Plan Review Details - Permit 12100900
Plan Review Stops For Permit 12100900
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-02-21 Cont ID  
Sent By jwitmer Date 2013-02-21 Time 10:01 Rev Time 0.00
Received By jwitmer Date 2013-02-21 Time 10:00 Sent To  
Notes
2013-02-21 10:28:14BUILDING PLAN REVIEW
 PERMIT: 12100900
 ADD: 4200 BROADWAY
 CONT: DI PASGVA CONSTRUCTION
 TEL: (561)275-2406
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 FEB. 21/2013
 BUILDING PROVISO:
  
 DRINKING FOUNTAIN TO COMPLY WITH;
 1) 2010 FL ACCESSIBILITY CODE 602.4 SPOUT HEIGHT. SPOUT
 OUTLETS SHALL BE 36 INCHES (915 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 2) 2010 FL ACCESSIBILITY CODE 602.7 DRINKING FOUNTAINS
 FOR STANDING PERSONS. SPOUT OUTLETS OF DRINKING
 FOUNTAINS FOR STANDING PERSONS SHALL BE 38 INCHES (965
 MM) MINIMUM AND 43 INCHES (1090 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. NO CUP DISPENSOR!!!!!!
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-11-08 Cont ID  
Sent By jwitmer Date 2012-11-08 Time 11:24 Rev Time 0.00
Received By jwitmer Date 2012-11-08 Time 11:14 Sent To  
Notes
2012-11-08 11:44:10BUILDING PLAN REVIEW
 PERMIT: 12100900
 ADD: 4200 BROADWAY
 CONT: DI PASGVA CONSTRUCTION
 TEL: (561)275-2406
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 NOV. 08/ 2012
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES THE CONTRACT VALUE
 OF $20,000. THE BUILDING NEEDS TO BE BROUGHT UP TO CODE
 FOR ACCESSIBILITY WITH AN ACCESSIBLE ENTRANCE AND TO
 ALTERED AREAS. A COST OF 20% OF THE CONTRACT VALUE OR
 $4,000.00 SHOULD BE ITEMIZED WHERE THESE MONIES WILL BE
 SPENT IN ACCESSILTY UPGRADES. SEE HOW THE FUNDS ARE TO
 BE SPENT.
  
 2010 FBC-ACCESSIBILTY 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 2010 FBC- ACCESSIBILTY 202.4.2 ACCESSIBLE FEATURES IN
 THE EVENT OF DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS
  
 1A) THE FRONT ENTRY DOORS DO NOT HAVE THE REQUIRED 18"
 LATCH SIDE OF THE DOOR AS REQUIED UNDER 2010
 FBC-ACCESSIBILITY FIGURE 404.2.4.1 (A).
  
 1B) DOOR INTO TOLIET ROOM # 2 ONLY HAS ONE FOOT LATCH
 SIDE OF DOOR, SEE 2010 FBC-ACCESSIBILITY FIGURE
 404.2.4.1 (A).
  
 1C) PLANS ARE NOT INDICATING IFTHE FRONT ENTRY IS AN
 ACCESSIBLE ENTRY? 2010 FBC ACCESSIBILTY 402.2
 COMPONENTS.
 ACCESSIBLE ROUTES SHALL CONSIST OF ONE OR MORE OF THE
 FOLLOWING COMPONENTS: WALKING SURFACES WITH A RUNNING
 SLOPE NOT STEEPER THAN 1:20, DOORWAYS, RAMPS, CURB
 RAMPS EXCLUDING THE FLARED SIDES, ELEVATORS, AND
 PLATFORM LIFTS. ALL COMPONENTS OF AN ACCESSIBLE ROUTE
 SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS OF
 CHAPTER 4 AND 208.3.1.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-02-25 Cont ID  
Sent By rlecky Date 2013-02-25 Time 14:47 Rev Time 0.00
Received By rlecky Date 2013-02-25 Time 14:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-11-19 Cont ID  
Sent By rlecky Date 2012-11-19 Time 16:19 Rev Time 0.00
Received By rlecky Date 2012-11-19 Time 16:07 Sent To  
Notes
2012-11-19 16:19:3412100900
 4200 BROADWAY
 COMMERCIAL RENOVATION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 PROVIDE A RISER PLAN SHOWING THE EXISTING ELECTRIC
 SERVICE COMPONENTS WITH METERS, MAIN DISCONNECTS AND
 PANEL BOARDS. NEC 110.26, 215.5, 240.24
 VERIFY THE REQUIRED WORKING CLEARANCES AND DEDICATED
 WORKING SPACE HAS BEEN PROVIDED AT THE ELECTRICAL
 SERVICE. NEC 110.26, 240.24
 VERIFY THE ELECTRICAL SERVICE MAINS FOR THIS BUILDING
 ARE SIX OR LESS AND GROUPED IN ONE LOCATION. NEC 230.2,
 230.71, 230.72
 PROVIDE A LIGHTING DENSITY CALCULATION SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC ENERGY CONSERVATION 505.3
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-11-03 Cont ID  
Sent By wjolin Date 2012-11-03 Time 16:28 Rev Time 0.00
Received By wjolin Date 2012-11-03 Time 16:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-04-12 Cont ID  
Sent By hmoser Date 2013-04-12 Time 09:43 Rev Time 0.00
Received By hmoser Date 2013-04-09 Time 10:16 Sent To  
Notes
2013-04-11 10:16:35SENT TO HAROLD'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-03-13 Cont ID  
Sent By hmoser Date 2013-03-13 Time 09:02 Rev Time 0.00
Received By hmoser Date 2013-02-15 Time 15:29 Sent To  
Notes
2013-02-19 15:36:08B--7

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-12-07 Cont ID  
Sent By lmartine Date 2012-12-07 Time 16:03 Rev Time 0.00
Received By lmartine Date 2012-10-30 Time 10:50 Sent To  
Notes
2012-10-31 10:51:12SENT TO B15 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2013-04-12 Cont ID  
Sent By hmoser Date 2013-04-12 Time 09:42 Rev Time 0.00
Received By hmoser Date 2013-04-12 Time 08:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2013-03-13 Cont ID  
Sent By hmoser Date 2013-03-13 Time 09:02 Rev Time 0.00
Received By hmoser Date 2013-03-12 Time 14:41 Sent To  
Notes
2013-03-13 09:02:12PLANS DENIED
 1) REFER TO SECTION 503.2.1 CALCULATION FOR HEATING &
 COOLING LOADS.
 2010 FLORIDA ENERGY CODE
 2) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS.
 FOR FRESH AIR
 2010 FLORIDA ENERGY CODE.
 3) COMPLETE THE EQUIPMENT SCHEDULE ON THE PLANS PER
 SECTION 107
 PLANS SHOW THREE A/C SYSTEMS SCHEDULE SHOWS TWO A/C
 SYSTEMS.
 2010 FBC.
 4) SHOW FRESH AIR DUCT ON THE MECHANICAL PLANS PER
 SECTION 107
 2010 FBC.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-12-07 Cont ID  
Sent By lmartine Date 2012-12-07 Time 15:59 Rev Time 0.00
Received By lmartine Date 2012-12-07 Time 15:59 Sent To  
Notes
2012-12-07 16:02:19*** PROVISO ***
 1) DOOR FROM RESTROOM TO A/C ROOM TO BE AIR TIGHT, PER
 2010 FBC/M 407.1.
  
 MECHANICAL PLAN REVIEW BY: TOM GORDON (HY-BYRD INC.)
 FOR ASSISTANCE CALL LUIS MARTINEZ (561) 805-6710

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-02-26 Cont ID  
Sent By lwagner Date 2013-02-26 Time 08:51 Rev Time 0.00
Received By lwagner Date 2013-02-26 Time 08:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-11-05 Cont ID  
Sent By lwagner Date 2012-11-05 Time 09:14 Rev Time 0.00
Received By lwagner Date 2012-11-05 Time 08:56 Sent To  
Notes
2012-11-05 09:14:25OK TO REMOVE W.C.