Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-10-29 Cont ID  
Sent By rlecky Date 2012-10-29 Time 09:47 Rev Time 0.00
Received By rlecky Date 2012-10-29 Time 09:12 Sent To  
Notes
2012-10-29 09:47:5212050341
 1711 LONGWOOD ROAD
 NEW ELECTRIC SYSTEM
  
 FEEDERS TO PANEL BOARD ?PM2? MAY NOT BE DIVIDED BETWEEN
 TWO CONDUITS. ALL CONDUCTORS OF THE SAME CIRCUIT SHALL
 BE CONTAINED WITHIN THE SAME RACEWAY. NEC 300.3 (B)
  
 PROVIDE A COMMON GROUNDING ELECTRODE CONDUCTOR FOR THE
 MULTIPLE SEPARATELY DERIVED SYSTEMS WHICH TIES BACK TO
 THE SERVICE. NEC 250.30 (4), 250.52.
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
  