| 2013-02-26 14:04:01 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2010 |
| | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| | |
| | COMMENTS FROM PREVIOUS LIST: |
| | |
| | 1. FOR THE SHUTTERS, COMPLETE THE SAMPLE INSTALLATION |
| | SCHEDULE OR PROVIDE ALL INFORMATION TO SHOW CODE |
| | COMPLIANCE IN ANOTHER FORMAT, FBC*106, FBC R301, |
| | FBC1609. TWO SETS REQUIRED. THIS FORM IS AVAILABLE IN |
| | THE LOBBY OR ON THE INTERNET AT |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ |
| | INSTALLATION.PDF |
| | |
| | 2ND REVIEW - ANCHOR SPACING WAS LEFT BLANK. PLEASE |
| | COMPLETE. |
| | |
| | 2. PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS WILL |
| | BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH THE |
| | INSTALLATION SCHEDULE, ITEM 2 ABOVE. FBC R301, FBC1609, |
| | FBC*106. |
| | |
| | 2ND REVIEW, NOT ADDRESSED. |
| | |
| | 3. FOR THE WINDOWS, PROVIDE A FLOOR PLAN SHOWING: |
| | WINDOW LOCATIONS, SIZES, WINDOW TYPE, ROOM |
| | DESIGNATIONS. NOTE EXISTING CONDITIONS (TYPE OF WINDOW) |
| | AND OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB 604.1. |
| | THE CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%. |
| | |
| | HORIZONTAL ROLLER WINDOWS PROPOSED FOR A 36X72 WINDOW. |
| | SEE PRODUCT APPROVAL, 63" IS THE MAX ALLOWED FOR THIS |
| | WINDOW. A 36" WIDE HORZONTAL ROLLER WINDOW WOULD NOT |
| | MEET EMERGENCY EGRESS REQUIREMENTS. NOT ENOUGH |
| | INFORMATION PROVIDED TO DETERMINE CODE COMPLIANCE. |
| | |
| | 4. SHOW THE EMERGENCY MEANS OF ESCAPE, FBC R310.4. |
| | |
| | NOT ADDRESSED. OUR RECORDS SHOW THAT THERE ARE OTHER |
| | SHUTTERS INSTALLED ON THIS STRUCTURE. PLEASE INCLUDE |
| | EMERGENCY MEANS OF ESCAPE ON THE FLOOR PLAN. |
| | |
| | NEW COMMENT: |
| | |
| | 5. TWO SETS OF ALL DOCUMENTS REQUIRED FOR PERMIT |
| | ISSUANCE FBC 107. |
| | |