Plan Review Details - Permit 12110164
Plan Review Stops For Permit 12110164
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2012-12-03 Cont ID  
Sent By lwagner Date 2012-12-03 Time 09:46 Rev Time 0.00
Received By lwagner Date 2012-12-03 Time 09:46 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2012-11-09 Cont ID  
Sent By lwagner Date 2012-11-09 Time 09:08 Rev Time 0.00
Received By lwagner Date 2012-11-08 Time 10:31 Sent To  
Notes
2012-11-09 09:13:01FBC 2010 FUEL GAS 2010 REVIEW #1
 DENIED:
  
 NOT ENOUGH INFORMATION TO REVIEW. PLEASE SEE CODE
 SECTION 401.4 AND APPLICATION CHECKLIST BELOW:
  
 401.4 ADDITIONAL APPLIANCES.
 WHERE AN ADDITIONAL APPLIANCE IS TO BE SERVED, THE
 EXISTING PIPING SHALL BE CHECKED TO DETERMINE IF IT HAS
 ADEQUATE CAPACITY FOR ALL APPLIANCES SERVED. IF
 INADEQUATE, THE EXISTING SYSTEM SHALL BE ENLARGED AS
 REQUIRED OR SEPARATE PIPING OF ADEQUATE CAPACITY SHALL
 BE PROVIDED.
  
 GAS PERMIT APPLICATION REQUIREMENTS:
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2010 FUEL GAS.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2007 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35)
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2007 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4)
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2007 FUEL GAS CODE SEC. 304
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2007
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2007 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2007 FUEL GAS SEC. 402.2
  
 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS
 ABOVE OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF
 THE TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS
 BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED
 PER NFPA 58 SECTION 3-2.2.7(H).
  
 12. EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE TO BE BELOW
 CEILING. MANUAL SHUT OFF VALVE TO BE UPSTREAM. UNION TO
 BE DOWN STREAM OF MANUAL VALVE.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status P Date 2012-12-03 Cont ID  
Sent By lwagner Date 2012-12-03 Time 09:46 Rev Time 0.00
Received By lwagner Date 2012-11-26 Time 16:38 Sent To  
Notes
2012-11-27 16:38:47UNDER 5 K PLUMBING

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-11-09 Cont ID  
Sent By lwagner Date 2012-11-09 Time 09:13 Rev Time 0.00
Received By lwagner Date 2012-11-06 Time 10:21 Sent To  
Notes
2012-11-07 10:21:49UNDER 5 K PLUMBING