Plan Review Details - Permit 12100870
Plan Review Stops For Permit 12100870
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-07-02 Cont ID  
Sent By jwitmer Date 2013-07-02 Time 18:21 Rev Time 0.00
Received By jwitmer Date 2013-07-02 Time 18:21 Sent To  
Notes
2013-07-02 18:22:26PRODUCT APPROVALS AND SHOP DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2012-11-19 Cont ID  
Sent By jwitmer Date 2012-11-19 Time 09:46 Rev Time 0.00
Received By jwitmer Date 2012-11-16 Time 15:48 Sent To  
Notes
2012-11-19 09:46:32BUILDING PLAN REVIEW
 PERMIT: 12100870
 ADD: 901 45TH STREET
 CONT: WESTBROOKE CORP.
 TEL: (561)239-7133
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2)MISSING PRODUCT APPROVALS PRESSURES ARE OK! 2010
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. SWING AND BREAKAWAY SLIDING
 DOORS.
 (B) WINDOWS/ STOREFRONT AND SPANDREL GLAZING SYSTEMS.
 (C) WALL LOUVERS,
 (E) SHUTTERS IF LARGE MISSILE IMPACT RESITANT GLAZING
 SYSTEMS ARE NOT INSTALLED
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-04-29 Cont ID  
Sent By rlecky Date 2013-04-29 Time 08:13 Rev Time 0.00
Received By dharvey Date 2013-04-25 Time 15:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-11-20 Cont ID  
Sent By wjolin Date 2012-11-20 Time 10:06 Rev Time 0.00
Received By wjolin Date 2012-11-20 Time 08:45 Sent To  
Notes
2012-11-20 10:06:34901 45TH STREET - WOUND CARE
 PERMIT #12100870
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR
 AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL
 HAVE "NO SMOKING" SIGNS POSTED. WHERE SMOKING IS
 PERMITTED, SAFE RECEPTACLES FOR SMOKING MATERIALS SHALL
 BE PROVIDED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 PER SECTION 7.2.1.9.1.3 OF NFPA 101- POWER OPERATED
 DOORS: A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT
 LESS THAN 1-INCH HIGH ON A CONTRASTING BACKGROUND THAT
 READS AS FOLLOWS SHALL BE LOCATED ON THE EGRESS SIDE OF
 EACH DOOR OPENING: IN EMERGENCY, PUSH TO OPEN.
  
 DOOR #28 EQUIPPED WITH "MAG" LOCKS:
 SECTION 7.2.1.6.2 OF NFPA 101 FLORIDA EDITION 2009
 ALLOWS ACCESS CONTROLLED EGRESS DOORS PROVIDED THAT ALL
 SEVEN OF THE FOLLOWING CRITERIA ARE MET:
 1. A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO DETECT AN OCCUPANT APPROACHING DOORS THAT
 ARE ARRANGED TO UNLOCK IN THE DIRECTION OF EGRESS UPON
 DETECTION OF AN APPROACHING OCCUPANT OR LOSS OF POWER
 TO THE SENSOR.
 2. LOSS OF POWER TO THE PART OF THE ACCESS CONTROL
 SYSTEM THAT LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK
 THE DOORS IN THE DIRECTION OF EGRESS.
 3. THE DOORS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE
 LOCATED VERTICALLY 40 TO 48 INCHES ABOVE THE FLOOR AND
 WITHIN 60 INCHES HORIZONTALLY OF THE SECURED DOORS.
 4. THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS
 PUSH TO EXIT.
 5. WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK,
 INDEPENDENT OF THE ACCESS CONTROL SYSTEM ELECTRONICS,
 AND THE DOORS SHALL REMAIN UNLOCKED FOR NOT LESS THAN
 30 SECONDS.
 6. ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
 7. ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER
 SYSTEM OR AUTOMATIC DETECTION SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-07-02 Cont ID  
Sent By jwitmer Date 2013-07-02 Time 18:21 Rev Time 0.00
Received By jwitmer Date 2013-06-27 Time 10:23 Sent To  
Notes
2013-06-28 10:23:50SUBMITTAL??? SENT TO RON'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-12-11 Cont ID  
Sent By lwagner Date 2012-12-11 Time 12:18 Rev Time 0.00
Received By lwagner Date 2012-10-30 Time 10:07 Sent To  
Notes
2012-10-30 10:07:25C--5

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-12-11 Cont ID  
Sent By lwagner Date 2012-12-11 Time 10:15 Rev Time 0.00
Received By lmartine Date 2012-12-11 Time 10:15 Sent To  
Notes
2012-12-11 10:17:15*** SEE PLUMBING PROVISO REGURDING CONDENSATE
 DISCHARGEING INTO SEWER SYSTEM IN PROHIBITED.

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status P Date 2012-12-11 Cont ID  
Sent By lwagner Date 2012-12-11 Time 10:08 Rev Time 0.00
Received By lwagner Date 2012-12-11 Time 09:22 Sent To  
Notes
2012-12-11 09:43:48***PROVISO***
 NO MED-GAS DEMO WITHOUT ISSUED
 MED-GAS PERMIT.
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-12-11 Cont ID  
Sent By lwagner Date 2012-12-11 Time 10:01 Rev Time 0.00
Received By lwagner Date 2012-11-13 Time 14:59 Sent To  
Notes
2012-11-14 09:06:40***PROVISO***
  
 1. P2.1, P2.3, & P4.1 AC CONDENSATE IS NOT PERMITTED IN
 THE CITY OF WEST PALM BEACH SEWER SYSTEM.
 SEC. 90-126. - PROHIBITIONS AND LIMITATIONS OF
 DISCHARGE. (5)
 STORMWATER, SURFACE WATER, GROUNDWATER, ARTESIAN WELL
 WATER, ROOF RUNOFF, SUBSURFACE DRAINAGE, SWIMMING POOL
 DISCHARGES, UNCONTAMINATED COOLING WATER, UNPOLLUTED
 INDUSTRIAL PROCESS WATERS, AIR CONDITIONING CONDENSATE,
 UNLESS SPECIFICALLY AUTHORIZED BY THE CITY IN WRITING.
  
  
  

Review Stop Z ZONING
Rev No 1 Status N Date 2012-11-08 Cont ID  
Sent By avann Date 2012-11-08 Time 14:29 Rev Time  
Received By ajones Date 2012-11-05 Time   Sent To  
Notes
***NONE***