Plan Review Details - Permit 12110603
Plan Review Stops For Permit 12110603
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-12-18 Cont ID  
Sent By shill Date 2012-12-18 Time 11:02 Rev Time 0.00
Received By shill Date 2012-12-18 Time 11:02 Sent To  
Notes
2012-12-18 11:03:36***RESUBMITTAL DONE PRIOR TO FIRST BUILDING REVIEW.
 THEREFORE, BUILDING COMMENTS REMAIN AS PER FIRST
 REVIEW:
  
  
 ****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. FBC R 314.3.1, SMOKE DETECTORS IN EXISTING DWELLING
 REQUIRED.
  
 2. FBC 107.2.1, ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
 3. INCLUDE WIND DESIGN CRITERIA ON THE PLAN, FBC R 301.
  
 4. IT IS NOT CLEAR HOW THE WALLS WILL BE STRUCTURALLY
 CONTINUOUS AROUND THE POSTS. DESIGN IS TO BE IN
 ACCORDANCE WITH ONE OF THE METHODS IN FBC R 301.1. HOW
 WILL SILL PLATES AND TOP PLATES BE INSTALLED THROUGH
 THE EXISTING COLUMNS WHICH ARE ATTACHED TO SLAB BELOW
 AND ROOF ABOVE? UNDER WHAT WIND DESIGN CRITERIA WAS THE
 CARPORT CONSTRUCTED? THIS IS A PARTIALLY ENCLOSED
 STRUCTURE, YOU ARE NOW MAKING A PORTION AN ENCLOSED
 STRUCTURE, BUT NO INFORMATION REGARDING REINFORCEMENT
 OF EXISTING WAS PROVIDED. IT APPEARS THAT ENGINEERING
 MAY BE REQUIRED. ADDITIONAL DETAILS SHOWING HOW THE
 WOOD FRAME WALLS WILL BE INTEGRATED INTO THE EXISTING
 STEEL COLUMNS WILL BE REQUIRED.
  
 5. SHOW ROOM DESIGNATION FOR THE ROOM FROM THE HOUSE TO
 THE PROPOSED STORAGE AREA, FBC R 310 (TO CONFIRM
 BEDROOM EMERGENCY ESCAPE AND RESCUE IS NOT BLOCKED).
  
 6. FOR THE SHUTTER, COMPLETE THE SAMPLE INSTALLATION
 SCHEDULE OR PROVIDE ALL INFORMATION TO SHOW CODE
 COMPLIANCE IN ANOTHER FORMAT, FBC*106, FBC R301,
 FBC1609. TWO SETS REQUIRED. THIS FORM IS AVAILABLE IN
 THE LOBBY OR ON THE INTERNET AT
  
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 7. FLORIDA STATE OR LOCAL PRODUCT APPROVAL COVER SHEET
 REQUIRED FOR THE DOOR, FAC9N-3. ONLY THE EVALUATION
 REPORT WAS PROVIDED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-12-05 Cont ID  
Sent By shill Date 2012-12-05 Time 11:45 Rev Time 0.00
Received By shill Date 2012-12-05 Time 11:45 Sent To  
Notes
2012-12-05 11:58:43****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. FBC R 314.3.1, SMOKE DETECTORS IN EXISTING DWELLING
 REQUIRED.
  
 2. FBC 107.2.1, ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
 3. INCLUDE WIND DESIGN CRITERIA ON THE PLAN, FBC R 301.
  
 4. IT IS NOT CLEAR HOW THE WALLS WILL BE STRUCTURALLY
 CONTINUOUS AROUND THE POSTS. DESIGN IS TO BE IN
 ACCORDANCE WITH ONE OF THE METHODS IN FBC R 301.1. HOW
 WILL SILL PLATES AND TOP PLATES BE INSTALLED THROUGH
 THE EXISTING COLUMNS WHICH ARE ATTACHED TO SLAB BELOW
 AND ROOF ABOVE? UNDER WHAT WIND DESIGN CRITERIA WAS THE
 CARPORT CONSTRUCTED? THIS IS A PARTIALLY ENCLOSED
 STRUCTURE, YOU ARE NOW MAKING A PORTION AN ENCLOSED
 STRUCTURE, BUT NO INFORMATION REGARDING REINFORCEMENT
 OF EXISTING WAS PROVIDED. IT APPEARS THAT ENGINEERING
 MAY BE REQUIRED. ADDITIONAL DETAILS SHOWING HOW THE
 WOOD FRAME WALLS WILL BE INTEGRATED INTO THE EXISTING
 STEEL COLUMNS WILL BE REQUIRED.
  
 5. SHOW ROOM DESIGNATION FOR THE ROOM FROM THE HOUSE TO
 THE PROPOSED STORAGE AREA, FBC R 310 (TO CONFIRM
 BEDROOM EMERGENCY ESCAPE AND RESCUE IS NOT BLOCKED).
  
 6. FOR THE SHUTTER, COMPLETE THE SAMPLE INSTALLATION
 SCHEDULE OR PROVIDE ALL INFORMATION TO SHOW CODE
 COMPLIANCE IN ANOTHER FORMAT, FBC*106, FBC R301,
 FBC1609. TWO SETS REQUIRED. THIS FORM IS AVAILABLE IN
 THE LOBBY OR ON THE INTERNET AT
  
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 7. FLORIDA STATE OR LOCAL PRODUCT APPROVAL COVER SHEET
 REQUIRED FOR THE DOOR, FAC9N-3. ONLY THE EVALUATION
 REPORT WAS PROVIDED.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-12-18 Cont ID  
Sent By shill Date 2012-12-18 Time 11:02 Rev Time 0.00
Received By shill Date 2012-12-05 Time 13:58 Sent To  
Notes
2012-12-05 13:58:56ZONING RESUBMITTAL ROUTED TO ZONING BOX
 (SUBMITTED PRIOR TO BUILDING REVIEW)
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-12-05 Cont ID  
Sent By shill Date 2012-12-05 Time 11:58 Rev Time 0.00
Received By shill Date 2012-11-21 Time 09:46 Sent To  
Notes
2012-11-27 10:03:22EXPEDITED
 IN ZONING BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2012-12-11 Cont ID  
Sent By mdekle Date 2012-12-11 Time   Rev Time 0.00
Received By mdekle Date 2012-12-06 Time   Sent To  
Notes
2012-12-11 13:41:28GAVE TO S.H. - MD

Review Stop Z ZONING
Rev No 1 Status F Date 2012-11-29 Cont ID  
Sent By mdekle Date 2012-11-29 Time   Rev Time 0.00
Received By mdekle Date 2012-11-27 Time 16:51 Sent To  
Notes
2012-11-29 15:50:07THE APPLICANT IS REQUESTED TO INCLUDE THE DIMENSIONS OF
 THE BUILLDING SETBACK FOR THE PROPOSED ENCLOSURE,
 RELATING TO THE PROPERTY LINE. PLEASE BE ADVISED; BASED
 ON THE SURVEY DIMENSIONS AND THE FLOOR PLAN, THE
 ENCLOSURE COULD POTENTIALLY ENCROACH .5 INCHES INTO THE
 REQUIRED BUILDING SETBACK AND SET FORTH IN SECTION 94
 OF THE CITY'S LDZR.