| Plan Review Stops For Permit 12110274 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2013-04-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2013-04-04 |
Time |
11:32 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2013-04-04 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2013-04-04 11:30:34 | BUILDING PLAN REVIEW | | | PERMIT: 12110274 | | | ADD: 3401 PARKER AVE RESTROOMS ONLY!!!!! | | | CONT: HEDRICK BROTHERS | | | CONTACT: DON JONES | | | TEL: (561)689-8880 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | RESTROOMS ONLY !!! SEE PERMIT # 12110276 ?WATER FEATURE | | | DEC. 07/ 2012 | | | ACTION: BUILDING PROVISO | | | | | | 1) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS | | | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | 2) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.41 COMPONENTS & CLADDING, FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) | | | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT | | | WILL REQUIRE PRODUCT APPROVALS: | | | (31)(A) EXTERIOR DOORS. | | | (C) WALL LOUVERS | | | (D) ROOFING PRODUCTS AND ASSEMBLIES | | | | | | | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2012-12-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2012-12-07 |
Time |
09:29 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2012-12-07 |
Time |
09:29 |
Sent To |
|
|
| Notes |
| 2012-12-07 10:20:14 | BUILDING PLAN REVIEW | | | PERMIT: 12110274 | | | ADD: 3401 PARKER AVE RESTROOMS ONLY!!!!! | | | CONT: HEDRICK BROTHERS | | | CONTACT: DON JONES | | | TEL: (561)689-8880 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW- RESTROOMS ONLY !!! | | | DEC. 07/ 2012 | | | ACTION: DENIED | | | | | | 1) THE PTS-2 SHEET FOUNDATION NOTE # 4 INDICATES THERE | | | TO BE A SOILS REPORT SUBMITTED. 2010 FBC-B 1803.1 | | | GENERAL. | | | GEOTECHNICAL INVESTIGATIONS SHALL BE CONDUCTED IN | | | ACCORDANCE WITH SECTION 1803.2 AND REPORTED IN | | | ACCORDANCE WITH SECTION 1803.6. WHERE REQUIRED BY THE | | | BUILDING OFFICIAL OR WHERE GEOTECHNICAL INVESTIGATIONS | | | INVOLVE IN-SITU TESTING, LABORATORY TESTING OR | | | ENGINEERING CALCULATIONS, SUCH INVESTIGATIONS SHALL BE | | | CONDUCTED BY A REGISTERED DESIGN PROFESSIONAL. | | | | | | 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS | | | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | 3) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.41 COMPONENTS & CLADDING, FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) | | | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT | | | WILL REQUIRE PRODUCT APPROVALS: | | | (31)(A) EXTERIOR DOORS. | | | (C) WALL LOUVERS | | | (D) ROOFING PRODUCTS AND ASSEMBLIES | | | | | | NOTE, THE PRESSURES FOR COMPONENTS & CLADDING ARE OK! | | | IF THE CONTRACTOR ELECTS NOT SUBMIT PRODUCT APPROVALS | | | BEFORE THE TIME OF PERMIT ISSUANCE THEN THEY WILL BE | | | CONSIDERED REVISIONS AND ASSOCIATED REVIEWS AND FEES | | | WILL OCCUR. A WRITTEN RESPONCE INDICATING PRODUCT | | | APPROVALS WOULD BE SUBMITTED LATER WOULD PROVIDE AS | | | WRITTEN NOTICE OF YOUR INTENT. | | | | | | 4) THE INTERACTIVE WATER FEATURES SHOULD BE PULLED | | | UNDER A SEPERATE PERMIT . THE CONTRACTOR WILL NEED TO | | | COME IN AND APPLY FOR A SEPERATE PERMIT, PLEASE PULL | | | THE ASSOCIATED VALUE FOR WATER FEATURE PERMIT OUT OF | | | THE RETROOM PERMIT VALUE, THANK YOU. THIS WILL PROVIDE | | | THE CONTRACTOR WITH THE CORRECT INSPECTION CODES FOR | | | THIS PERMIT . | | | IT IS OK TO HAVE BOTH THE RESTROOMS AND INTERACTIVE | | | WATER FEATURE WITHIN THE SAME PLANS. | | | | | | 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | CONSTRUCTION SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF | | | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 | | | | | | REVIEW FOR INTERACTIVE WATER FEATURE | | | | | | 1) SD 1.05 THE BUTTERFLY IS SHOWN WITH TWO DRAINS, | | | SHEET SD 1.06 INDICATES THE FOUNDATION FOR THE POLE TO | | | SUPPORT THIS STRUCTURE AND SD 1.08 DETAIL # 1 INDICATES | | | THE TWO MAIN DRAINS BOXES BUT THE SIZE OF THE | | | FOUNDATION NOR IS THE SIZE OR SPACING OF THE REBAR | | | PROVIDED. 107.1.2 ADDITIONAL INFORMATION REQUIRED. | | | | | | 2) SD 1.08 INDICATES THE USE OF A SPECIAL INSPECTOR | | | WHILE THE AREA UNDER THE SLAB IS BEING COMPACTED, | | | PLEASE CONTACT CONTACT KEN CONRAD | | | TEL: 561-805-6666 | | | E-MAIL: [email protected] | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | CONSTRUCTION SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2013-05-02 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-05-02 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-05-02 |
Time |
15:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2012-11-20 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-11-20 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-11-20 |
Time |
09:42 |
Sent To |
|
|
| Notes |
| 2012-11-20 10:55:12 | | | | THE FOLLOWING CODE REQUIREMENT WAS NOTED ON THE PLAN. | | | | | | | | | ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH | | | GFCI PROTECTION. NEC 422.52 | | | | | | ROBERT LECKY | | | ELECTRIC PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2013-05-01 |
|
|
Cont ID |
|
| Sent By |
MGONZALE |
Date |
2013-05-01 |
Time |
|
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2013-05-01 |
Time |
|
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2012-12-31 |
|
|
Cont ID |
|
| Sent By |
Mgonzale |
Date |
2012-12-31 |
Time |
|
Rev Time |
0.25 |
| Received By |
mgonzale |
Date |
2012-12-31 |
Time |
|
Sent To |
I |
|
| Notes |
| 2012-12-31 07:19:26 | #1 LOCATE AND SHOW ON PLAN ALL EXISTING CITY OF WPB | | | UTILITIES. | | | | | | #2 SHOW DOMESTIC WATER METER AND BACKFLOW, | | | | | | #3 CITY STANDARD DETAIL MUST BE INCLUDED. | | | | | | #4 SHOW SEWER SERVICE LATERAL AND SERVICE CLEAN-OUT | | | LOCATION. | | | | | | MANUEL JULIAN GONZALEZ | | | ENGINEERING PROJECT COORDINATOR | | | ENGINEERING SERVICES DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | MOBILE: (561) 644-7301 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2013-04-01 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2013-04-01 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2013-04-01 |
Time |
13:12 |
Sent To |
|
|
| Notes |
| 2013-04-01 13:25:21 | NOTE: COULD ONLY LOCATE ONE SET OF PLANS TO BE STAMPED. | | | | | | UPDATE: SECOND SET STAMPED APRIL 2, 2013. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2012-11-19 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2012-11-19 |
Time |
14:39 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2012-11-19 |
Time |
14:26 |
Sent To |
|
|
| Notes |
| 2012-11-19 14:39:37 | 3401 PARKER AVENUE - RESTROOM & WATER FEATURE | | | PERMIT #12110274 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | NO CIVIL DRAWINGS HAVE BEEN SUBMITTED FOR THE ENTIRE | | | SITE SHOWING WATER MAINS, FIRE HYDRANT LOCATIONS, FIRE | | | DEPARTMENT ACCESS ROADS, ETC. | | | | | | A FIRE DEPARTMENT ACCESS ROAD SHALL EXTEND TO WITHIN 50 | | | FEET OF AT LEAST ONE EXTERIOR DOOR THAT CAN BE OPENED | | | FROM THE OUTSIDE AND THAT PROVIDES ACCESS TO THE | | | INTERIOR OF THE BUILDING. | | | | | | PROVIDE A NAME, ADDRESS OR LETTER ON THE BUILDING SO | | | THE LOCATION CAN BE IDENTIFIED BY EMERGENCY RESPONDERS. | | | NUMBERS/LETTERS SHALL BE AT LEAST SIX-INCHES IN HEIGHT | | | WITH 1-INCH STROKE AND SHALL CONTRAST THE BACKGROUND. | | | | | | STRUCTURES WITH LIGHT FRAME ROOF TRUSS CONSTRUCTION | | | SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO THE | | | BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS | | | 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED | | | REFLECTIVE COLOR AND BEAR THE LETTER R. | | | | | | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | | | | INDICATE THE LOCATION OF THE NEAREST FIRE HYDRANT(S). | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2013-05-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2013-05-29 |
Time |
11:00 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2013-05-29 |
Time |
11:00 |
Sent To |
|
|
| Notes |
| 2013-05-29 11:01:42 | P B CTY IMPACT FEE ASSESSMENT | | | NO FEES DUE, WPB CITY PARK | | | W M SWOOPE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2013-05-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-05-03 |
Time |
08:30 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-03-11 |
Time |
13:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-01-14 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2012-12-31 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2012-11-09 |
Time |
16:12 |
Sent To |
|
|
| Notes |
| 2012-11-09 16:14:44 | INCOMING SENT TO C-27 BOX. JW |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
N |
Date |
2013-05-30 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2013-05-30 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2013-05-30 |
Time |
10:47 |
Sent To |
|
|
| Notes |
| 2013-05-30 10:47:59 | IMPACT FEE OK WM SWOOPE |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2013-04-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2013-04-04 |
Time |
11:34 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2013-04-04 |
Time |
11:33 |
Sent To |
|
|
| Notes |
| 2013-04-04 11:33:55 | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | CONSTRUCTION SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2012-12-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2012-12-07 |
Time |
09:29 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2012-12-07 |
Time |
09:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2012-12-11 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2012-12-11 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2012-12-11 |
Time |
14:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2013-04-01 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2013-04-01 |
Time |
12:45 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2013-04-01 |
Time |
10:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2012-12-10 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2012-12-10 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2012-12-05 |
Time |
14:13 |
Sent To |
|
|
| Notes |
| 2012-12-05 15:30:43 | FBC 2010 ACCESSIBILITY CODE | | | FBC 2010 PLUMBING REVIEW #1 | | | DENIED: | | | | | | 1. SHEET PTA-1 THE OCCUPANCY IS LISTED AS ASSEMBLY WITH | | | 69 OCCUPANTS. SEPARATE FACILITIES ARE REQUIRED FOR MEN | | | AND WOMEN. | | | FBC PLUMBING 403.2 | | | | | | 2. SHEET PTA-1, SD-1.02: THE MENS ACCESSIBLE STALL WILL | | | BE REQUIRED TO BE A MINIMUM OF 7'-1" WIDE TO ACHIEVE | | | THE REQUIRED 5' CLEAR SPACE FOR THE WATER CLOSET | | | FBC ACCESSIBILITY CODE 2010 604.3.1 A 60" CLEAR SPACE | | | IS REQUIRED FOR WATER CLOSET FROM SIDE WALL. | | | FBC ACCESSIBILITY CODE 2010 604.3.2 THE LAVATORY WILL | | | NOT BE PERMITTED IN THE 60" SPACE. | | | | | | 3. SHEET PTA-1, SD-1.02: AN ACCESSIBLE WOMENS STALL | | | WILL BE REQUIRED. | | | FBC ACCESSIBILITY CODE 2010 213.3.1 | | | | | | 4. SHEET PTP-02 , SD-1.09 THE DRAINAGE CONNECTION FOR | | | THE FILTER BACKWASH IS NOT SHOWN ON THE PTP-02 SANITARY | | | DRAWING. THE BACKWASH WILL BE REQUIRED TO DRAIN TO THE | | | SANITARY SYSTEM. | | | CITY ORD. 90-203 | | | | | | 5. SHEET SD-1.05 (M) MAKE UP WATER SHALL BE PROTECTED | | | FROM BACKFLOW. | | | PLUMBING 608.3 | | | | | | 6. SHEET SD-1.10 THE AIR GAP DETAIL IS NOT A PROPER AIR | | | GAP. THE DETAIL ALSO STATES THAT THE AIR GAP IS TO THE | | | STORM SEWER. | | | FBC 424.1.6.5.15 | | | PLUMBING 202 AIR GAP (DRAINAGE SYSTEM). THE | | | UNOBSTRUCTED VERTICAL DISTANCE THROUGH THE FREE | | | ATMOSPHERE BETWEEN THE OUTLET OF THE WASTE PIPE AND THE | | | FLOOD LEVEL RIM OF THE RECEPTACLE INTO WHICH THE WASTE | | | PIPE IS DISCHARGING. | | | | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2013-04-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2013-04-04 |
Time |
11:32 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2013-04-04 |
Time |
11:32 |
Sent To |
|
|
| Notes |
| 2013-04-04 11:33:03 | BUILDING PLAN REVIEW | | | PERMIT: 12110274 | | | ADD: 3401 PARKER AVE RESTROOMS ONLY!!!!! | | | CONT: HEDRICK BROTHERS | | | CONTACT: DON JONES | | | TEL: (561)689-8880 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | RESTROOMS ONLY !!! SEE PERMIT # 12110276 ?WATER FEATURE | | | DEC. 07/ 2012 | | | ACTION: BUILDING PROVISO | | | | | | 1) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS | | | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | 2) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.41 COMPONENTS & CLADDING, FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) | | | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT | | | WILL REQUIRE PRODUCT APPROVALS: | | | (31)(D) ROOFING PRODUCTS AND ASSEMBLIES | | | | | | | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2013-04-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2013-04-04 |
Time |
11:31 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2013-04-04 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2013-04-04 11:31:24 | ROOFING | | | BUILDING PLAN REVIEW | | | PERMIT: 12110274 | | | ADD: 3401 PARKER AVE RESTROOMS ONLY!!!!! | | | CONT: HEDRICK BROTHERS | | | CONTACT: DON JONES | | | TEL: (561)689-8880 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | RESTROOMS ONLY !!! SEE PERMIT # 12110276 ?WATER FEATURE | | | DEC. 07/ 2012 | | | ACTION: BUILDING PROVISO | | | | | | 1) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS | | | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | 2) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.41 COMPONENTS & CLADDING, FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) | | | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT | | | WILL REQUIRE PRODUCT APPROVALS: | | | (31)(D) ROOFING PRODUCTS AND ASSEMBLIES | | | | | | | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2013-05-09 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2013-05-09 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2013-05-09 |
Time |
09:13 |
Sent To |
|
|
| Notes |
| 2013-05-09 09:13:31 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 05.09.2013 | | | PERMIT NO.: 12110274 | | | ADDRESS: 3401 PARKER AVENUE | | | CONTRACTOR/CONTACT: DON JONES ? HEDRICK BROTHERS | | | CONSTRUCTION CO. | | | TELEPHONE NO.: 561.689.8880 | | | SCOPE OF REVIEW: NEW RESTROOM BUILDING. | | | ___________________________________________ | | | | | | REVIEW STATUS: PASSED WITH PROVISOS | | | ___________________________________________ | | | | | | THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING | | | PROVISOS: | | | | | | 1. PERMIT IS ISSUED FOR THE RESTROOM BUILDING ONLY. A | | | SEPARATE PERMIT APPLICATION SHALL BE SUBMITTED FOR ALL | | | OTHER SITE IMPROVEMENTS, SUCH AS FENCING, BIKE RACKS, | | | BENCHES, ETC. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN ROACH, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | PHONE: 561.822.1448 | | | FAX: 561.822.1460 | | | | | | EMAIL: [email protected] | | | | | | WWW.WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2013-04-01 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2013-04-01 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2013-03-14 |
Time |
18:24 |
Sent To |
|
|
| Notes |
| 2013-04-01 15:21:52 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 12.17.2012 | | | PERMIT NO.: 12110274 | | | ADDRESS: 3401 PARKER AVENUE | | | CONTRACTOR/CONTACT: DON JONES ? HEDRICK BROTHERS | | | CONSTRUCTION CO. | | | TELEPHONE NO.: 561.689.8880 | | | SCOPE OF REVIEW: NEW WATER FEATURE AND RESTROOM | | | BUILDING. | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. AS THE SUBJECT FACILITIES ARE TO BE TURNED OVER, | | | OPERATED, AND MAINTAINED BY THE CITY UPON COMPLETION OF | | | THE PUBLIC PARK, THE FOLLOWING COMMENTS WERE MADE BY | | | JACKSON LOEBIG, THE CITY?S O&M SUPERINTENDENT ? PUMPING | | | OPERATIONS: | | | | | | A. REPEAT COMMENT: THE PVC PIPE SPEC IS FOR SCH40 PVC, | | | IT IS OUR RECOMMENDATION THAT THEY USE SCH80, | | | ESPECIALLY ON THE LARGER DIAMETER PIPE (THE FOUNTAIN AT | | | SOUTH OLIVE IS SCH80.) | | | | | | B. REPEAT COMMENT: THE SPEC FOR FASTENERS IS S/S 304; | | | IT IS OUR RECOMMENDATION THAT THIS BE S/S 316. THE HIGH | | | CHLORINE RESIDUAL REQUIRED BY THE DEPARTMENT OF HEALTH | | | (6 - 8 PARTS) IS AGGRESSIVE. | | | | | | C. FOR QUESTIONS/COMMENTS REGARDING THESE ITEMS, PLEASE | | | CONTACT: | | | | | | JACKSON LOEBIG | | | O&M SUPERINTENDENT | | | PUMPING OPERATIONS | | | CITY OF WEST PALM BEACH | | | 1045 CHARLOTTE AVENUE | | | WEST PALM BEACH, 33401 | | | TEL: 561 822-2068 | | | CELL: 561 951-7656 | | | [email protected] | | | | | | 2. CHRISTINE THROWER, DIRECTOR OF PARKS & RECREATION, | | | HAS POSED THE FOLLOWING QUESTIONS IN LIGHT OF THE | | | MODIFICATIONS THAT WERE MADE FROM THE FIRST SUBMITTAL: | | | | | | A. WHY WAS THE BATHROOM CONFIGURATION CHANGED TO | | | GENDER-SPECIFIC, WHICH ULTIMATELY RESULTED IN THE LOSS | | | OF TWO (2) FACILITIES? | | | | | | B. WHY WAS THE ROOFING MATERIAL CHANGED TO S-TILE? THE | | | STANDING SEAM ROOF IS PREFERRED ON THE BASIS OF | | | LONG-TERM MAINTENANCE OBLICATION. | | | | | | PLEASE CLARIFY THE ABOVE QUESTIONS. FOR | | | QUESTIONS/COMMENTS REGARDING THESE ITEMS, YOU MAY | | | CONTACT: | | | | | | CHRISTINE THROWER, DIRECTOR | | | CITY OF WEST PALM BEACH | | | DEPARTMENT OF PARKS & RECREATION | | | P.O. BOX 3366 | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FL 33402 | | | PHONE: 561-804-4900 | | | DIRECT: 561-804-4903 | | | FAX - 561-822-1560 | | | [email protected] | | | | | | 3. IS ALL FURNITURE, ETC. INCLUDED IN THE SCOPE OF THIS | | | PERMIT? IF SO, PLEASE NOTE THE FOLLOWING: | | | | | | A. THE PROPOSED BIKE RACK SHALL CONFORM TO THE MINIMUM | | | CITY REQUIREMENTS. PLEASE EMAIL ME AT [email protected] | | | FOR A COPY OF THE APPROVED BIKE RACK DESIGNS. | | | | | | B. PLEASE PROVIDE A DETAIL OF THE PROPOSED BENCHES. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN ROACH, SENIOR PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | PHONE: 561.822.1435 | | | FAX: 561.822.1460 | | | | | | EMAIL: [email protected] | | | | | | WWW.WPB.ORG | | | | | | 11/15/12 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2012-12-17 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2012-12-17 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2012-11-28 |
Time |
10:57 |
Sent To |
|
|
| Notes |
| 2012-12-17 11:43:22 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 12.17.2012 | | | PERMIT NO.: 12110274 | | | ADDRESS: 3401 PARKER AVENUE | | | CONTRACTOR/CONTACT: DON JONES ? HEDRICK BROTHERS | | | CONSTRUCTION CO. | | | TELEPHONE NO.: 561.689.8880 | | | SCOPE OF REVIEW: NEW WATER FEATURE AND RESTROOM | | | BUILDING. | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. PLEASE PROVIDE TWO (2) COPIES OF A CURRENT AND | | | ACCURATE SURVEY. | | | | | | 2. AS THE SUBJECT FACILITIES ARE TO BE TURNED OVER, | | | OPERATED, AND MAINTAINED BY THE CITY UPON COMPLETION OF | | | THE PUBLIC PARK, THE FOLLOWING COMMENTS WERE MADE BY | | | JACKSON LOEBIG, THE CITY?S O&M SUPERINTENDENT ? PUMPING | | | OPERATIONS: | | | | | | A. THE PVC PIPE SPEC IS FOR SCH40 PVC, IT IS OUR | | | RECOMMENDATION THAT THEY USE SCH80, ESPECIALLY ON THE | | | LARGER DIAMETER PIPE (THE FOUNTAIN AT SOUTH OLIVE IS | | | SCH80.) | | | | | | B. THE SPEC FOR FASTENERS IS S/S 304; IT IS OUR | | | RECOMMENDATION THAT THIS BE S/S 316. THE HIGH CHLORINE | | | RESIDUAL REQUIRED BY THE DEPARTMENT OF HEALTH (6 - 8 | | | PARTS) IS AGGRESSIVE. | | | | | | C. A SECOND PUMP WAS SPEC'D AT 208 VOLT WHEN THE LARGE | | | PUMP IS ALREADY REQUIRING 460/480 THREE PHASE TO THE | | | SITE. THE 208 VOLT PUMP WILL REQUIRE AN ADDITIONAL | | | TRANSFORMER AND LARGER WIRING THAN A SIMILAR PUMP AT | | | 460/480. | | | | | | D. FOR QUESTIONS/COMMENTS REGARDING THESE ITEMS, PLEASE | | | CONTACT: | | | | | | JACKSON LOEBIG | | | O&M SUPERINTENDENT | | | PUMPING OPERATIONS | | | CITY OF WEST PALM BEACH | | | 1045 CHARLOTTE AVENUE | | | WEST PALM BEACH, 33401 | | | TEL: 561 822-2068 | | | CELL: 561 951-7656 | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN ROACH, SENIOR PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | PHONE: 561.822.1435 | | | FAX: 561.822.1460 | | | | | | EMAIL: [email protected] | | | | | | WWW.WPB.ORG | | | | | 2012-11-15 14:07:19 | 11/15/12 |
|
|