Plan Review Details - Permit 12100614
| Plan Review Stops For Permit 12100614 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2012-11-30 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-11-30 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-11-29 |
Time |
15:55 |
Sent To |
|
|
| Notes |
| 2012-11-29 16:16:17 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE PLANS ARE TOO SMALL TO BE CLEARLY LEGIBLE. CITY | | | AMENDMENT 107.2.1.4 REQUIRES PLANS TO BE DRAWN TO A | | | MINIMUM OF 1/8" SCALE. PLEASE SUBMIT TWO SETS OF | | | COMPLIANT PLANS. | | | | | | 2) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | | CLARITY TO INDICATE THE NATURE AND EXTENT OF THE WORK | | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | | PROVISIONS OF THE 2010 FLORIDA BUILDING CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS AS | | | DETERMINED BY THE BUILDING OFFICIAL. CITY AMENDMENTS | | | 107.2.1 | | | | | | 3) SPECIFY THE DESIGN CRITERIA ON THE PLANS. | | | (WINDSPEED, EXPOSURE CATEGORY, COMPONENT AND CLADDING | | | PRESSURES) FBCR301.2.1 | | | | | | 4) IT APPEARS THAT THE FLORIDA LICENSE OF THE ENGINEER | | | THAT SIGNED AND SEALED THE CONSTRUCTION DETAILS THAT | | | WERE SUBMITTED IS NULL AND VOID. THEREFORE, THESE | | | DOCUMENTS CAN NOT BE APPROVED PER FLORIDA STATUTES | | | FS471. | | | | | | 5) |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2012-11-09 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-11-09 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-11-09 |
Time |
14:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2012-11-30 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-11-30 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-10-19 |
Time |
09:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2012-11-30 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-11-30 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-11-30 |
Time |
13:56 |
Sent To |
|
|
| Notes |
| 2012-11-30 13:56:58 | AN IMPACT FEE REVIEW BY PALM BEACH COUNTY IS REQUIRED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2012-11-30 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-11-30 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-11-30 |
Time |
13:57 |
Sent To |
|
|
| Notes |
| 2012-11-30 14:10:37 | 2010 FBC | | | | | | DENIED BY MECHANICAL | | | | | | 1) SUBMIT TWO SETS OF HEATING AND COOLING EQUIPMENT | | | SIZING CALCULATIONS AS REQUIRED BY FBCR M1401.3. | | | | | | 2) SUBMIT TWO SETS OF MECHANICAL PLANS THAT SPECIFY THE | | | DUCT SIZES, GRILL SIZES AND CFMS AT EACH SUPPLY. CITY | | | AMENDMENTS 107.3.5.3 | | | | | | 3) SPECIFY THE RETURN AIR GRILL AND DUCT SIZES ON THE | | | PLANS SHOWING COMPLIANCE WITH FBC M1602.4. | | | | | | 4) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLANS. SPECIFY | | | THE LOCATION OF THE EQUIPMENT AND THE SEER FOR THE | | | EQUIPMENT ON THE PLANS. CITY AMENDMENTS 107.3.5.3 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2012-11-19 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2012-11-19 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2012-11-19 |
Time |
14:21 |
Sent To |
|
|
| Notes |
| 2012-11-19 14:28:48 | FBC 2010 PLUMBING REVIEW #1 | | | DENIED: | | | | | | THE EXTERIOR SINK IS NOT PERMITTED TO WET VENT THE | | | BATHROOM GROUP. A LAV. STACK OR VERTICAL DRY VENT IS | | | PERMITTED. (UPDATE 12/12/12 OWNER HAS IDENTIFIED THE | | | EXTERIOR SINK AS A BAR SINK. THIS WOULD BE OK ON THE | | | WET VENT) | | | P3108.1 HORIZONTAL WET VENT PERMITTED. | | | ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS | | | LOCATED ON THE SAME FLOOR LEVEL ARE PERMITTED TO BE | | | VENTED BY A HORIZONTAL WET VENT. THE WET VENT SHALL BE | | | CONSIDERED THE VENT FOR THE FIXTURES AND SHALL EXTEND | | | FROM THE CONNECTION OF THE DRY VENT ALONG THE DIRECTION | | | OF THE FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM | | | FIXTURE DRAIN CONNECTION. EACH FIXTURE DRAIN SHALL | | | CONNECT HORIZONTALLY TO THE HORIZONTAL BRANCH BEING WET | | | VENTED OR SHALL HAVE A DRY VENT. EACH WET-VENTED | | | FIXTURE DRAIN SHALL CONNECT INDEPENDENTLY TO THE | | | HORIZONTAL WET VENT. ONLY THE FIXTURES WITHIN THE | | | BATHROOM GROUPS SHALL CONNECT TO THE WET-VENTED | | | HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL | | | DISCHARGE DOWNSTREAM OF THE HORIZONTAL WET VENT. | | | P3108.2.1 HORIZONTAL WET VENT. ...NOT MORE THAN ONE | | | WET-VENTED FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF | | | THE DRY-VENTED FIXTURE DRAIN CONNECTION. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2012-10-24 |
|
|
Cont ID |
|
| Sent By |
mdekle |
Date |
2012-10-24 |
Time |
|
Rev Time |
|
| Received By |
mdekle |
Date |
2012-10-24 |
Time |
|
Sent To |
|
|
| Notes |
|
|
|