Plan Review Details - Permit 12100729
Plan Review Stops For Permit 12100729
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-12-03 Cont ID  
Sent By rmcdouga Date 2012-12-03 Time 15:37 Rev Time 0.00
Received By rmcdouga Date 2012-12-03 Time 15:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-11-07 Cont ID  
Sent By rmcdouga Date 2012-11-07 Time 15:56 Rev Time 0.00
Received By rmcdouga Date 2012-11-07 Time 15:56 Sent To  
Notes
2012-11-07 16:46:142010 FBC
  
 DENIED BY BUILDING
  
 1) THE PLANS THAT WERE SUBMITTED ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT SPECIFIED IN THE
 TITLE BLOCK PER FS 481.
  
 2) THE PLANS HAVE BEEN REDUCED IN SIZE FROM THE
 ORIGINAL 1/4" SCALE AND ARE TOO SMALL. CITY AMENDMENT
 107.2.1.4 REQUIRES PLANS TO BE A MINIMUM SCALE OF 1/8"
 SCALE. PLEASE CORRECT.
  
 3) THERE ARE NO DIMENSIONS ON THE PLANS. PROVIDE
 DIMENSIONED FLOOR PLANS. CITY AMENDMENT 107.2.1
  
 4) ON SHEET SP-1 THE WRONG CODE EDITION AND DESIGN
 CRITERIA IS SPECIFIED FOR THE PROJECT INFORMATION. THE
 WINDOW AND DOOR PRESSURES LISTED ARE TOO LOW FOR
 EXPOSURE C WITH A 25' MRH. THE PRESSURES FOR A 10 SQFT
 OPENING IN WALL ZONE 5 WOULD BE +42.3, -56.6 PSF PER
 FBCR 301.2.1.
  
 5) TWO PRODUCT APPROVALS WERE SUBMITTED FOR TRACO
 SINGLE HUNG WINDOWS. THERE IS NO MENTION OF WINDOW
 REPLACEMENT ON THE APPLICATION OR IN THE SCOPE OF WORK
 ON THE PLANS. PLEASE CLARIFY. NOTE: THESE PRODUCT
 APPROVALS EXPIRED IN 2007.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-11-07 Cont ID  
Sent By rmcdouga Date 2012-11-07 Time 15:47 Rev Time 0.00
Received By rmcdouga Date 2012-11-07 Time 15:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-12-03 Cont ID  
Sent By rmcdouga Date 2012-12-03 Time 15:37 Rev Time 0.00
Received By rmcdouga Date 2012-11-29 Time 16:45 Sent To  
Notes
2012-11-29 16:48:59GAVE TO ROBBIE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-11-07 Cont ID  
Sent By rmcdouga Date 2012-11-07 Time 15:56 Rev Time 0.00
Received By rmcdouga Date 2012-10-23 Time 16:21 Sent To  
Notes
2012-10-23 16:22:42R--15

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-12-03 Cont ID  
Sent By rmcdouga Date 2012-12-03 Time 15:36 Rev Time 0.00
Received By rmcdouga Date 2012-12-03 Time 15:36 Sent To  
Notes
2012-12-03 15:37:37REDLINED PLANS

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-11-07 Cont ID  
Sent By rmcdouga Date 2012-11-07 Time 15:47 Rev Time 0.00
Received By rmcdouga Date 2012-11-07 Time 15:47 Sent To  
Notes
2012-11-07 15:55:352010 FBC
  
 PLUMBING DENIED
  
 1) SUBMIT TWO SETS OF AN ISOMETERIC PLUMBING RISER
 DIAGRAM AS REQUIRED BY CITY AMENDMENTS 107.3.5.3 (11).
 SHOW ALL VENT AND DRAIN PIPE SIZES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]