Plan Review Details - Permit 12100670
Plan Review Stops For Permit 12100670
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-12-28 Cont ID  
Sent By jwitmer Date 2012-12-28 Time 13:21 Rev Time 0.00
Received By jwitmer Date 2012-12-28 Time 10:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-12-12 Cont ID  
Sent By jwitmer Date 2012-12-12 Time 16:10 Rev Time 0.00
Received By jwitmer Date 2012-12-12 Time 11:58 Sent To  
Notes
2012-12-12 16:25:22BUILDING PLAN REVIEW
 PERMIT: 12100670
 ADD: 801 VILLAGE BLVD # 303-304
 CONT: PAGE CONTRACING
 TEL: (954)868-4561
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DEC. 12/ 2012
 ACTION:DENIED
  
 1) SHEET A-2.01:
  
 1A) COMPLIED.
  
 1B) 2ND REQUEST PLEASE REVIEW OCCUPANT LOAD CHART AND
 TOTAL OCCUPANCY LOAD. 2010 FBC-B TABLE 1004.1.1 FOR
 DAYCARE THE OCCUPANT LOAD IS FIGURED AT 20 NET NOT THE
 35 SQ FT AS INDICATED, THE OFFICE, LOBBY AND KITCHEN DO
 NOT INDICATE ANY OCCUPANT LOADS WITHIN THE CHART BUT
 THE FLOOR PLAN DOES, PLEASE CORRECT THE OCCUPANT LOAD
 FOR EACH ROOM WITHIN THE CHART, CORRECT THE SQ FT
 REQUIRED FOR EACH OCCUPANT PER TABLE 1004.1. AAND
 PROVIDE THE TOTAL OCCUPANT LOAD FOR THE DAYCARE
 OCCUPANCY.
 2) SHEET A2.01:
  
 2A) COMPLIED.
  
 2B) COMPLIED.
  
 3) COMPLIED.
  
 4) 2ND REQUEST, SHEET E1 NOR THE LIFE SAFETY SHEEET
 INDICATE COMPLIANCE WITH2010 EXISTING BLDG CODE 912.2.2
 FIRE ALAARM AND DETECTION SYSTEMS AND 2010 FBC-B 436.7
 DETECTION AND ALARM SYSTEMS . THE RESPONSE INDICATES
 THAT FIRE ALARM AND FIRE SPRINKLER DRAWINGS ARE
 REQUIRED FOR A GENERAL BUILDING PERMIT BUT NONE HAVE
 BEEN PROVIDED.
 2010 WPB ADMINISTRATIVE CODE. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFICAND THE
 TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN
 PART...
  
 5) COMPLIED..
  
 6) 2ND REQUEST. PLANSDO NOT INDICATE WALL FINISHES FOR
 SPRINKLERED BUILDING PROVIDE COMPLIANCE WITH TABLE
 803.9 AND 806.1.2 COMBUSTIBLE DECORATIVE MATERIALS.
  
 7) 2ND REQUEST. SHEET A2.02 THE NEW SIDEWALKS ON THE
 BUILDING ARE 5'-0" WIDE CODE COMPLIANT FOR AN
 ACCESSIBLE ENTRANCE AS DEPICTED IN FIGURE 404.2.4.1 (D)
 REQUIRING 60" BUT THE NEW SIDEWALK ON THE SIDE OF THE
 BUILDING IS ONLY 4'-0" WIDE A NEW NON-CODE COMPLIANT
 ELEMENT, THE PORTION THAT IS DIRECTLY AGAINST THE
 BUILDING.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-11-14 Cont ID  
Sent By jwitmer Date 2012-11-14 Time 09:20 Rev Time 0.00
Received By jwitmer Date 2012-11-14 Time 08:02 Sent To  
Notes
2012-11-14 09:41:15BUILDING PLAN REVIEW
 PERMIT: 12100670
 ADD: 801 VILLAGE BLVD # 303-304
 CONT: PAGE CONTRACING
 TEL: (954)868-4561
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 NOV. 14/ 2012
 ACTION:DENIED
  
 1) SHEET A-2.01:
  
 1A) BUILDING DATA CHART INDICATES THIS IS A LEVEL II
 ALTERATION. 2010 EXISTING BUILDING CODE PLEASE REVIEW
 901.3.1 PARTIAL CHANGE OF OCCUPANCY AND 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 THIS IS A CHANGE IN OCCUPANCY GOING FROM BUSINESS TO
 DAYCARE.
  
 1B) PLEASE REVIEW OCCUPANT LOAD CHART AND TOTAL
 OCCUPANCY LOAD. 2010 FBC-B TABLE 1004.1.1 FOR DAYCARE
 THE OCCUPANT LOAD IS FIGURED AT 20 NET NOT THE
 35 SQ FT AS INDICATED, THE TOTAL OCCUPANT LOAD IS
 APPROXIMATELY 214 WITH THE SQ FT INCLUDED FOR OFFICE
 STAFF.
  
 2) SHEET A2.01:
  
 2A) THE HARDWARE SCHEDULE DOESN'T INDICATE COMPLIANCE
 WITH 436.3 BATHROOM DOORS.
  
 2B) PLEASE REVIEW REQUIREMENTS FOR THE MAINTENACE ROOM/
 LAUNDRY UNDER 2010 FBC-B 436.6.2 FOR THE REQUIREMENT OF
 A 1 HOUR FIRE RATING OF WALLS AND OPENING PROTECTION IN
 ACCORDANCE WITH TABLE 715.4.
  
 3) THE E1 SHEET INDICATES THE USE OF EXIT LIGHTS AND
 BATTERY BACK UP ILLUMINATION UNITS WITH THE CORRIDOR
 103. 2010 FBC-B TABLE 1006.
  
 4) SHEET E1 NOR THE LIFE SAFETY SHEEET INDICATE
 COMPLIANCE WITH2010 EXISTING BLDG CODE 912.2.2 FIRE
 ALAARM AND DETECTION SYSTEMS AND 2010 FBC-B 436.7
 DETECTION AND ALARM SYSTEMS .
  
 5) SHEET A-2.1 INDICATES THE EXIT CORRIDOR WALLS TO BE
 A WALL TAG TYPE D, AND NO INFORMATION ON THE CORRIDOR
 CEILING TYPE, PLEASE PROVIDE COMPLIANCE WITH
 2010 FBC-B 436.8 CORRIDORS EXCEPTION # 1 CORRIDOR WALLS
 FORMING SMOKE PARTITIONS IN ACCORDANCE WWITH 710.
  
 6) PLANSDO NOT INDICATE WALL FINISHES FOR SPRINKLERED
 BUILDING PROVIDE COMPLIANCE WITH TABLE 803.9 AND
 806.1.2 COMBUSTIBLE DECORATIVE MATERIALS.
  
 7) SHEET A2.02 THE NEW SIDEWALKS ON THE BUILDING ARE
 5'-0" WIDE CODE COMPLIANT FOR AN ACCESSIBLE ENTRANCE AS
 DEPICTED IN FIGURE 404.2.4.1 (D) REQUIRING 60" BUT THE
 NEW SIDEWALK ON THE SIDE OF THE BUILDING IS ONLY 4'-0"
 WIDE A NEW NON-CODE COMPLIANT ELEMENT.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2012-12-27 Cont ID  
Sent By rlecky Date 2012-12-27 Time 10:45 Rev Time 0.00
Received By rlecky Date 2012-12-27 Time 10:40 Sent To  
Notes
2012-12-21 16:11:43NEW SHEET E2. JG.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-12-19 Cont ID  
Sent By rlecky Date 2012-12-19 Time 15:07 Rev Time 0.00
Received By rlecky Date 2012-12-19 Time 14:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-11-14 Cont ID  
Sent By rlecky Date 2012-11-14 Time 15:20 Rev Time 0.00
Received By rlecky Date 2012-11-14 Time 15:04 Sent To  
Notes
2012-11-14 15:24:3612100670
 801 VILLAGE BLVD. #303
 COMMERCIAL REMODEL ? DAYCARE
  
 PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW
 COMMENTS.
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC ENERGY CONSERVATION 505.3
 ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH
 GFCI PROTECTION. NEC 422.52
 ALL RECEPTACLES LOCATED WITH IN SIX FEET OF A SINK MUST
 BE GFCI PROTECTED. NEC 210.8
 A FIRE ALARM SYSTEM IS REQUIRED. FBC 436.7
 A SMOKE DETECTION SYSTEM IS REQUIRED. FBC 436.7.2
  
 NOTE:
 SEPARATE PERMITS ARE REQUIRED FOR VOICE AND DATA AND
 ALARM SYSTEMS.
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2013-03-15 Cont ID  
Sent By rlecky Date 2013-01-09 Time 09:30 Rev Time 0.00
Received By ddaniels Date 2013-01-09 Time 09:30 Sent To  
Notes
2013-01-09 09:33:15FIRE COMMENTS ADDRESSED UNDER PERMIT # 12100670. COPY
 OF APPROVED FIRE SPRINKLER PLAN ATTACHED TO MASTER
 PLANS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2013-01-04 Cont ID  
Sent By wjolin Date 2013-01-04 Time 10:42 Rev Time 0.00
Received By wjolin Date 2013-01-04 Time 10:24 Sent To  
Notes
2013-01-04 10:42:56801 VILLAGE BOULEVARD - SUITE #303-304
 PERMIT #12100670
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT: NO ADDRESS PROVIDED IN THE PLAN
 TITLEBLOCK INFORMATION.
  
 REPEAT COMMENT: ENGINEERED FIRE SPRINKLER CONSTRUCTION
 DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT.
  
 REPEAT COMMENT: PER FLORIDA ADMINISTRATIVE CODE SECTION
 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS
 SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER
 SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE
 TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR
 EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN
 DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT
 FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION
 SUCH AS PRE-ENGINEERED SYSTEMS.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2012-12-17 Cont ID  
Sent By wjolin Date 2012-12-17 Time 09:19 Rev Time 0.00
Received By wjolin Date 2012-12-17 Time 09:01 Sent To  
Notes
2012-12-17 09:19:42801 VILLAGE BOULEVARD - SUITE #303-304
 PERMIT #12100670
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT: NO ADDRESS PROVIDED IN THE PLAN
 TITLEBLOCK INFORMATION.
  
 NEW COMMENT: REVISE THE OCCUPANT LOAD CHART TO MATCH
 THE OCCUPANT LOADS SHOWN ON THE FLOOR PLAN.
 ORIGINAL COMMENT: PER TABLE 7.3.1.2 (NFPA 101 -
 FLORIDA) THE DAY-CARE OCCUPANT LOAD FACTOR SHALL BE 20
 SQ.FT. PER PERSON NOT 35 SQ.FT. PER PERSON.
  
 REPEAT COMMENT: ELECTRICAL - NO MANUAL FIRE ALARM
 SYSTEM OR SMOKE DETECTION PROVIDED PER SECTION 16.3.4
 (NFPA 101 - FLORIDA).
  
 REPEAT COMMENT: ENGINEERED FIRE ALARM AND FIRE
 SPRINKLER CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A
 GENERAL BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS
 BEEN ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT.
  
 REPEAT COMMENT: PER FLORIDA ADMINISTRATIVE CODE SECTION
 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS
 SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER
 SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE
 TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR
 EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN
 DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT
 FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION
 SUCH AS PRE-ENGINEERED SYSTEMS.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-10-29 Cont ID  
Sent By wjolin Date 2012-10-29 Time 13:18 Rev Time 0.00
Received By wjolin Date 2012-10-29 Time 12:37 Sent To  
Notes
2012-10-29 13:18:26801 VILLAGE BOULEVARD - SUITE #303-304
 PERMIT #12100670
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK INFORMATION.
  
 PLEASE PROVIDE A NOTE ON THE LIFE SAFETY PLAN
 INDICATING THE FOLLOWING INFORMATION:
  
 1) ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS
 SHALL NOT EXCEED 50 PERCENT OF THE INDIVIDUAL WALL
 AREA.
  
 2) AN EMERGENCY PLAN TO BE DEVELOPED AND POSTED IN
 BUILDING PRIOR TO OCCUPANCY.
  
 3) EMERGENCY EGRESS DRILLS SHALL BE CONDUCTED MONTHLY.
 ALL DRILLS SHALL BE SOUNDED ON THE FIRE ALARM SYSTEM.
  
 4) FIRE PREVENTION INSPECTIONS SHALL BE CONDUCTED
 MONTHLY BY A TRAINED SENIOR MEMBER OF THE STAFF, AFTER
 WHICH A COPY OF THE LATEST INSPECTION REPORT SHALL BE
 POSTED IN A CONSPICUOUS PLACE IN THE DAY-CARE FACILITY.
 IT SHALL BE THE DUTY OF THE STAFF TO INSPECT ALL EXITS
 DAILY TO ENSURE THAT ALL DOORS AND EXIT PATHS ARE
 MAINTAINED CLEAR OF OBSTRUCTIONS.
  
 TRASH AND CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE
 SITE DAILY. SMOKING SHALL BE PROHIBITED EXCEPT IN
 DESIGNATED EXTERIOR AREAS. ALL OTHER DEMOLITION OR
 CONSTRUCTION AREAS SHALL HAVE "NO SMOKING" SIGNS
 POSTED. WHERE SMOKING IS PERMITTED, SAFE RECEPTACLES
 FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 PER TABLE 7.3.1.2 (NFPA 101 - FLORIDA) THE DAY-CARE
 OCCUPANT LOAD FACTOR SHALL BE 20 SQ.FT. PER PERSON NOT
 35 SQ.FT. PER PERSON.
  
 CONFIRM EXISTING DOORS IN LOBBY #101 ARE EQUIPPED WITH
 PANIC HARDWARE.
  
 EVERY BATHROOM DOOR LOCK SHALL BE DESIGNED TO ALLOW
 OPENING OF THE LOCKED DOOR FROM THE OUTSIDE BY AN
 OPENING DEVICE THAT SHALL BE READILY ACCESSIBLE TO THE
 STAFF.
  
 EACH SMOKE OR FIRE-RATED BARRIER SHALL BE PERMANENTLY
 IDENTIFIED WITH SIGNS OR STENCILING READING FIRE/SMOKE
 BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT
 LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER.
  
 IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM, CORRIDOR WALLS
 SHALL NOT BE REQUIRED TO BE FIRE RATED PROVIDED THAT
 SUCH WALLS FORM SMOKE PARTITIONS.
  
 SHEET E-2: NO EXIT SIGN AND EMERGENCY LIGHT HAS BEEN
 PROVIDED FOR THE SECONDARY EXIT DOOR.
  
 ELECTRICAL: NO MANUAL FIRE ALARM SYSTEM OR SMOKE
 DETECTION PROVIDED PER SECTION 16.3.4 (NFPA 101 -
 FLORIDA).
  
 ENGINEERED FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION
 DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2013-01-09 Cont ID  
Sent By rlecky Date 2013-01-09 Time 09:33 Rev Time 0.00
Received By rlecky Date 2013-01-08 Time 16:49 Sent To  
Notes
2013-01-08 16:49:42TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-01-04 Cont ID  
Sent By wjolin Date 2013-01-04 Time 10:43 Rev Time 0.00
Received By wjolin Date 2012-12-21 Time 16:17 Sent To  
Notes
2012-12-21 16:17:51SENT TO C16 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-12-19 Cont ID  
Sent By jwitmer Date 2012-12-19 Time 16:41 Rev Time 0.00
Received By jwitmer Date 2012-12-07 Time 15:53 Sent To  
Notes
2012-12-10 16:08:23EXPEDITED
 C--16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-12-05 Cont ID  
Sent By lmartine Date 2012-12-05 Time 10:00 Rev Time 0.00
Received By lmartine Date 2012-10-26 Time 09:01 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2012-12-28 Cont ID  
Sent By jwitmer Date 2012-12-28 Time 13:24 Rev Time 0.00
Received By jwitmer Date 2012-12-28 Time 13:24 Sent To  
Notes
2012-12-28 13:25:25IMPACT FEE STAMP - ZERO DUE. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2012-12-19 Cont ID  
Sent By jwitmer Date 2012-12-19 Time 16:40 Rev Time 0.00
Received By jwitmer Date 2012-12-19 Time 16:40 Sent To  
Notes
2012-12-19 16:41:00BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-11-14 Cont ID  
Sent By jwitmer Date 2012-11-14 Time 09:41 Rev Time 0.00
Received By jwitmer Date 2012-11-14 Time 09:41 Sent To  
Notes
2012-11-14 09:42:10BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-12-13 Cont ID  
Sent By lmartine Date 2012-12-13 Time 09:12 Rev Time 0.00
Received By lmartine Date 2012-12-13 Time 09:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-12-05 Cont ID  
Sent By lmartine Date 2012-12-05 Time 09:25 Rev Time 0.00
Received By lmartine Date 2012-12-05 Time 09:25 Sent To  
Notes
2012-12-05 09:59:21*** CORRECTIONS NEED TO MECHANICAL PLANS***
  
 1) MECHANICAL PLAN M1, ROOM #112 HAS EF-1 EXHAUSTION 80
 CFM'S FROM THE ROOM, THE A/C DUCT IS ONLY SUPPLYING 75
 CFM'S OF AIR TO THE ROOM, THIS WOULD PUT THE ROOM AT A
 NEGATIVE PRESSURE. THE CLOTHES DRYER MAY NOT BE ABLE TO
 DISCHARGE TO THE ROOF WHEN THE ROOM IS AT A NEGATIVE
 PRESSURE. PLEASE PROVIDE DOCUMENTATION FROM THE
 MANUFACTURE OF THE DRYER SHOWING THE EQUIPMENT CAN
 OPERATE CORRECTLY UNDER THIS ENVIRONMENT, OR PLEASE
 CORRECT. SEE 2010 FBC/M 304.1.
  
 2) AHU'S 1, 2, 5, & 7 NEED TO SHOW THE OUTDOOR AIR (FA)
 IS BEING DUCTED TO THE ROOF, PLEASE CORRECT. SEE 2010
 FBC/M 401.4.
  
 3) PLAN M-1 SHOWS A RETURN AIR GRILL IN THE KITCHEN
 (ROOM 111). PER 2010 FBC/M 407.1 RETURN AIR MAY NOT BE
 TAKEN FROM A KITCHEN, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY TOM GORDON (HY-BYRD INC.)
 FOR ASSISTANCE CALL LUIS MARTINEZ (561) 805-6710

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-12-19 Cont ID  
Sent By lwagner Date 2012-12-19 Time 16:10 Rev Time 0.00
Received By lwagner Date 2012-12-19 Time 15:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-11-01 Cont ID  
Sent By lwagner Date 2012-11-01 Time 10:35 Rev Time 0.00
Received By lwagner Date 2012-11-01 Time 09:26 Sent To  
Notes
2012-11-01 10:19:09***PROVISO***
 ACCESS REQUIRED FOR WATER HEATER
 502.5 CLEARANCES FOR MAINTENANCE AND REPLACEMENT.

Review Stop Z ZONING
Rev No 1 Status N Date 2012-10-29 Cont ID  
Sent By ajones Date 2012-10-29 Time 15:02 Rev Time 0.00
Received By ajones Date 2012-10-29 Time 15:02 Sent To  
Notes
***NONE***