Plan Review Details - Permit 12100898
Plan Review Stops For Permit 12100898
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-12-06 Cont ID  
Sent By jwitmer Date 2012-12-06 Time 08:31 Rev Time 0.00
Received By jwitmer Date 2012-12-06 Time 07:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-11-07 Cont ID  
Sent By jwitmer Date 2012-11-07 Time 13:41 Rev Time 0.00
Received By jwitmer Date 2012-11-07 Time 12:30 Sent To  
Notes
2012-11-07 13:41:43BUILDING PLAN REVIEW
 PERMIT: 12100898
 ADD: 500 PALM ST UNIT # 32
 CONT: LIVINGSTON BUILDERS
 TEL: (561)833-3242
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 NOV. 07/ 2012
 ACTION: DENIED
  
 1) 2010 FBC-B/ WEST PALM BEACH ADMINISTRATIVE CODE
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS:
 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD / MEANS OF EGRESS TRAVEL DISTANCE
 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE: WIND DESIGN
 CRITERIA, FOUNDATION PLANS INDICATE THE CUTTING OF SLAB
 FOR NEW CONCRETE PADS FOR
 FOUR POST CAR LIFT, NO DESIGN CRITERIA FOR FOUNDATION
 NOR REINFORCEMENT NOR ANCHORAGE OF 4 POST CAR LIFT.
  
 2) PLANS DO NOT PROVIDE IF THIS IS A CHANGE OF
 OCCUPANCY OR TO WHAT LEVEL THE DESIGNER HAS DESSIGNED
 UNDER THE 2010 FBC- EXISTING BUILDING. CHAPTER 4 OF THE
 2010 EXISTING BUILDING CODE.
  
 3) PLEASE REVIEW SECTION 406.6 FOR REPAIR GARAGES .
 REPAIR GARAGES SHALL BE CONSTRUCTED IN ACCORDANCE WITH
 THE FLORIDA FIRE PREVENTION CODE AND SECTIONS 406.6.1
 THROUGH 406.6.6. THIS OCCUPANCY SHALL NOT INCLUDE MOTOR
 FUEL-DISPENSING FACILITIES, AS REGULATED IN SECTION
 406.5.
  
 4) REPAIR GARAGES ARE CLASSIFIED AS A S1 OCCUPANCY
 PLEASE REVIEW 2010 FBC-B TABLE 508.4 DEPENDING ON THE
 OCCUPANCIES ON EITHER OR BOTH SIDES A ONE HOUR OR TWO
 HOUR OCCUPANCY SEPERATION MAY BE REQUIRED.
  
 5) PLANS DO NOT INDICATE IF THE A/C IS NEW OR IF
 EXISTING, IF NEW PLEASE PROVIDE INSULATION NOT
 INDICATED IN THE ENERGY CALCULATIONS. 2010 ENERGY
 502.1.1.1.
  
 6) PLANS INDICATE THE REPLACEMENT OF THE OVERHEAD DOOR
 NO PRODUCT TESTING REPORT WAS SUBMITTED AT THIS TIME.
 1609.4.4.1 COMPONENTS AND CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 7) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2013-04-24 Cont ID  
Sent By dharvey Date 2013-04-24 Time 15:33 Rev Time 0.00
Received By dharvey Date 2013-04-24 Time 15:33 Sent To  
Notes
2013-04-24 15:37:28NOTES PUT HERE BY MISTAKE. SEE REVISION NUMBER FOR SAME
 NOTES.
 DESIGNER HAS CHANGED - NEED DOCUMENTATION OF DESIGN
 PROFESSIONAL CHANGE
 PLANS DO NOT MATCH ORIGINAL FLOOR PLAN. NEED BUILDING,
 MECHANICAL AND PLUMBING PLANS
 NO REVIEW DONE
  
 FILED IN DENIED UNDER "L" DH

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-11-05 Cont ID  
Sent By rlecky Date 2012-11-05 Time 13:59 Rev Time 0.00
Received By rlecky Date 2012-11-05 Time 13:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-12-06 Cont ID  
Sent By wjolin Date 2012-12-06 Time 14:01 Rev Time 0.00
Received By wjolin Date 2012-12-06 Time 13:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-11-17 Cont ID  
Sent By wjolin Date 2012-11-17 Time 15:21 Rev Time 0.00
Received By wjolin Date 2012-11-17 Time 14:58 Sent To  
Notes
2012-11-17 15:21:48500 PALM STREET - SUITE #32
 PERMIT #12100898
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 INDICATE THE TYPES OF WORK (OIL CHANGES, ENGINE
 OVERHAUL, WELDING, PAINTING, ETC.) TO BE PERFORMED AT
 THIS LOCATION.
  
 PERMANENT NO SMOKING OR OPEN FLAME SIGNS TO BE POSTED
 IN THE WORK BAYS AND WORKSHOP.
  
 THE COMMON PATH OF TRAVEL FROM THE PRIMARY BAY TO A
 SIDE SWINGING EGRESS DOOR EXCEEDS 50 FEET. NOTE:
 OVERHEAD ROLL-UP DOORS DO NOT CONSTITUTE AN EXIT.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-12-06 Cont ID  
Sent By lmartine Date 2012-12-06 Time 17:41 Rev Time 0.00
Received By lmartine Date 2012-12-05 Time 15:56 Sent To  
Notes
2012-12-05 15:58:59EXPEDITED 2ND RUN
 GAVE TO WESLEY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-11-17 Cont ID  
Sent By wjolin Date 2012-11-17 Time 15:21 Rev Time 0.00
Received By wjolin Date 2012-10-30 Time 10:00 Sent To  
Notes
2012-11-01 10:05:53EXPEDITED
 B--3

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-11-14 Cont ID  
Sent By hmoser Date 2012-11-14 Time 14:22 Rev Time 0.00
Received By hmoser Date 2012-11-14 Time 10:56 Sent To  
Notes
2012-11-14 14:22:53PROVISO
 PAGE M1.1 OF THE PLANS SAY CONDENSER STAND IS NEW.
 PAGE M2.1 OF THE PLANS SAY CONDENSER STAND IS EXISTING.
 IF THE CONDENSER STAND IS NEW PROVIDE A LETTER FROM THE
 ENGINEER ON THE STAND TO ROOF TIEDOWN AT FIRST
 INSPECTION.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-11-02 Cont ID  
Sent By lwagner Date 2012-11-02 Time 15:21 Rev Time 0.00
Received By lwagner Date 2012-11-02 Time 14:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2012-11-05 Cont ID  
Sent By ajones Date 2012-11-05 Time 11:03 Rev Time 0.00
Received By ajones Date 2012-11-05 Time 11:03 Sent To  
Notes
***NONE***