Plan Review Details - Permit 12100867
Plan Review Stops For Permit 12100867
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-02-13 Cont ID  
Sent By shill Date 2013-02-13 Time 11:03 Rev Time 0.00
Received By shill Date 2013-02-13 Time 11:03 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-12-11 Cont ID  
Sent By shill Date 2012-12-11 Time 14:03 Rev Time 0.00
Received By shill Date 2012-12-11 Time 14:03 Sent To  
Notes
2012-12-11 14:19:16****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. PROVIDE A LEGIBLE PLAN WHICH CLEARLY SHOWS THE
 FOLLOWING INFORMATION:
  
 TOTAL NUMBER OF PARKING SPACES
 NUMBER OF ACCESSIBLE SPACES
 LOCATION OF ACCESSIBLE SPACES AND ACCESS AISLES
 LOCATION OF ACCESSIBLE ENTRANCES
 SHOW ACCESSIBLE ROUTE FROM PUBLIC WAY
  
 SEE FBC 2010 ACCESSIBLITY 202.3 (ALTERATIONS), 208.2
 (PARKING SPACES), 502 (PARKING SPACES), 206 (ACCESSIBLE
 ROUTE).
  
 YOU MAY FIND THE FOLLOWING DOCUMENT USEFUL,
 PARTICULARLY THE INTRODUCTION: "WHEN A BUSINESS
 RESTRIPES A PARKING LOT, IT MUST PROVIDE ACCESSIBLE
 PARKING SPACES AS REQUIRED BY THE ADA STANDARDS FOR
 ACCESSIBLE DESIGN."
  
 HTTP://WWW.ADA.GOV/RESTRIPE.HTM
  
 2ND REVIEW - AS DISCUSSED, TWO DIFFERENT PLANS WERE
 SUBMITTED ON FIRST REVIEW. ONE PLAN WAS AN ILLEGIBLE
 SURVEY. THE OTHER PLAN IS LEGIBLE BUT DOES NOT INCLUDE
 ALL INFORMATION PERTINENT TO THIS JOB SUCH AS LOCATION
 OF ALL ACCESSIBLE SPACES AND ACCESSIBLE ROUTE.
  
 ALTHOUGH I ADVISED CONTRACTOR THAT I HAD AN OBJECTION
 TO STAMPING A NON COMPLIANT PLAN, SAME PLANS WERE
 SUBMITTED.
  
 THE LETTER FROM CONTRACTOR STATES THAT THERE ARE 223
 STANDARD SPACES AND 7 ACCESSIBLE SPACES. THIS APPEARS
 TO BE THE NUMBER IN THE AREA TO BE REPAIRED. A TOTAL
 FOR THE LOT IS REQUIRED, AS WELL AS LOCATION OF ALL
 ACCESSIBLE SPACES, IN A LEGIBLE FORMAT. ALTHOUGH YOU
 ARE NOT WORKING IN THE REMAINDER OF THE LOT, IF THE
 SEVEN SPACES PLUS ADDITIONAL SPACES ON THE LOT NOT
 INCLUDED IN THE CONTRACTOR'S COUNT DO NOT COMPLY WITH
 THE REQUIREMENT FOR THE LOT OVERALL, ADDITIONAL
 ACCESSIBLE SPACES WILL BE REQUIRED.
  
 2. NA
  
 2. THE INDIVIDUAL TAKING RESPONSIBILITY FOR THE DESIGN
 IS TO PROVIDE THEIR PRINTED NAME AND SIGNATURE ON THE
 PLAN, FBC 109.
  
 2ND REVIEW, NOT ADDRESSED. PROVIDE ONE PLAN WHICH SHOWS
 ALL ITEMS IN COMMENT #1.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-11-13 Cont ID  
Sent By shill Date 2012-11-13 Time 10:55 Rev Time 0.00
Received By shill Date 2012-11-13 Time 10:55 Sent To  
Notes
2012-11-13 11:13:52****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. PROVIDE A LEGIBLE PLAN WHICH CLEARLY SHOWS THE
 FOLLOWING INFORMATION:
  
 TOTAL NUMBER OF PARKING SPACES
 NUMBER OF ACCESSIBLE SPACES
 LOCATION OF ACCESSIBLE SPACES AND ACCESS AISLES
 LOCATION OF ACCESSIBLE ENTRANCES
 SHOW ACCESSIBLE ROUTE FROM PUBLIC WAY
  
 SEE FBC 2010 ACCESSIBLITY 202.3 (ALTERATIONS), 208.2
 (PARKING SPACES), 502 (PARKING SPACES), 206 (ACCESSIBLE
 ROUTE).
  
 YOU MAY FIND THE FOLLOWING DOCUMENT USEFUL,
 PARTICULARLY THE INTRODUCTION: "WHEN A BUSINESS
 RESTRIPES A PARKING LOT, IT MUST PROVIDE ACCESSIBLE
 PARKING SPACES AS REQUIRED BY THE ADA STANDARDS FOR
 ACCESSIBLE DESIGN."
  
 HTTP://WWW.ADA.GOV/RESTRIPE.HTM
  
 2. THE TYPED "JOB SPECIFICATION" STATES THAT THERE WILL
 BE 6 ACCESSIBLE SPACES PROVIDED. THE SURVEY SHOWS MORE
 THAN SIX ACCESSIBLE ("HANDICAP") SPACES. IT APPEARS
 THAT THE ACCESSIBLE SPACE ON THE SOUTH END OF THE
 PARKING LOT IS TO BE ELIMINATED. AS THE NUMBER OF
 ACCESSIBLE SPACES ON THE PLAN DO NOT CORRELATE WITH THE
 NUMBER PROPOSED, IT IS NOT CLEAR WHICH OTHER SPACES ARE
 PROPOSED TO BE ELIMINATED.
  
 SEE FBC 2010 ACCESSILIBILITY 208.3, "PARKING SPACES
 COMPLYING WITH 502 THAT SERVE A PARTICULAR BUILDING OR
 FACILITY SHALL BE LOCATED ON THE SHORTEST ACCESSIBLE
 ROUTE FROM PARKING TO AN ENTRANCE COMPLYING WITH 206.4.
 BY ELIMINATING ACCESSIBLE SPACES IN THE NORTH OR SOUTH
 AREAS OF THE PARKING LOT, YOU ARE INCREASING THE
 DISTANCE OF TRAVEL, WHICH DOES NOT COMPLY WITH THE
 MINIMUM CODE REQUIREMENTS. PLEASE REVISE.
  
 2. THE INDIVIDUAL TAKING RESPONSIBILITY FOR THE DESIGN
 IS TO PROVIDE THEIR PRINTED NAME AND SIGNATURE ON THE
 PLAN, FBC 109.
  
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2012-11-09 Cont ID  
Sent By Mgonzale Date 2012-11-09 Time   Rev Time 1.00
Received By mgonzale Date 2012-11-09 Time   Sent To B
Notes
2012-11-09 15:50:49NO CONFLICT WITH CITY OF WPB PUBLIC UTILITIES.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-02-20 Cont ID  
Sent By mdekle Date 2013-02-20 Time   Rev Time 0.00
Received By mdekle Date 2013-02-07 Time 18:38 Sent To  
Notes
2013-02-13 11:03:532/13 TO ZONING IN BOX
  
2013-02-07 18:38:34TO SH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-01-14 Cont ID  
Sent By shill Date 2013-12-11 Time 14:37 Rev Time 0.00
Received By shill Date 2012-11-28 Time 07:05 Sent To  
Notes
2012-12-03 08:52:5112/3 TO ZONING
  
2012-11-28 07:06:33SENT TO S HILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-11-13 Cont ID  
Sent By shill Date 2012-11-13 Time 11:13 Rev Time 0.00
Received By shill Date 2012-10-29 Time 15:20 Sent To  
Notes
2012-10-29 15:20:25IN ZONING BOX

Review Stop Z ZONING
Rev No 3 Status P Date 2013-02-20 Cont ID  
Sent By mdekle Date 2013-02-20 Time   Rev Time 0.00
Received By mdekle Date 2013-02-20 Time 13:32 Sent To  
Notes
2013-02-20 13:32:15PROVISO - UPON FINAL INSPECTION: THE EXISTING
 LANDSCAPING ON THE SUBJECT PROPERTY MUST BE IN
 COMPLIANCE WITH THE APPROVED LANDSCAPE PLAN WHICH WAS
 APPROVED WITH THE ORIGINAL DEVELOPMENT APPROVAL. ANY
 DEFICIENCIES MUST BE INSTALLED ACCORDINGLY.

Review Stop Z ZONING
Rev No 2 Status P Date 2012-12-07 Cont ID  
Sent By mdekle Date 2012-12-07 Time   Rev Time 0.00
Received By mdekle Date 2012-12-03 Time   Sent To B
Notes
2012-12-07 08:15:20PROVISO - UPON FINAL INSPECTION: THE EXISTING
 LANDSCAPING ON THE SUBJECT PROPERTY MUST BE IN
 COMPLIANCE WITH THE APPROVED LANDSCAPE PLAN WHICH WAS
 APPROVED WITH THE ORIGINAL DEVELOPMENT APPROVAL. ANY
 DEFICIENCIES MUST BE INSTALLED ACCORDINGLY.

Review Stop Z ZONING
Rev No 1 Status P Date 2012-11-08 Cont ID  
Sent By mdekle Date 2012-11-08 Time   Rev Time  
Received By mdekle Date 2012-10-29 Time   Sent To ENG
Notes
2012-11-08 13:56:58PROVISO - UPON FINAL INSPECTION: THE EXISTING
 LANDSCAPING ON THE SUBJECT PROPERTY MUST BE IN
 COMPLIANCE WITH THE APPROVED LANDSCAPE PLAN WHICH WAS
 APPROVED WITH THE ORIGINAL DEVELOPMENT APPROVAL. ANY
 DEFICIENCIES MUST BE INSTALLED ACCORDINGLY.