Plan Review Details - Permit 12110523
Plan Review Stops For Permit 12110523
Review Stop AD ADDRESSING
Rev No 2 Status N Date 2013-01-28 Cont ID  
Sent By shill Date 2013-01-28 Time 12:33 Rev Time 0.00
Received By shill Date   Time   Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2012-12-20 Cont ID  
Sent By shill Date 2012-12-20 Time 17:49 Rev Time 0.00
Received By shill Date 2012-12-20 Time 17:49 Sent To  
Notes
2012-12-20 17:49:37****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. REVISE FLOOR PLAN TO SHOW ROOM DESIGNATIONS. NOTE
 EXISTING CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE
 FOR BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING
 CANNOT BE REDUCED BY MORE THAN 5%.
  
 2ND REVIEW, NOT ENTIRELY ADDRESSED; PLEASE REVISE FLOOR
 PLAN TO NOTE EXISTING CONDITIONS (TYPE OF WINDOW),
 CLEAR OPENING SIZE FOR BEDROOMS, PROPOSED CLEAR OPENING
 SIZE FOR BEDROOMS.
  
 2. MINIMUM CODE ENVELOPE EFFICIENCY LEVELS SHALL BE MET
 FOR COMPONENTS BEING CHANGED PER FBC ENERGY
 CONSERVATION 2010 TABLE 101.4.1, ALSO SEE SECTION 402.
  
 2ND REVIEW, NOT ADDRESSED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-02-01 Cont ID  
Sent By shill Date 2013-02-01 Time 08:05 Rev Time 0.00
Received By shill Date 2013-02-01 Time 08:05 Sent To  
Notes
2013-02-01 08:05:31REDUCED SCOPE $$

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-01-28 Cont ID  
Sent By shill Date 2013-01-28 Time 12:33 Rev Time 0.00
Received By shill Date 2013-01-28 Time 12:33 Sent To  
Notes
2013-01-28 12:35:13****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. A CONTRACT AND NEW FLOOR PLAN WERE SUBMITTED BUT THE
 CONTRACT DOES NOT CORRELATE WITH THE FLOOR PLAN, 12
 OPENINGS SHOWN ON ONE, 11 OPENINGS SHOWN ON THE OTHER.
  
 2. PLEASE REVISE FLOOR PLAN AS PREVIOUSLY REQUESTED TO
 INCLUDE EXISTING WINDOW TYPE. THIS WAS SENT VIA EMAIL
 BUT NOT INCLUDED ON THE PLAN. AS RESUBMITTAL IS
 REQUIRED, PLEASE REVISE FLOOR PLAN.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-12-05 Cont ID  
Sent By shill Date 2012-12-05 Time 14:49 Rev Time 0.00
Received By shill Date 2012-12-05 Time 14:49 Sent To  
Notes
2012-12-05 14:50:18****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. REVISE FLOOR PLAN TO SHOW ROOM DESIGNATIONS. NOTE
 EXISTING CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE
 FOR BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING
 CANNOT BE REDUCED BY MORE THAN 5%.
  
 2. MINIMUM CODE ENVELOPE EFFICIENCY LEVELS SHALL BE MET
 FOR COMPONENTS BEING CHANGED PER FBC ENERGY
 CONSERVATION 2010 TABLE 101.4.1, ALSO SEE SECTION 402.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-12-20 Cont ID  
Sent By shill Date 2012-12-20 Time 17:55 Rev Time 0.00
Received By shill Date 2012-12-14 Time 10:19 Sent To  
Notes
2012-12-17 10:20:13SENT TO SAMANTHA'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-12-05 Cont ID  
Sent By shill Date 2012-12-05 Time 14:50 Rev Time 0.00
Received By shill Date 2012-11-20 Time 16:20 Sent To  
Notes
2012-11-20 16:20:41INCOMING SENT TO MISC BOX # 1.JW