Plan Review Details - Permit 12110720
Plan Review Stops For Permit 12110720
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-01-29 Cont ID  
Sent By shill Date 2013-01-29 Time 13:45 Rev Time 0.00
Received By shill Date 2013-01-29 Time 13:45 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-12-11 Cont ID  
Sent By shill Date 2012-12-11 Time 20:28 Rev Time 0.00
Received By shill Date 2012-12-11 Time 20:28 Sent To FIRE
Notes
2012-12-11 20:31:33****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. AS THIS APPEARS TO BE ASSEMBLY OCCUPANCY
 (RESTAURANT), PROVIDE MORE INFORMATION REGARDING THE
 DOORS. WILL THIS DOOR HAVE A PANIC DEVICE? IF YES,
 PLEASE REVISE PLAN TO INCLUDE PANIC HARDWARE.
  
 IF NOT, PROVIDE A LIFE SAFETY PLAN TO SHOW THAT THIS
 DOOR IS EXEMPT FROM FBC 1008.1.10 AND PROVIDE HARDWARE
 INFORMATION.
  
 2. THE PRODUCT APPROVAL FOR THE ALUMINUM WALL SYSTEM IS
 EXPIRED; PLEASE PROVIDE CURRENT FLORIDA STATE OR LOCAL
 PRODUCT APPROVAL FAC9N-3.
  
 3. THE CONTRACTOR ON THE APPLICATION IS SOUTHWINDS" BUT
 THE CONTRACTOR IS REGISTERED AS DUCKWORTH & DUCKWORTH.
 PLEASE ADDRESS AT THE FRONT COUNTER; PERMIT APPLICATION
 AND CONTRACTOR REGISTRATION IS TO MATCH FS489.
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-01-30 Cont ID  
Sent By wjolin Date 2013-01-30 Time 14:28 Rev Time 0.00
Received By wjolin Date 2013-01-30 Time 14:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-12-13 Cont ID  
Sent By wjolin Date 2012-12-13 Time 12:51 Rev Time 0.00
Received By wjolin Date 2012-12-13 Time 12:44 Sent To B
Notes
2012-12-13 12:51:221023 NORTH DIXIE HIGHWAY
 PERMIT #12110720
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE LOCK/LATCH RELEASING MECHANISM ON ALL DOORS SHALL
 OPEN THE DOOR WITH NOT MORE THAN ONE RELEASING
 OPERATION. THE RELEASING MECHANISM SHALL HAVE AN
 OBVIOUS METHOD OF OPERATION THAT IS READILY OPERATED
 UNDER ALL LIGHTING CONDITIONS. THE RELEASING DEVICE
 SHOULD BE CAPABLE OF BEING OPERATED WITH ONE HAND AND
 SHOULD NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR
 TWISTING OF THE WRIST TO OPERATE PER SECTION 7.2.1.5.9
 OF NFPA 101 FLORIDA EDITION 2007.
  
 THUMB-TURN LOCK TO BE EQUIPPED WITH A LOCK/UNLOCK
 INDICATOR.
  
 FOR OCCUPANCIES WITH AN OCCUPANT LOAD OF 100 OR MORE
 PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON DOORS TO
 RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES ARE
 PERMITTED THAT WOULD NOT BE RELEASED BY THE PANIC
 HARDWARE. AS A SUBSTITUTE FOR PANIC HARDWARE, THE MAIN
 ENTRANCE IS PERMITTED TO HAVE AN INTERIOR KEYED DOOR
 LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN STATING
 THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS
 OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1 INCH IN
 HEIGHT. A THUMB TURN STYLE LOCK IS NOT PERMITTED TO BE
 SUBSTITUTED FOR A KEYED LOCK.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-01-30 Cont ID  
Sent By wjolin Date 2013-01-30 Time 14:28 Rev Time 0.00
Received By wjolin Date 2013-01-18 Time 16:27 Sent To  
Notes
2013-01-18 16:27:48TO SAMANTHA'S DESK.JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-12-18 Cont ID  
Sent By shill Date 2012-12-18 Time 08:13 Rev Time 0.00
Received By shill Date 2012-11-29 Time 11:49 Sent To  
Notes
2012-11-29 11:50:04MISC. 1