Plan Review Details - Permit 12110590
Plan Review Stops For Permit 12110590
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-03-13 Cont ID  
Sent By shill Date 2013-03-13 Time 15:04 Rev Time 0.00
Received By shill Date 2013-03-13 Time 15:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-01-28 Cont ID  
Sent By shill Date 2013-01-28 Time 16:53 Rev Time 0.00
Received By shill Date 2013-01-28 Time 16:53 Sent To  
Notes
2013-01-28 16:55:56****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 1. OK
  
 2. STUCCO OVER WOOD SHEATHING REQUIRES A BOND BREAK,
 FBC RESIDENTIAL 703.6.3.
  
 2ND REVIEW, NOT ADDRESSED. NOT CLEAR WHY APPLICATION IS
 FOR WOOD SIDING, DETAIL IS FOR STUCCO.
  
 3. ROOF PERMIT REQUIRED. THE ROOF SUBCONTRACTOR MAY
 SUBMIT FOR PERMIT AFTER ISSUANCE OF THE RENOVATION
 PERMIT BUT MUST OBTAIN SUB PERMIT PRIOR TO COMMENCEMENT
 OF WORK. (ADVISORY ONLY)
  
 4. FOR THE ROOF, PROVIDE THE FOLLOWING:
  
 ON THE NOA, INDICATE WHICH APPROVED ASSEMBLY IS
 PROPOSED
 SEE GENERAL LIMITATION #7, ENHANCE FASTENING FOR ZONES
 2 AND 3 TO BE SPECIFIED BY AN ARCHITECT, ENGINEER, OR
 REGISTERED ROOF CONSULTANT
  
 2ND REVIEW, NOT ADDRESSED. ROOF SCOPE WILL BE REMOVED
 IF NOT ADDRESSED PRIOR TO ISSUANCE OF WINDOW PERMIT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-12-11 Cont ID  
Sent By shill Date 2012-12-11 Time 16:05 Rev Time 0.00
Received By shill Date 2012-12-11 Time 16:05 Sent To  
Notes
2012-12-11 16:11:26****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS,
 SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING
 CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR
 BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING
 CANNOT BE REDUCED BY MORE THAN 5%.
  
 2. STUCCO OVER WOOD SHEATHING REQUIRES A BOND BREAK,
 FBC RESIDENTIAL 703.6.3.
  
 3. ROOF PERMIT REQUIRED. THE ROOF SUBCONTRACTOR MAY
 SUBMIT FOR PERMIT AFTER ISSUANCE OF THE RENOVATION
 PERMIT BUT MUST OBTAIN SUB PERMIT PRIOR TO COMMENCEMENT
 OF WORK. (ADVISORY ONLY)
  
 4. FOR THE ROOF, PROVIDE THE FOLLOWING:
  
 ON THE NOA, INDICATE WHICH APPROVED ASSEMBLY IS
 PROPOSED
 SEE GENERAL LIMITATION #7, ENHANCE FASTENING FOR ZONES
 2 AND 3 TO BE SPECIFIED BY AN ARCHITECT, ENGINEER, OR
 REGISTERED ROOF CONSULTANT
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-03-13 Cont ID  
Sent By shill Date 2013-03-13 Time 15:04 Rev Time 0.00
Received By shill Date 2013-03-11 Time 09:37 Sent To  
Notes
2013-03-12 09:38:13GAVE TO SAMANTHA

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-01-28 Cont ID  
Sent By shill Date 2013-01-28 Time 16:56 Rev Time 0.00
Received By shill Date 2013-01-17 Time 15:18 Sent To  
Notes
2013-01-17 15:19:09SENT TO S HILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-12-11 Cont ID  
Sent By shill Date 2012-12-11 Time 16:11 Rev Time 0.00
Received By shill Date 2012-11-21 Time 10:19 Sent To  
Notes
2012-11-26 10:20:08SENT TO MISCELLANEOUS SHELF #1 FOR REVIEW. JG.