Plan Review Details - Permit 12100899
Plan Review Stops For Permit 12100899
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-11-15 Cont ID  
Sent By jgomez Date 2012-11-15 Time 10:38 Rev Time 0.00
Received By jgomez Date 2012-11-15 Time 10:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-11-02 Cont ID  
Sent By jgomez Date 2012-11-02 Time 09:32 Rev Time 0.00
Received By jgomez Date 2012-11-02 Time 08:59 Sent To  
Notes
2012-11-02 10:26:42RESIDENTIAL (R3) REPAIRS/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- WALL SECTIONS: SHOW HOW ARE THE LOADS TRANSFERED
 FROM CEILING TO FOUNDATION AS REQUIRED BY SEC. R601.2
 OF 2010 FBC-RESIDENTIAL. HOW IS THE WALL ATTACHED TO
 NEW 3 1/2" X 7" PARALLAM BEAM?. WALL SECTIONS SUBMITTED
 DON'T SPECIFY ANY CONNECTORS HERE.
  
 2- SPECIFY HOW ARE ALL THE FLOOR FRAMING MEMBERS
 PROTECTED FROM DECAY AS REQUIRED BY SEC. R317.1.
  
 3- SPECIFY CRAWL SPACE VENTILATION AS REQUIRED BY SEC.
 R408.1.
 NOTE; ALSO CHECK THE ALUMINUM TRAILER SKIRT
 MANUFACTURER' SPECIFICATIONS. THEY REQUIRE VENTILATION.
  
 4- CLARIFY IF REPLACING EXISTING ENTRY DOOR OR
 REBUILDING THE ENTRY DOOR FRAMING TO VERIFY COMPLIANCE
 WITH SEC. 601.2 OF 2010 FBC-EXISTING BUILDING. SPECIFY
 SIZE OF EXISTING DOOR. REBUILDING THE DOOR FRAME
 REQUIRES COMPLIANCE WITH SEC. 602.4 OF 2010
 FBC-EXISTING BUILDING. SEE SEC. R311.2 OF 2010
 FBC-RESIDENTIAL FOR REQUIRED SIZE.
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) SINGLE HUNG WINDOWS: ACCORDING TO THE MIAMI-DADE
 WEBSITE NOA 09-0316.10 SUBMITTED WAS SUPERSEDED. VISIT
 THE MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA.
 RESUBMIT CURRENT NOA. PRODUCT APPROVALS REQUIRED BY DCA
 RULE 9N-3.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED BY THE
 ARCHITECT ON PLANS SUBMITTED. PROVIDE ONLY THE COVER
 PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR.
  
 6- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 107.3.4.1 CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-11-01 Cont ID  
Sent By rlecky Date 2012-11-01 Time 17:50 Rev Time 0.00
Received By rlecky Date 2012-11-01 Time 17:32 Sent To  
Notes
2012-11-01 17:50:50TO JG

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-11-15 Cont ID  
Sent By jgomez Date 2012-11-15 Time 10:28 Rev Time 0.00
Received By jgomez Date 2012-11-13 Time 10:27 Sent To  
Notes
2012-11-15 10:28:10SENT TO JULIO'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-11-02 Cont ID  
Sent By mdekle Date 2012-11-02 Time   Rev Time 0.00
Received By mdekle Date 2012-10-30 Time 11:49 Sent To  
Notes
2012-10-31 16:22:28EXPEDITED
 R--21
  

Review Stop Z ZONING
Rev No 1 Status P Date 2012-11-02 Cont ID  
Sent By mdekle Date 2012-11-02 Time   Rev Time  
Received By mdekle Date 2012-11-02 Time   Sent To  
Notes
***NONE***