Plan Review Details - Permit 12100614
Plan Review Stops For Permit 12100614
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-11-30 Cont ID  
Sent By rmcdouga Date 2012-11-30 Time 13:56 Rev Time 0.00
Received By rmcdouga Date 2012-11-29 Time 15:55 Sent To  
Notes
2012-11-29 16:16:172010 FBC
  
 DENIED BY BUILDING
  
 1) THE PLANS ARE TOO SMALL TO BE CLEARLY LEGIBLE. CITY
 AMENDMENT 107.2.1.4 REQUIRES PLANS TO BE DRAWN TO A
 MINIMUM OF 1/8" SCALE. PLEASE SUBMIT TWO SETS OF
 COMPLIANT PLANS.
  
 2) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THE 2010 FLORIDA BUILDING CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS AS
 DETERMINED BY THE BUILDING OFFICIAL. CITY AMENDMENTS
 107.2.1
  
 3) SPECIFY THE DESIGN CRITERIA ON THE PLANS.
 (WINDSPEED, EXPOSURE CATEGORY, COMPONENT AND CLADDING
 PRESSURES) FBCR301.2.1
  
 4) IT APPEARS THAT THE FLORIDA LICENSE OF THE ENGINEER
 THAT SIGNED AND SEALED THE CONSTRUCTION DETAILS THAT
 WERE SUBMITTED IS NULL AND VOID. THEREFORE, THESE
 DOCUMENTS CAN NOT BE APPROVED PER FLORIDA STATUTES
 FS471.
  
 5)

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-11-09 Cont ID  
Sent By rlecky Date 2012-11-09 Time 15:48 Rev Time 0.00
Received By rlecky Date 2012-11-09 Time 14:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-11-30 Cont ID  
Sent By rmcdouga Date 2012-11-30 Time 15:04 Rev Time 0.00
Received By rmcdouga Date 2012-10-19 Time 09:11 Sent To  
Notes
2012-10-19 09:11:55RO7

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-11-30 Cont ID  
Sent By rmcdouga Date 2012-11-30 Time 13:56 Rev Time 0.00
Received By rmcdouga Date 2012-11-30 Time 13:56 Sent To  
Notes
2012-11-30 13:56:58AN IMPACT FEE REVIEW BY PALM BEACH COUNTY IS REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-11-30 Cont ID  
Sent By rmcdouga Date 2012-11-30 Time 13:57 Rev Time 0.00
Received By rmcdouga Date 2012-11-30 Time 13:57 Sent To  
Notes
2012-11-30 14:10:372010 FBC
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO SETS OF HEATING AND COOLING EQUIPMENT
 SIZING CALCULATIONS AS REQUIRED BY FBCR M1401.3.
  
 2) SUBMIT TWO SETS OF MECHANICAL PLANS THAT SPECIFY THE
 DUCT SIZES, GRILL SIZES AND CFMS AT EACH SUPPLY. CITY
 AMENDMENTS 107.3.5.3
  
 3) SPECIFY THE RETURN AIR GRILL AND DUCT SIZES ON THE
 PLANS SHOWING COMPLIANCE WITH FBC M1602.4.
  
 4) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLANS. SPECIFY
 THE LOCATION OF THE EQUIPMENT AND THE SEER FOR THE
 EQUIPMENT ON THE PLANS. CITY AMENDMENTS 107.3.5.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-11-19 Cont ID  
Sent By lwagner Date 2012-11-19 Time 14:29 Rev Time 0.00
Received By lwagner Date 2012-11-19 Time 14:21 Sent To  
Notes
2012-11-19 14:28:48FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 THE EXTERIOR SINK IS NOT PERMITTED TO WET VENT THE
 BATHROOM GROUP. A LAV. STACK OR VERTICAL DRY VENT IS
 PERMITTED. (UPDATE 12/12/12 OWNER HAS IDENTIFIED THE
 EXTERIOR SINK AS A BAR SINK. THIS WOULD BE OK ON THE
 WET VENT)
 P3108.1 HORIZONTAL WET VENT PERMITTED.
 ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS
 LOCATED ON THE SAME FLOOR LEVEL ARE PERMITTED TO BE
 VENTED BY A HORIZONTAL WET VENT. THE WET VENT SHALL BE
 CONSIDERED THE VENT FOR THE FIXTURES AND SHALL EXTEND
 FROM THE CONNECTION OF THE DRY VENT ALONG THE DIRECTION
 OF THE FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM
 FIXTURE DRAIN CONNECTION. EACH FIXTURE DRAIN SHALL
 CONNECT HORIZONTALLY TO THE HORIZONTAL BRANCH BEING WET
 VENTED OR SHALL HAVE A DRY VENT. EACH WET-VENTED
 FIXTURE DRAIN SHALL CONNECT INDEPENDENTLY TO THE
 HORIZONTAL WET VENT. ONLY THE FIXTURES WITHIN THE
 BATHROOM GROUPS SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE HORIZONTAL WET VENT.
 P3108.2.1 HORIZONTAL WET VENT. ...NOT MORE THAN ONE
 WET-VENTED FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF
 THE DRY-VENTED FIXTURE DRAIN CONNECTION.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status P Date 2012-10-24 Cont ID  
Sent By mdekle Date 2012-10-24 Time   Rev Time  
Received By mdekle Date 2012-10-24 Time   Sent To  
Notes
***NONE***