Plan Review Details - Permit 12110592
Plan Review Stops For Permit 12110592
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-01-07 Cont ID  
Sent By jwitmer Date 2013-01-07 Time 14:10 Rev Time 0.00
Received By jwitmer Date 2013-01-07 Time 14:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-12-04 Cont ID  
Sent By jwitmer Date 2012-12-04 Time 08:08 Rev Time 0.00
Received By jwitmer Date 2012-12-04 Time 08:00 Sent To  
Notes
2012-12-04 09:02:32BUILDING PLAN REVIEW
 PERMIT: 12110592
 ADD: 1401 FORUM WAY # 600
 CONT: T & M DEVELOPMENT
 TEL: (561)2121398
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE SEE FIRE & MECHANICAL REVIEWS FOR COMMENTS
 THAT PERTAIN TO THE BUILDING REVIEW. SHEET UNDER THE
 HEADING" THIS PROJECT SHALL COMPLY WITH",
 EXISTING FIRE SEPERATIONS AT ELEVATORS, STAIRS,
 BUILDING ELECTRICAL & MECHANICAL ROOMS, ARE NOT
 MODIFIED OR ALTERED IN ANY MANNER.
  
 SHEET A1 THE RECEPTION LOBBY (101) / ELEVATOR LOBBY
 INDICATES A WALL TAG TYPE P2 & P4. THESE WALLS ARE
 INDICATED AS NON-RATED WALLS. PLEASE REVIEW THE 2010
 FBC-B 708.14.1 ELEVATOR LOBBY AND THE 7 EXCEPTIONS. THE
 PLANS DO NOT INDICATE THE ELEVATOR SHAFT TO BE
 PRESSURIZED IN ACCORDANCE WITH 708.14.2 SEE EXCEPTION #
 6. IT APPEARS WITH THE PARTITION TYPE P2 & P4 BEING
 DEPICTED FROM FLOOR TO CONCRETE DECK ABOVE THEY ARE
 BEING BUILT AS EITHER 1 HOUR FIRE RATING OR A SMOKE
 PARTITION (EXCEPTION #5) WOULD NEED TO MEET THE
 REQUIREMENTS LISTED WITHIN THE EXCEPTION, THE
 MECHANICAL PLANS DO NOT INDICATE THE USE OF ANY FIRE
 DAMPERS IN THIS LOCATION.
 IF THE P-4 WALL IS GOING TO BE BUILT AS A FIRE
 PARTITION THEN THE TEMPERED GLASS WINDOW WILL ALSO NEED
 TO QUALIFY UNDER THE REQUIREMENTS OF OPENING
 PROTECTIVES SEE TABLE 715.5 FOR FIRE PARTITION AND
 REQUIRED 3/4 HR WINDOW ASSEMBLY RATING.
  
 2) THE PLANS LACK IN PROVIDING THE MINIMUM PLAN REVIEW
 CRITERIA FOR COMMERCIAL BUILDINGS:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
  
 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS
  
 6. LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING REQUIREMENTS:
 HIGH RISE 907.2.13 FIRE ALARMS
  
 7. LIFE SAFETY PLAN, OCCUPANCY LOAD/EGRESS REQUIREMENTS
 SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
  
 107.3.5.1.2 ELECTRICAL
  
 4. EMERGENCY SYSTEMS LIGHTING
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-11-27 Cont ID  
Sent By rlecky Date 2012-11-27 Time 11:37 Rev Time 0.00
Received By rlecky Date 2012-11-27 Time 11:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-01-05 Cont ID  
Sent By wjolin Date 2013-01-05 Time 11:47 Rev Time 0.00
Received By wjolin Date 2013-01-05 Time 11:19 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-11-29 Cont ID  
Sent By wjolin Date 2012-11-29 Time 12:11 Rev Time 0.00
Received By wjolin Date 2012-11-29 Time 11:39 Sent To  
Notes
2012-11-29 12:11:191401 FORUM PLACE - #600
 PERMIT #12110592
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE A DEMOLITION PLAN.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR
 AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL
 HAVE "NO SMOKING" SIGNS POSTED. WHERE SMOKING IS
 PERMITTED, SAFE RECEPTACLES FOR SMOKING MATERIALS SHALL
 BE PROVIDED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL FIRE RATED
 WALLS, EXIT SIGNS, EMERGENCY LIGHTING, TRAVEL
 DISTANCES, COMMON PATH OF TRAVEL, FIRE EXTINGUISHERS,
 ETC.
  
 THE DOOR HARDWARE SCHEDULE DOES NOT INDICATE THE
 LOCKSETS TO BE INSTALLED ON THE VARIOUS DOORS.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 NO FIRE ALARM OR FIRE SPRINKLER INFORMATION PROVIDED ON
 PLANS. ENGINEERED FIRE ALARM AND FIRE SPRINKLER
 CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL
 BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS BEEN
 ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-01-07 Cont ID  
Sent By jwitmer Date 2013-01-07 Time 14:10 Rev Time 0.00
Received By jwitmer Date 2013-01-04 Time 16:52 Sent To  
Notes
2013-01-04 16:53:02EXPEDITED
 2ND RUN
 GAVE TO WESLEY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-12-04 Cont ID  
Sent By jwitmer Date 2012-12-04 Time 09:02 Rev Time 0.00
Received By jwitmer Date 2012-11-21 Time 16:55 Sent To  
Notes
2012-11-26 16:57:25EXPEDITED
 B--18

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-12-03 Cont ID  
Sent By lmartine Date 2012-12-03 Time 14:28 Rev Time 0.00
Received By lmartine Date 2012-12-03 Time 14:28 Sent To  
Notes
2012-12-03 14:37:36*** PROVISO ***
 1) DUCTS & TRANSFER OPENINGS THAT PENETRATE RATED
 ASSEMBLIES SHALL COMPLY WITH 2010 FBC/M 607.