCE FOR EMERGENCY MEANS OF |
| | ESCAPE AND RESCUE HAS NOT BEEN SHOWN FOR THE FOLLOWING |
| | ROOMS: |
| | |
| | BEDROOM, FIRST FLOOR, OPENINGS M, N, O ARE ALL FIXED |
| | WINDOWS. PLEASE SHOW EMERGENCY MEANS OF ESCAPE AND |
| | RESCUE FOR THIS ROOM, AS WELL AS CLEAR OPENING |
| | DIMENSIONS. REVISE WINDOW SCHEDULE AS NECESSARY. |
| | |
| | BEDROOM 2ND FLOOR, WINDOWS P AND Q CASEMENT, SIZE AND |
| | CLEAR OPENING NOT CLEAR. THE DIMENSIONS, 22X46, DO NOT |
| | CORRELATE WITH THE PHOTOGRAPHS PROVIDED AND THE |
| | DIMENSIONS PROVIDED BY PREVIOUS CONTRACTOR. 22" DOES |
| | NOT MEET THE MINIMUM WIDTH FOR EMERGENCY ESCAPE AND |
| | RESCUE, BUT THE PHOTOGRAPH FOR EAST ELEVATION SHOWS A |
| | WIDER WINDOW. PLEASE SHOW COMPLIANCE FOR FBC R 310. |
| | |
| | BEDROOMS ON 2ND FLOOR WITH WINDOWS R THROUGH U, WINDOW |
| | HEIGHTS DO NOT MEET REQUIREMENT FOR EMERGENCY ESCAPE |
| | AND RESCUE. PROVIDE INFORMATION REQUESTED - EXISTING |
| | WINDOW TYPE, CLEAR OPENING. |
| | |
| | PLEASE NOTE THAT ONLY ONE EMERGENCY ESCAPE AND RESCUE |
| | OPENING IS REQUIRED FOR EACH BEDROOM. |
| | |
| | 2. OK |
| | |
| | 3. OK |
| | |
| | NEW COMMENT: |
| | |
| | 4. THE INSPECTION LETTER FROM THE ENGINEER IS CONFUSING |
| | AS IT IS FOR STRUCTURAL STEEL CONNECTIONS. NO |
| | STRUCTURAL STEEL SHOWN ON THE PLAN. |
| | |
| | ALSO, PHOTOGRAPHS SHOW THAT ONE WINDOW WILL BE |
| | ELIMINATED. PROVIDE A STRUCTURAL DETAIL FOR CLOSING THE |
| | OPENING. |
| | |
| | |
| | |