Plan Review Details - Permit 12110354
Plan Review Stops For Permit 12110354
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-11-19 Cont ID  
Sent By rlecky Date 2012-11-19 Time 13:05 Rev Time 0.00
Received By rlecky Date 2012-11-19 Time 13:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-11-19 Cont ID  
Sent By rlecky Date 2012-11-19 Time 09:02 Rev Time 0.00
Received By rlecky Date 2012-11-19 Time 08:32 Sent To  
Notes
2012-11-19 09:04:0212110354
 1023 N. DIXIE HWY.
 SERVICE UPGRADE
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 INDICATE THE FAULT CURRENT CAPABILITY OF THE SERVICE
 EQUIPMENT. NEC 110.9
 PROVIDE WIRE SIZES FOR EACH SERVICE. NEC T. 310.16
 THE SERVICE FEEDER IS UNDERSIZED BASED ON THE LOAD
 CALCULATION SUBMITTED. NEC 310.16
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
 VERIFY THE REQUIRED WORKING CLEARANCES AND DEDICATED
 WORKING SPACE HAS BEEN PROVIDED AT THE ELECTRICAL
 SERVICE. NEC 110.26, 240.24
 VERIFY THE ELECTRICAL SERVICE MAINS FOR THIS BUILDING
 ARE SIX OR LESS AND GROUPED IN ONE LOCATION.
 NEC 230.2, 230.71, 230.72
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-11-19 Cont ID  
Sent By rlecky Date 2012-11-19 Time 13:05 Rev Time 0.00
Received By rlecky Date 2012-11-19 Time 13:04 Sent To  
Notes
2012-11-19 13:05:08PLAN REVISED BY CONTRACTOR.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-11-19 Cont ID  
Sent By rlecky Date 2012-11-19 Time 09:04 Rev Time 0.00
Received By rlecky Date 2012-11-14 Time 11:24 Sent To  
Notes
2012-11-15 11:24:30UNDER 5 K ELECTRIC