Plan Review Details - Permit 12110413
Plan Review Stops For Permit 12110413
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-01-16 Cont ID  
Sent By rlecky Date 2013-01-16 Time 14:25 Rev Time 0.00
Received By rlecky Date 2013-01-16 Time 11:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-11-26 Cont ID  
Sent By rlecky Date 2012-11-26 Time 09:38 Rev Time 0.00
Received By rlecky Date 2012-11-26 Time 09:29 Sent To  
Notes
2012-11-26 09:38:4412110413
 4001 NORTH SHORE DRIVE
 SITE LIGHTING
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENT.
  
 PROVIDE A SIGNED AND SEALED ENGINEERING FOR THE WIND
 LOAD DESIGN FOR LIGHT POLES AND FIXTURES COMBINED.
 PROVIDE SOIL AND BURIAL DETAIL FOR THE LIGHT POLES.
 INDICATE THE EXPOSURE CATEGORY AND IMPORTANCE FACTOR.
 FBC 2010 1609, ASCE 7-10
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-01-16 Cont ID  
Sent By rlecky Date 2013-01-16 Time 14:25 Rev Time 0.00
Received By rlecky Date 2013-01-15 Time 10:04 Sent To  
Notes
2013-01-15 10:04:35TO ELECTRIC

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-11-26 Cont ID  
Sent By rlecky Date 2012-11-26 Time 09:38 Rev Time 0.00
Received By rlecky Date 2012-11-15 Time 10:43 Sent To  
Notes
2012-11-15 10:44:08TO ZONING
  

Review Stop Z ZONING
Rev No 1 Status P Date 2012-11-21 Cont ID  
Sent By mdekle Date 2012-11-21 Time   Rev Time 0.00
Received By mdekle Date 2012-11-21 Time   Sent To E
Notes
***NONE***