| Plan Review Stops For Permit 12110343 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2012-12-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2012-12-27 |
Time |
08:41 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2012-12-27 |
Time |
08:41 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2012-12-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2012-12-18 |
Time |
15:06 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2012-12-18 |
Time |
15:06 |
Sent To |
|
|
| Notes |
| 2012-12-18 15:13:04 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. ORIGINAL PERMIT FOR THIS BUILDING WAS FOR A NON | | | COMBUSTIBLE BUILDING, BASED ON THE PLANS PROVIDED FROM | | | 1998. ENGINEER IS NOW CHANGIN THE BUILDING TYPE TO TYPE | | | III, WHICH REQUIRES NON COMBUSTIBLE WALLS BUT ALLOWS | | | COMBUSTIBLE ROOF AND INTERIOR WALLS. | | | | | | IN ORDER TO CHANGE THE BUILDING TYPE TO A TYPE LESS | | | STRINGENT THAN ORIGINALLY CONSTRUCTED, CODE COMPLIANCE | | | FOR THE NEW BUILDING TYPE MUST BE SHOWN. SEE FBC TABLES | | | 601, 602, FBC EXISTING BUIDLING 601.2. | | | | | | IT APPEARS THAT THE SIMPLEST RESOLUTION WOULD BE TO | | | ALLOW THE BUILDING TYPE TO REMAIN NON COMBUSTIBLE (TYPE | | | I OR TYPE II) AND TO REVISE THE WALL DETAILS TO BE FRT | | | OR METAL STUD. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2012-12-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2012-12-18 |
Time |
07:56 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2012-12-18 |
Time |
07:56 |
Sent To |
|
|
| Notes |
| 2012-12-18 07:59:32 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. PLANS SHOW BUILDING AS A TYPE IV. THIS IS HEAVY | | | TIMBER. IT APPEARS THAT ENGINEER USED THE BUILDING TYPE | | | WHICH WAS ON THE PLAN FROM 1998. THE CODE HAS CHANGED A | | | NUMBER OF TIMES SINCE THEN. PLAN STATES THAT, AS A 1998 | | | TYPE IV, THIS IS A NON COMBUSTIBLE BUILDING. | | | | | | PLEASE SEE FBC CHAPTER 6 AND SELECT AN APPROPRIATE | | | BUILDING TYPE. DETAILS FOR THE NEW PARTITIONS SHOW WOOD | | | FRAMING. PLEASE SEE FBC 602.3, TABLE 601, AND 603. | | | | | | ***IT IS POSSIBLE THAT A PERMIT CAN BE ISSUED WITH | | | PROVISO THAT PLANS BE REVISED TO CORRECTLY REFLECT | | | BUILDING TYPE, OR TO OFFICIALLY CHANGE THE BUILDING | | | TYPE, AND NEW DETAILS BE SUBMITTED.*** | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2012-11-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2012-11-19 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2012-11-19 |
Time |
13:40 |
Sent To |
FIRE |
|
| Notes |
| 2012-11-19 13:43:22 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. PROVIDE A CODE SUMMARY - PROPOSED OCCUPANCY | | | CLASSIFICATION, PREVIOUS OCCUPANCY, BUILDING SIZE, | | | TYPE, OTHER OCCUPANCIES IN BUILDING, FIRE SPRINKLERS OR | | | UNSPRINKLERED, ETC. IT IS NOT CLEAR WHETHER OR NOT | | | COMBUSTIBLE MATERIALS ARE ALLOWED AS NO INFORMATION | | | PROVIDED REGARDING BUILDING TYPE, FBC CHAPTER 5. | | | | | | 2. PROVIDE DIMENSIONS ON THE PLAN - NONE PROVIDED. | | | | | | 3. PLAN SHOWS "WORKSHOP." PROVIDE DETAILED INFORMATION | | | REGARDING THE "WORKSHOP" AND ACTIVITY. | | | | | | 4. THE DOORS TO BOTH OFFICES LACK THE MANEUVERING | | | CLEARANCE REQUIRED BY FBC 2010 ACCESSIBILITY FBC | | | 404.2.4. IT IS NOT CLEAR WHICH WALLS ARE NEW, WHICH ARE | | | PROPOSED, AND WHETHER ALL EXISTING IMPROVEMENTS WERE | | | PERMITTED. | | | | | | REVISE PLAN TO SHOW SHOW EXISTING AND PROPOSED. NO | | | LEGEND PROVIDED. PROVIDE A COPY OF THE CONTRACT FOR | | | THIS JOB WITH COST BREAKDOWNS. ADDITIONAL WORK MAY BE | | | REQUIRED, SEE FBC 2010 ACCESSIBILITY 202.4. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
N |
Date |
2012-11-27 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-11-27 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-11-27 |
Time |
09:42 |
Sent To |
|
|
| Notes |
| 2012-11-27 09:45:35 | NO ELECTRICAL WORK PROPOSED. RL |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2012-12-27 |
|
|
Cont ID |
|
| Sent By |
rferguso |
Date |
2012-12-27 |
Time |
12:56 |
Rev Time |
0.00 |
| Received By |
rferguso |
Date |
2012-12-27 |
Time |
12:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2012-12-13 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2012-12-13 |
Time |
13:01 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2012-12-13 |
Time |
12:53 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2012-11-26 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2012-11-26 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2012-11-26 |
Time |
09:50 |
Sent To |
E |
|
| Notes |
| 2012-11-26 09:57:42 | 2658 ELECTRONICS WAY | | | PERMIT #12110343 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | THE ADDRESS PROVIDED ON THE PLANS (2656) DOES NOT MATCH | | | THE ADDRESS (2658) PROVIDED ON THE PERMIT APPLICATION. | | | | | | ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO | | | THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION | | | DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING | | | SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR | | | AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL | | | HAVE "NO SMOKING" SIGNS POSTED. | | | | | | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | | MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE | | | ALARM SYSTEM. | | | | | | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | | | | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY | | | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING | | | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM | | | WWW.KNOXBOX.COM. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2012-12-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2012-12-27 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2012-12-26 |
Time |
14:52 |
Sent To |
|
|
| Notes |
| 2012-12-27 08:42:23 | 12/27 TO WJ DESK | | | | | 2012-12-26 14:53:22 | GAVE TO SAMANTHA |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2012-12-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2012-12-18 |
Time |
15:30 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2012-12-18 |
Time |
15:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2012-12-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2012-12-18 |
Time |
08:00 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2012-12-13 |
Time |
12:22 |
Sent To |
|
|
| Notes |
| 2012-12-13 12:22:49 | TO FIRE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2012-11-27 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-11-27 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-11-13 |
Time |
09:23 |
Sent To |
|
|
| Notes |
| 2012-11-19 13:43:49 | 11/19 TO FIRE | | | | | 2012-11-14 09:25:59 | BUILDING<5K |
|
|